SIST EN IEC 62561-8:2026
(Main)Lightning protection system components (LPSC) - Part 8: Requirements for components for electrically insulated LPS
- Abstract
IEC 62561-8:2026 specifies the requirements and tests for components used for electrically insulated LPS. These components, which can reduce the separation distance, are as follows:
- insulating stand-offs, used in conjunction with an air-termination system and down-conductors with the aim of maintaining the proper separation distance;
- insulating down‑conductors, including their specific fasteners.
Testing of insulating stand-offs and insulating down-conductor components for an explosive atmosphere is not covered by this document. This first edition cancels and replaces IEC TS 62561-8 published in 2018. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to IEC TC 62561-8:2018:
a) title and scope of the standard has been adjusted;
b) the document has been updated in line with IEC 60068-2-52:2017 on salt mist treatment;
c) the document has been updated in line with ISO 22479:2019 on humid sulphureous atmosphere treatment;
d) two different possible example configurations for pull out tests have been introduced;
e) additional information on pollution has been included;
f) an alternate test arrangement for high voltage impulse test has been included;
g) a new normative Annex H for applicability of previous tests has been introduced;
h) pass criteria for high voltage impulse testing updated;
i) explanation on high voltage impulse testing with negative polarity has been added.
- Status
- Published
- Public Enquiry End Date
- 29-Sep-2025
- Publication Date
- 13-Sep-2026
- Technical Committee
- STZ - Lightning protection
- Current Stage
- 6060 - National Implementation/Publication (Adopted Project)
- Start Date
- 04-Sep-2026
- Due Date
- 09-Nov-2026
- Completion Date
- 14-Sep-2026
SIST EN IEC 62561-8:2026 is the Slovenian adoption of EN IEC 62561-8:2026, published by SIST from IEC 62561-8:2026. It specifies requirements and tests for lightning protection system components (LPSC) used in electrically insulated LPS, mainly insulating stand-offs and insulating down-conductors. For manufacturers, test laboratories, installers and specifiers, it shows how these parts are classified, marked, documented and type-tested so they can maintain the required separation distance in a lightning protection system designed according to the IEC 62305 series.
What does SIST EN IEC 62561-8:2026 specify?
SIST EN IEC 62561-8:2026 covers the requirements and tests for components used in electrically insulated LPS. The scope is focused on two product groups that reduce the separation distance: insulating stand-offs and insulating down-conductors, including the specific fasteners for insulating down-conductors.
The document is organized into:
- Clause 1 scope
- Clause 2 normative references
- Clause 3 terms and definitions
- Clause 4 insulating stand-off
- Clause 5 insulating down-conductor
- Annexes A to H, with a mix of normative and informative material
| Annex | What it covers |
|---|---|
| A | Corrosion resistance tests |
| B | Resistance to ultraviolet light |
| C | Flow chart of tests for insulating stand-offs |
| D | Flow chart of tests for insulating down-conductors |
| E | Informative high voltage impulse test to determine the correction factor k for insulating stand-offs |
| F | Informative installation arrangement test for the influence of supporting structures on separation distance |
| G | Alternate test arrangement for the high voltage impulse test |
| H | Applicability of previous tests |
The scope excludes testing of insulating stand-offs and insulating down-conductor components for an explosive atmosphere.
What are the key requirements of SIST EN IEC 62561-8:2026?
SIST EN IEC 62561-8:2026 sets out type-test based requirements for two component families. In practice, the standard asks the manufacturer to define the product class, prove mechanical and electrical performance, provide installation information, and show that the marking remains legible after simple wear tests.
Insulating stand-offs
Clause 4 requires an insulating stand-off to retain, support and insulate the conductor under lightning impulse stress and under mechanical and environmental loads. That matters because these parts carry the air-termination system or down-conductors while keeping safe distance from the structure.
The stand-off is classified by conductor clamping arrangement and by mounting, with classes for free-standing and rigidly fixed products. This helps users match the component to the actual installation method instead of treating all stand-offs as interchangeable.
