SIST EN 1047-2:2009
(Main)Secure storage units - Classification and methods of test for resistance to fire - Part 2: Data rooms and data container
Secure storage units - Classification and methods of test for resistance to fire - Part 2: Data rooms and data container
This part of the European Standard EN 1047 specifies requirements for data rooms and data containers. It includes a method of test for the determination of the ability of data rooms and data containers to protect temperature and humidity sensitive data media (see 3.5) and hardware systems (see 3.6) from the effects of fire. A test method for measuring the resistance to mechanical stress (impact test) provided by data rooms type B and data containers is also specified. Requirements are also specified for test specimens, the technical documentation of the test specimens, materials specimens, physical fittings, the correlation of test specimens with the technical documentation and the preparation for type testing as well as test procedures. In addition, a scheme to classify data rooms and data containers from the test results is given (see Table 2). As well as providing protection against fire, correctly installed data rooms and data containers offer protection against impacts caused by failure during fire of components and objects external to the data room or data container. Data rooms and data containers having the same design, protection and construction features (type and thickness of construction and protective materials, rebate geometry, lockings, doors, etc.) will only be given the same protection classification as that of the test specimen if the tolerances are within the ranges specified in Table 1.
Wertbehältnisse - Klassifizierung und Methoden zur Prüfung des Widerstandes gegen Brand - Teil 2: Datensicherungsräume und Datensicherungscontainer
Dieser Teil der Europäischen Norm EN 1047 legt Anforderungen an Datensicherungsräume und Datensicherungscontainer
fest. Er umfasst eine Prüfmethode zur Ermittlung der Widerstandsfähigkeit von
Datensicherungsräumen und Datensicherungscontainern zum Schutz von temperatur- und feuchtigkeitsempfindlichen
Datenträgern (siehe 3.5) und Hardwaresystemen (siehe 3.6) vor Brandeinwirkung. Ferner wird
eine Prüfmethode zur Messung des Widerstandes gegen mechanische Beanspruchung (Stoßprüfung) auf
Datensicherungsräume Typ B und Datensicherungscontainer festgelegt.
Außerdem sind Anforderungen für die Probekörper, Technische Dokumentation der Probekörper,
Materialproben, Einbauten, Übereinstimmung von Probekörpern mit der Technischen Dokumentation und die
Vorbereitung der Typprüfung sowie die Prüfverfahren definiert.
Ferner wird ein Schema zur Klassifizierung von Datensicherungsräumen und Datensicherungscontainern
entsprechend ihrem Prüfergebnis gegeben (siehe Tabelle 2).
Neben dem Schutz vor Bränden bieten sachgemäß installierte Datensicherungsräume und Datensicherungscontainer
zusätzlich Schutz gegen Stöße aufgrund eines brandbedingten Versagens von Bauteilen und
Objekten, die sich außerhalb des Datensicherungsraumes oder Datensicherungscontainers befinden.
Datensicherungsräume und Datensicherungscontainer, die über dieselbe Konstruktion, denselben Schutz und
Aufbau (Art und Dicke der Konstruktions- und Schutzmaterialien, Anordnung der Falze, Verschlüsse, Türen
usw.) verfügen, können nur dann in die Güteklasse wie der Probekörper eingestuft werden, wenn die
Toleranzen nach Tabelle 1 eingehalten sind.
ANMERKUNG Diese Europäische Norm regelt nicht die Verwendung des Datensicherungsraumes im Sinne des
Baurechts der jeweiligen Länder. Bei der Errichtung von Datensicherungsräumen sollten die jeweiligen nationalen
Anforderungen zu berücksichtigt werden.
Unités de stockage en lieu sûr - Classification et méthodes d'essai de résistance au feu - Partie 2: Conteneurs et chambres réfractaires
La présente partie de la norme européenne EN 1047 spécifie les exigences relatives aux conteneurs et chambres réfractaires. Elle présente une méthode d'essai permettant de déterminer la capacité des chambres et conteneurs réfractaires à protéger des supports d’informations (voir 3.5) sensibles à la température et à l'humidité, ainsi que les systèmes matériels (voir 3.6), contre les effets d'un incendie. Une méthode d’essai est également proposée pour mesurer la résistance à une force mécanique (essai de résistance à l’impact) des chambres réfractaires de type B et des conteneurs réfractaires.
De plus, des exigences sont spécifiées pour les spécimens d’essai, la documentation technique devant accompagner les spécimens d’essai, les échantillons de matériels, les équipements matériels, la corrélation des spécimens d’essai avec la documentation technique, ainsi que la préparation des essais de type et les procédures d'essai.
Un plan est également présenté (voir Tableau 2) permettant une classification des chambres et conteneurs réfractaires à partir des résultats des essais.
Les chambres et les conteneurs réfractaires correctement installés assurent une protection contre les impacts dus à des incidents, au cours de l’incendie, de composants et d’objets externes.
Les chambres et conteneurs réfractaires ayant les mêmes caractéristiques de conception, de protection et de construction (types et épaisseurs des matériaux de construction et de protection, géométrie des feuillures, verrouillages, portes, etc.) appartiennent seulement à la même classification de protection que celle du spécimen d'essai si les tolérances se trouvent dans les fourchettes spécifiées dans le Tableau 1.
NOTE La présente norme européenne ne réglemente pas l’utilisation des chambres réfractaires par le moyen de lois sur la construction, applicables dans les pays respectifs.