Clause 4 also requires construction that avoids burrs, flash and similar defects, plus compatibility with the conductor and mounting surface. The stand-off must also withstand corrosion and UV exposure typical of the installation environment.
For electrical performance, the stand-off has an insulating length and an effective length. The effective length, or the effective length correction factor k, is what is compared with the required separation distance s from IEC 62305-3. In practice, this means the component must prove that it can substitute for the separation distance required in the lightning protection design.
Insulating down-conductors
Clause 5 classifies insulating down-conductors by lightning current carrying capability and also classifies their fasteners by material and fixing arrangement. That matters because the conductor, its insulation and its fixings must all work together under lightning stress.
The down-conductor shall be suitable for the required separation distance s and shall use dedicated fasteners so that the conductor and insulation are not damaged during installation. The manufacturer also has to provide documentation that lets the installer select and fit the product correctly.
Clause 5 requires the metallic parts to withstand corrosion and the non-metallic parts to withstand UV exposure. It also requires the down-conductor to meet the mechanical requirements of IEC 62561-2, unless the product proves its electrical performance by the relevant test.
For electrical performance, the standard requires two different checks: lightning current carrying capability and high voltage impulse withstand for the equivalent separation distance. This is what proves that the product can both carry the lightning current and keep the insulation distance needed in service.
Type testing, specimen preparation and pass criteria
For both product families, the document uses type tests on three specimens and specifies the order of tests in Annex C or Annex D. The specimens are assembled as in normal use, with the manufacturer’s recommended conductors, connectors and tightening torques. That means the test result reflects the product as it is actually installed.
The tests cover documentation review, marking, construction, environmental conditioning, mechanical tests and electrical tests. If one specimen fails, the failed sequence is repeated on three new specimens, and no failure is allowed in the repeat sequence.
The high voltage impulse tests use comparison arrangements and negative polarity. For stand-offs, the test verifies the correction factor k; for down-conductors, it verifies the equivalent separation distance s. Annex G allows an alternate rod-plane arrangement, and Annex F gives a test for installation arrangements where supporting structures can influence the dielectric performance.
Reporting and EMC
Clauses 4.5 and 5.7 define the content of the test report. The report has to identify the specimen, the test methods, the equipment, the measuring instruments, the results and the pass or fail statement. The standard also treats the products as passive with respect to electromagnetic influences.
What terms does SIST EN IEC 62561-8:2026 define?
SIST EN IEC 62561-8:2026 defines the terms that make the electrical and mechanical checks unambiguous.
- Insulating stand-off - A non-metallic or composite component that supports and insulates the air-termination system or down-conductors at the required separation distance.
- Insulating down-conductor - A conductor with an electrical insulation layer used to reduce the separation distance.
- Equivalent separation distance s - The corrected distance value used instead of the stand-off insulating length when checking the required separation distance.
- Effective length correction factor k - The factor used to relate the insulating stand-off geometry to its electrical withstand behavior.
- Effective length - The air-gap length that has breakdown behavior equivalent to the insulating stand-off.
- Installation arrangement - The complete installation with one or more insulating down-conductors and supporting means used to hold the distance and support the conductor mechanically.
- Steepness correction factor - A factor used in the impulse tests to account for the effect of steep-front voltages and subsequent negative short strokes.
Who uses SIST EN IEC 62561-8:2026?
SIST EN IEC 62561-8:2026 is used by manufacturers of lightning protection components, especially producers of insulating stand-offs, insulating down-conductors and their fasteners. They use it to design products, prepare type tests, write installation instructions and decide what to mark on the product or packaging.
Testing and certification laboratories use it to set up the environmental, mechanical and high voltage impulse tests and to prepare the test report. Installers and lightning protection designers use it when choosing components for an LPS based on the IEC 62305 series. Quality managers and buyers use it to check whether a product’s declared class, separation distance, marking and documentation fit the intended application.
What changed in SIST EN IEC 62561-8:2026 from the previous edition?
SIST EN IEC 62561-8:2026 is the first edition and it cancels and replaces IEC TS 62561-8:2018. The document states these technical changes relative to the 2018 technical specification:
- title and scope adjusted
- updated to IEC 60068-2-52:2017 for salt mist treatment
- updated to ISO 22479:2019 for humid sulphureous atmosphere treatment
- two example pull-out test configurations added
- additional information on pollution added
- alternate high voltage impulse test arrangement added
- new normative Annex H on applicability of previous tests added
- pass criteria for high voltage impulse testing updated
- explanation added for high voltage impulse testing with negative polarity
Which standards are used with SIST EN IEC 62561-8:2026?
SIST EN IEC 62561-8:2026 relies on a set of normative references for test equipment, environmental conditioning and related lightning protection parts.
- IEC 60060-2:2025 - measuring systems for high-voltage tests
- IEC 60068-2-52:2017 - salt mist environmental testing
- IEC 60068-2-75:2014 - hammer impact testing
- IEC 61083-1 and IEC 61083-2 - instruments and software for impulse measurements
- IEC 62305-3 - the lightning protection design basis for separation distance
- IEC 62561-1:2023 - connection components and lightning impulse current test methods
- IEC 62561-2:2025 - conductors and earth electrodes
- IEC 62561-4 - conductor fasteners
- ISO 4892-2, ISO 4892-3:2024 and ISO 4892-4 - UV exposure methods for plastics
- ISO 6957:1988 - ammonia atmosphere stress-corrosion test for copper alloys
- ISO 22479:2019 - humid sulphurous atmosphere corrosion test
The introduction also places the document within the IEC 62305 series for lightning protection of structures, and the bibliography lists IEC 62305-1:2024, IEC 62305-2:2024 and IEC 62305-4:2024 as related parts.
What does the SIST EN IEC 62561-8:2026 document contain?
SIST EN IEC 62561-8:2026 contains classification tables, type-test sequences, specimen preparation rules, environmental test methods, mechanical test methods, electrical test arrangements and report requirements. It includes formulas and comparison arrangements for the high voltage impulse tests, plus figures showing typical stand-off and down-conductor setups and alternate arrangements.
The annexes add the practical laboratory content: salt mist and corrosion procedures in Annex A, UV conditioning options in Annex B, flow charts in Annex C and D, informative methods for determining k in Annex E, an installation arrangement test in Annex F, an alternate high voltage setup in Annex G, and a legacy-use provision in Annex H. In practice, this means the document is mainly a laboratory and product-verification standard for proving that electrically insulated LPS components perform as declared.
Relations
- Effective Date
- 14-Jul-2026
- Effective Date
- 14-Jul-2026
- Effective Date
- 14-Jul-2026
- Effective Date
- 14-Jul-2026
- Effective Date
- 14-Jul-2026
- Effective Date
- 14-Jul-2026
- Effective Date
- 14-Jul-2026
- Effective Date
- 14-Jul-2026
- Effective Date
- 14-Jul-2026
- Effective Date
- 14-Jul-2026
- Effective Date
- 14-Jul-2026
- Effective Date
- 18-Aug-2026
- Effective Date
- 18-Aug-2026
Get Certified
Connect with accredited certification bodies for this standard

DIBt (Deutsches Institut für Bautechnik)
German Institute for Building Technology.
DIN CERTCO
DIN Group product certification.

IMQ S.p.A. (Certification)
Italian electrical product certification.
Sponsored listings
Frequently Asked Questions
SIST EN IEC 62561-8:2026 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Lightning protection system components (LPSC) - Part 8: Requirements for components for electrically insulated LPS". This standard covers: IEC 62561-8:2026 specifies the requirements and tests for components used for electrically insulated LPS. These components, which can reduce the separation distance, are as follows: - insulating stand-offs, used in conjunction with an air-termination system and down-conductors with the aim of maintaining the proper separation distance; - insulating down‑conductors, including their specific fasteners. Testing of insulating stand-offs and insulating down-conductor components for an explosive atmosphere is not covered by this document. This first edition cancels and replaces IEC TS 62561-8 published in 2018. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to IEC TC 62561-8:2018: a) title and scope of the standard has been adjusted; b) the document has been updated in line with IEC 60068-2-52:2017 on salt mist treatment; c) the document has been updated in line with ISO 22479:2019 on humid sulphureous atmosphere treatment; d) two different possible example configurations for pull out tests have been introduced; e) additional information on pollution has been included; f) an alternate test arrangement for high voltage impulse test has been included; g) a new normative Annex H for applicability of previous tests has been introduced; h) pass criteria for high voltage impulse testing updated; i) explanation on high voltage impulse testing with negative polarity has been added.
IEC 62561-8:2026 specifies the requirements and tests for components used for electrically insulated LPS. These components, which can reduce the separation distance, are as follows: - insulating stand-offs, used in conjunction with an air-termination system and down-conductors with the aim of maintaining the proper separation distance; - insulating down‑conductors, including their specific fasteners. Testing of insulating stand-offs and insulating down-conductor components for an explosive atmosphere is not covered by this document. This first edition cancels and replaces IEC TS 62561-8 published in 2018. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to IEC TC 62561-8:2018: a) title and scope of the standard has been adjusted; b) the document has been updated in line with IEC 60068-2-52:2017 on salt mist treatment; c) the document has been updated in line with ISO 22479:2019 on humid sulphureous atmosphere treatment; d) two different possible example configurations for pull out tests have been introduced; e) additional information on pollution has been included; f) an alternate test arrangement for high voltage impulse test has been included; g) a new normative Annex H for applicability of previous tests has been introduced; h) pass criteria for high voltage impulse testing updated; i) explanation on high voltage impulse testing with negative polarity has been added.
SIST EN IEC 62561-8:2026 is classified under the following ICS (International Classification for Standards) categories: 29.020 - Electrical engineering in general; 91.120.40 - Lightning protection. The ICS classification helps identify the subject area and facilitates finding related standards.
SIST EN IEC 62561-8:2026 has the following relationships with other standards: It is inter standard links to SIST EN IEC 62561-2:2026, SIST EN ISO 4892-3:2024, SIST EN IEC 60060-2:2025, SIST EN IEC 62561-1:2023, SIST EN IEC 62305-3:2024, SIST EN IEC 60068-2-52:2018, SIST EN IEC 62561-4:2024, SIST EN 60068-2-75:2014, SIST EN ISO 22479:2022, SIST EN 61083-2:2013, SIST EN ISO 4892-2:2013, SIST EN IEC 62305-4:2024, SIST EN 16282-3:2017. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
SIST EN IEC 62561-8:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
Contents
- 1 Scope
- 2 Normative references
- 3 Terms and definitions
- 3.1 insulating stand-off
- 3.2 effective length correction factor
- 3.3 steepness correction factor
- 3.4 effective length
- 3.5 insulating length
- 3.6 equivalent separation distance
- 3.7 down-conductor
- 3.8 insulating down-conductor
- 3.9 steepness correction factor
- 3.10 clearance of the comparison arrangement
- 3.11 time to chopping
- 3.12 effective material insulating factor
- 3.13 installation arrangement
- 3.14 fasteners for insulating down-conductors
- 4 Insulating stand-off
- 4.1 Classification
- 4.2 Requirements
- 4.3 Tests
- 4.4 Electromagnetic compatibility (EMC)
- 4.5 Structure and content of the test report
- 5 Insulating down-conductor
- 5.1 Classification
- 5.2 Lightning current carrying capability
- 5.3 Preferred values of equivalent separation distance (s )
- 5.4 Requirements
- 5.5 Tests
- 4 Installation arrangement test 5.5.7.3 C Depends on the
- 5.6 Electromagnetic compatibility (EMC)
- 5.7 Structure and content of the test report
- Annex A
- Annex B
- Annex C
- Annex D
- Annex E
- Annex F
- Annex G
- Annex H
- Bibliography
INTRODUCTION This part of IEC 62561 deals with the requirements and tests for lightning protection system components (LPSC), specifically components for electrically insulated LPS, used for the installation of a lightning protection system (LPS) designed and implemented according to the
IEC 62305 series [1] .
Numbers in square brackets refer to the Bibliography.
SIST EN IEC 62561-8:2026
1 Scope
This document specifies the requirements and tests for components used for electrically insulated LPS. These components, which can reduce the separation distance, are as follows:
- insulating stand-offs, used in conjunction with an air-termination system and downconductors with the aim of maintaining the proper separation distance;
- insulating down-conductors, including their specific fasteners. Testing of insulating stand-offs and insulating down-conductor components for an explosive atmosphere is not covered by this document.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
IEC 60060-2:2025, High-voltage test techniques - Part 2: Measuring systems IEC 60068-2-52:2017, Environmental testing - Part 2-52: Tests - Test Kb: Salt mist, cyclic (sodium chloride solution) IEC 60068-2-75:2014, Environmental testing - Part 2-75: Tests - Test Eh: Hammer tests IEC 61083-1, Instruments and software used for measurements in high-voltage and high-current tests - Part 1: Requirements for instruments for impulse tests IEC 61083-2, Instruments and software used for measurement in high-voltage and high-current tests - Part 2: Requirements for software for tests with impulse voltages and currents IEC 62305-3, Protection against lightning - Part 3: Physical damage to structures and life hazard IEC 62561-1:2023, Lightning protection system components (LPSC) - Part 1: Requirements for connection components IEC 62561-2:2025, Lightning protection system components (LPSC) - Part 2: Requirements for conductors and earth electrodes IEC 62561-4, Lightning protection system components (LPSC) - Part 4: Requirements for conductor fasteners ISO 4892-2, Plastics - Methods of exposure to laboratory light sources - Part 2: Xenon-arc lamps ISO 4892-3:2024, Plastics - Methods of exposure to laboratory light sources - Part 3:
Fluorescent UV lamps ISO 4892-4, Plastics - Methods of exposure to laboratory light sources - Part 4: Open-flame carbon-arc lamps ISO 6957:1988, Copper alloys - Ammonia test for stress corrosion resistance
SIST EN IEC 62561-8:2026
ISO 22479:2019, Corrosion of metals and alloys - Sulfur dioxide test in a humid atmosphere (fixed gas method)
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply. ISO and IEC maintain terminological databases for use in standardization at the following addresses:
- IEC Electropedia: available at http://www.electropedia.org/
- ISO Online browsing platform: available at http://www.iso.org/obp
3.1 insulating stand-off
non-metallic or composite component, consisting of the insulator and fixation parts, designed to retain, support and insulate the air-termination system or down-conductors at a required separation distance
3.2 effective length correction factor
k
factor evaluating the different withstand voltages of air gaps and insulators under test voltages
3.3 steepness correction factor
is_st <insulating stand-off> factor considering the effect of higher steepness and the probability of occurrence of subsequent negative short strokes on the disruptive voltage of an insulating stand-off Note 1 to entry: The value is defined in the test procedure.
3.4 effective length
eff <insulating stand-off> length (distance) of an air gap with equivalent breakdown behaviour to an insulating stand-off
3.5 insulating length
st <insulating stand-off> shortest measured clearance distance between two conductive elements of different electrical potential, for example between a metallic conductor fastener and a mounting assembly
3.6 equivalent separation distance
s e corrected distance value to be used instead of the insulating length of a stand-off distance value equivalent to the separation distance of conventional down-conductors required in IEC 62305-3
SIST EN IEC 62561-8:2026
3.7 down-conductor
part of the down-conductor system intended to conduct lightning current from the air-termination system to the earth-termination system of the LPS [SOURCE: IEC 62561-2:2025, 3.7]
3.8 insulating down-conductor
conductor provided with a layer of electric insulation with the purpose to reduce the separation distance
3.9 steepness correction factor
dc_st <insulating down-conductor> factor considering the effect of higher steepness and the probability of occurrence of subsequent negative short strokes on the withstand voltage of insulating down-conductors during testing Note 1 to entry: The value is defined in the test procedure.
3.10 clearance of the comparison arrangement
s
gap distance of the comparison arrangement used for verification of the effective length correction factor k and separation distance s x e
3.11 time to chopping
T
virtual parameter defined as the interval between the virtual origin and the instant of chopping
3.12 effective material insulating factor
k m coefficient of material which depends on the electrical insulation material Note 1 to entry: See IEC 62305-3.
3.13 installation arrangement
installation containing one or more insulating down-conductors and additional installation means (according to the manufacturer's instruction) to keep the defined separation distance and to support the insulating down-conductor mechanically Note 1 to entry: One example is given in Figure F.1.
3.14 fasteners for insulating down-conductors
metallic, non-metallic or composite components designed to retain and support down-conductor installed at intervals along the length of the conductors
SIST EN IEC 62561-8:2026
4 Insulating stand-off
4.1 Classification
4.1.1 General
Classification of the product depends on the withstand capability of mechanical forces.
4.1.2 According to conductor clamping arrangement
There are two classes of insulating stand-off according to the conducting clamping arrangement:
a) conductor fasteners that are designed to clamp the conductor; b) conductor fasteners that are designed to clamp but allow axial movement of the conductor.
4.1.3 According to mounting
Regarding the mounting, there are two classes of insulating stand-off:
a) free standing; b) rigidly fixed on a structure.
4.2 Requirements
4.2.1 General
An insulating stand-off shall retain, support and insulate the conductor when subjected to the stress of a lightning discharge under high impulse voltage and shall withstand the mechanical and environmental influences such as perpendicular and axial compression loads caused by the weight of the supported conductor along with snow, ice, wind and thermal expansion or contraction of the conductor.
An insulating stand-off shall be compatible with the conductor it is supporting and the surface to which it is fixed.
4.2.2 Construction
4.2.2.1 General
An insulating stand-off shall be so designed and constructed that a) the surface is free from burrs, flash moulding, deformation and similar inconsistencies which are likely to inflict injury to the installer or user, and b) it carries the perpendicular and axial compression loads caused by the weight of the supported conductor along with snow, ice, wind and thermal expansion/contraction of the conductor.
Compliance to a) is checked by visual inspection and compliance to b) is checked in accordance with 4.3.6.2 and 4.3.6.4.
4.2.2.2 Corrosion resistance
An insulating stand-off shall withstand the effects of corrosion typical of the environment to which it is exposed.
Compliance is checked by testing in accordance with 4.3.5.1.
SIST EN IEC 62561-8:2026
4.2.2.3 UV light resistance
An insulating stand-off shall withstand the effects of UV exposure typical of the environment to which it is exposed.
Compliance is checked by testing in accordance with 4.3.5.2.
4.2.3 Mechanical requirements
4.2.3.1 General
An insulating stand-off can consist of a mounting assembly, an insulator and a conductor fastener as shown in Figure 1 and Figure 2. The manufacturer of the insulating stand-off shall guarantee with appropriate mechanical tests or calculations that the stand-off fulfills the requirements stated in their documentation.
Compliance is checked by testing in accordance with 4.3.
Key 1 mounting assembly 2 insulator 3 metallic conductor fastener 4 conductor l insulating length st Figure 1 – Typical insulating stand-off with a metallic fastener
SIST EN IEC 62561-8:2026
Key 1 mounting assembly 2 insulator 3 non metallic conductor fastener 4 conductor l insulating length st Figure 2 – Typical insulating stand-off with a non-metallic fastener
4.2.3.2 Mounting assembly
The mounting assembly, which holds the insulator in position on the structure, shall withstand mechanical stress.
Compliance is checked by testing in accordance with 4.3.6.
4.2.3.3 Insulator
The insulator shall withstand mechanical stress, for example pull out force, impact strength and bending load.
Compliance is checked by testing in accordance with 4.3.6.
4.2.3.4 Conductor fastener
The conductor fastener, which is part of the insulating stand-off, shall comply with the requirements and tests of IEC 62561-4.
4.2.4 Electrical requirements
An insulating stand-off shall be capable of withstanding the very high impulse voltages generated by a lightning strike.
SIST EN IEC 62561-8:2026
An insulating stand-off has an insulating length l , as shown in Figure 1 and Figure 2. This is st different from its effective length l , which is the value to be compared to the required eff separation distance s according to IEC 62305-3. This effective length of the insulating stand-off shall be equal to or greater than the required separation distance s. The isolating capability of an insulating stand-off can be provided by either a) its effective length l , or eff b) its effective length correction factor k .
The effective length correction factor k is determined from the effective length l and the x eff insulating length l as showed in Formula (1):
st I eff
k = (1)
I st
Compliance is checked by testing in accordance with 4.3.1, 4.3.2 and 4.3.7. For the purpose of calculating the separation distance as used in IEC 62305-3, the value of the effective material insulating factor k can be set equal to the value k . m x NOTE A value of k = 0,7 for GFRP, PE and PVC insulating stand-offs under normal operating conditions can be
used, based on laboratory test results [2].
4.2.5 Documentation and installation instructions
The manufacturer or supplier of the insulating stand-off shall provide adequate information in the installation instructions to ensure that the installer can select and install the component in a suitable and safe manner in accordance with the requirements of IEC 62305-3. Compliance is checked by inspection in accordance with 4.3.3.
4.2.6 Marking
4.2.6.1 Content of marking
An insulating stand-off shall be marked with a) the manufacturer's or responsible vendor's name, logo or trademark, and b) the product identification or type.
Where it is not possible to make these marks directly onto the product, they shall be provided on the smallest supplied packaging.
Compliance is checked by visual inspection.
4.2.6.2 Durability and legibility
Marking on the product shall be durable and easily legible.
NOTE Marking can be applied for example by moulding, pressing, engraving, printing, adhesive labels or water slide transfers.
Compliance is checked by testing in accordance with 4.3.4.
SIST EN IEC 62561-8:2026
4.3 Tests
4.3.1 General test conditions
Tests according to this document are type tests. These tests are of such a nature that, after they have been performed, they are not required to be repeated unless changes are made to the materials, design or type of manufacturing process, which can change the performance characteristics of the insulating stand-off.
All tests are carried out with the specimens assembled and installed as in normal use according to the manufacturer's or supplier's instructions, using the recommended conductor materials, sizes and tightening torques.
The insulating length l of all specimens shall be (500 ± 5) mm unless otherwise specified in st the relevant test procedure. The manufacturer shall prepare the test specimens according to Figure 3 for a metallic fastener or Figure 4 for a non-metallic fastener. Dimensions in millimetres
Key 1 mounting assembly 2 insulator 3 metallic conductor fastener 4 conductor l insulating length st Figure 3 – Typical insulating stand-off with a metallic fastener prepared for testing
SIST EN IEC 62561-8:2026
Dimensions in millimetres
Key 1 mounting assembly 2 insulator 3 non-metallic conductor fastener 4 conductor l insulating length st Figure 4 – Typical insulating stand-off with a non-metallic fastener prepared for testing This document cannot cover all possible types of insulating stand-offs and the way of fixing them on various surfaces of different materials. When required for these applications, agreement should be obtained between the test engineer and manufacturer on the specific testing regime.
An insulating stand-off classified by the manufacturer in more than one of the classifications in 4.1 shall be tested for each applicable category.
Type tests are carried out on three specimens according to the test sequence indicated in Table 1. Within any test sequence, the tests shall be carried out in the order given in Annex C. A specimen has passed a test sequence of Table 1 if all the requirements of the relevant test clauses and the relevant pass criteria have been fulfilled.
If the required number of specimens passes a test sequence, the design of the insulating stand-off is acceptable for that test sequence. If two or more test specimens fail a test sequence, the insulating stand-off does not comply with this document. In the event that a single specimen does not pass a test, this test, and those preceding in the same test sequence that could have influenced the result of this test, shall be repeated with three new specimens. No failure of any specimen is allowed in the second sequence of tests. One set of three specimens can be used for more than one test sequence if agreed by the manufacturer.
SIST EN IEC 62561-8:2026
The applicants, when submitting the first set of specimens, can also submit an additional set of specimens that can be necessary should one specimen fail. The test house shall then, without further request, test the additional set of specimens and shall only reject if a further failure occurs. If the additional set of specimens is not submitted at the same time, a failure of one specimen shall entail rejection.
Tests on non-metallic specimens shall not commence earlier than 168 h from the time of manufacture.
NOTE The value of 168 h is a curing time and is a typical value based on experience. The test shall be performed in free air, with an ambient temperature between +15 °C and +40 °C and relative humidity between 25 % and 75 %.
A torque meter having a resolution of at least 0,5 Nm and an accuracy of at least 4 % shall be used for all tightening operations.
Table 1 – Type test requirements for an insulating stand-off Test Identification of Test description Sub-clause Number of specimens sequence sets 1 Documentation 4.3.3 A 1 Marking test 4.3.4 A 3 Construction 4.3.6.1 A 3
Corrosion test 4.3.5.1 E 3 Pull out test 4.3.6.4 E 3 9 or more due to surface
UV light test 4.3.5.2 B, C, D deterioration during high voltage test.
a Bending test 4.3.6.2 B 3 a Impact test of the insulator 4.3.6.3 3 C 3 or more due to surface a Electrical test 4.3.7 deterioration during high voltage D test.
a Upon the agreement between the manufacturer and the laboratory, a set of specimens previously tested can also be suitable for use in other tests of this document as well.
4.3.2 General test setup
Unless otherwise specified by the manufacturer, the conductors and specimens shall be cleaned by using a suitable degreasing agent followed by cleaning in demineralized water and drying. They shall then be assembled according to the manufacturer's installation instructions, for example with the recommended conductors and tightening torques. The tightening torque should be applied in a steady and uniform manner. Any insulating stand-off accommodating a range of conductor's variance in diameter shall be tested on the minimum conductor size recommended.
SIST EN IEC 62561-8:2026
4.3.3 Documentation
The manufacturer or responsible vendor shall provide the following in their literature:
a) classifications according to 4.1; b) maximum and minimum conductor dimensions; c) conductor materials to be used; d) type of mounting surface to be fixed; e) recommended method of assembly, installation and fixing to the mounting surface; f) pull out force; g) bending force; h) mechanical strength (e.g. load torque, support load); i) k coefficient.
Compliance is checked by inspection.
4.3.4 Marking test
The durability of marking shall be tested by easy rubbing for ten times with a piece of cloth soaked with water.
Markings made by moulding, pressing or engraving are not subjected to this test. The specimen is deemed to have passed the test if the marking remains legible.
4.3.5 Environmental influence tests
4.3.5.1 Corrosion test
An insulating stand-off with metallic components, including its conductor fastener and mounting assembly, shall be subjected to environmental influence tests consisting of a salt mist test as specified in Clause A.2 followed by a humid sulphurous atmosphere test as specified in Clause A.3. An additional test by an ammonia atmosphere as specified in Clause A.4 shall be carried out on an insulating stand-off having parts made of copper alloy with a copper content less than 80 %.
The specimens are deemed to have passed the test if no base metals of the metallic components show any corrosive deterioration visible to normal or corrected vision. NOTE White rust, patina and surface oxidation are not considered as corrosive deterioration.
4.3.5.2 UV light test
The insulating part (insulator) of the insulating stand-off shall be subjected to an environmental test consisting of an ultraviolet light test as specified in Annex B. The length of the test specimen shall be sufficient so that, after the UV light test, a complete insulating stand-off can be assembled for further tests requiring an insulating length l of st (500 ± 5) mm.
The specimens are deemed to have passed the test if there are no signs of disintegration and cracks visible under normal or corrected vision.
SIST EN IEC 62561-8:2026
4.3.5.3 Pollution test
As the voltage stress for insulating stand-offs and insulating down-conductors is in the range of microseconds, pollution is not effective. Therefore, a specific test is not applicable [3], [4].
4.3.6 Mechanical tests
4.3.6.1 Construction
The surface of the insulating stand-off shall be free from burrs associated with the cutting process, moulding joint deformation and similar inconsistencies which are likely to inflict injury to the installer or user.
Compliance is checked by visual and manual inspection.
...