Varnostne shranjevalne enote - Klasifikacija in metode preskušanja odpornosti proti ognju - 2. del: Prostori in vsebniki za shranjevanje podatkov
General Information
Relations
Standards Content (Sample)
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Varnostne shranjevalne enote - Klasifikacija in metode preskušanja odpornosti proti ognju - 2. del: Prostori in vsebniki za shranjevanje podatkovWertbehältnisse - Klassifizierung und Methoden zur Prüfung des Widerstandes gegen Brand - Teil 2: Datensicherungsräume und DatensicherungscontainerUnités de stockage en lieu sûr - Classification et méthodes d'essai de résistance au feu - Partie 2: Conteneurs et chambres réfractairesSecure storage units - Classification and methods of test for resistance to fire - Part 2: Data rooms and data container35.220.99Druge naprave za shranjevanje podatkovOther data storage devices13.310Varstvo pred kriminalomProtection against crime13.220.40Sposobnost vžiga in obnašanje materialov in proizvodov pri gorenjuIgnitability and burning behaviour of materials and productsICS:Ta slovenski standard je istoveten z:EN 1047-2:2009SIST EN 1047-2:2009en,fr01-november-2009SIST EN 1047-2:2009SLOVENSKI
STANDARDSIST EN 1047-2:20001DGRPHãþD
SIST EN 1047-2:2009
EUROPEAN STANDARDNORME EUROPÉENNEEUROPÄISCHE NORMEN 1047-2August 2009ICS 13.220.40; 13.310; 35.020Supersedes EN 1047-2:1999
English VersionSecure storage units - Classification and methods of test forresistance to fire - Part 2: Data rooms and data containerUnités de stockage en lieu sûr - Classification et méthodesd'essai de résistance au feu - Partie 2: Conteneurs etchambres réfractairesWertbehältnisse - Klassifizierung und Methoden zurPrüfung des Widerstandes gegen Brand - Teil 2:Datensicherungsräume und DatensicherungscontainerThis European Standard was approved by CEN on 23 July 2009.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the CEN Management Centre or to any CEN member.This European Standard exists in three official versions (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as theofficial versions.CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMITÉ EUROPÉEN DE NORMALISATIONEUROPÄISCHES KOMITEE FÜR NORMUNGManagement Centre:
Avenue Marnix 17,
B-1000 Brussels© 2009 CENAll rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 1047-2:2009: ESIST EN 1047-2:2009
EN 1047-2:2009 (E) 2 Contents Page Foreword .3Introduction .41Scope .52Normative references .63Terms and definitions .74Requirements and classification.95Test specimens, technical documentation, material samples, physical fittings and correlation . 105.1Data room type A test specimens . 105.2Data room type B test specimens . 125.3Data container test specimens . 145.4Test specimen with floor constructions other than according to 5.1, 5.2 and 5.3 . 145.5Test specimen for walls and/or ceiling constructions different from those specified in 5.1, 5.2 and 5.3 . 145.6Test specimen – other construction variants . 155.7Technical documentation of the test specimens . 155.8Material samples . 155.9Fire-retarding sealings . 155.10Correlation of test specimen and technical documentation . 166Test methods . 166.1General . 166.2Test apparatus . 166.3Preparation of test specimens . 176.4Preparation of furnace . 276.5Conditioning including air conditioning . 296.5.1Data room . 296.5.2Data containers . 296.5.3Wall and floor panels (data rooms, data containers) . 296.6Test procedure . 296.6.1Fire endurance test . 296.6.2Impact test . 306.6.3Comparison tests of respectively floor constructions, alternative wall and ceiling constructions and other construction variants . 316.6.4Examinations . 326.7Test report . 327Labelling . 33Bibliography . 34 SIST EN 1047-2:2009
EN 1047-2:2009 (E) 3 Foreword This document (EN 1047-2:2009) has been prepared by Technical Committee CEN/TC 263 “Secure storage of cash, valuables and data media”, the secretariat of which is held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by February 2010, and conflicting national standards shall be withdrawn at the latest by February 2010. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights. This document supersedes EN 1047-2:1999. Part 1 of this Standard has been published as: EN 1047-1, Secure storage units — Classification and methods of test for resistance to fire - Part 1: Data cabinets and diskette inserts According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. SIST EN 1047-2:2009
EN 1047-2:2009 (E) 4 Introduction The testing conditions given in this European Standard provide a basis for simulating fires to determine, in a reproducible way, the fire resistance of data rooms and data containers. The values for the maximum temperature increase in protection classes R60D and C60D specified in accordance with Table 2 in this European Standard relate to the relatively short time of high temperature exposure occurring during a fire test; in general, they are not experienced by data media and systems hardware stored in data rooms and data containers in the normal and correct way. EN 1363-1 establishes the general principles for determining the fire resistance of various elements of construction when subjected to standard fire exposure conditions. Alternative and additional procedures to meet special requirements are given in EN 1363-2. The development of the temperatures and the relative humidity in the interior of a data room and data container cannot be measured under the standard series
EN 1363. The sensitivity of media (see 3.5) and hardware systems (see 3.6) to temperature and humidity requires additional protection with regard to excessively high temperatures and relative humidity, proof of which cannot be furnished through type tests in accordance with the European Standards EN 1363-1 and EN 1363-2. This additional protection requires a series of product solutions, the performance of which is type tested and certified on the basis of the standard series EN 1047. EN 1047-1 covers the type testing of data cabinets as freestanding units. EN 1047-2 covers the type testing of data rooms and data containers. For wall, ceiling and floor elements type tested within the framework of this system test, proof of an additional protection can be furnished in accordance with the European Standards EN 1363-1 and EN 1363-2.
SIST EN 1047-2:2009
EN 1047-2:2009 (E) 5 1 Scope This part of the European Standard EN 1047 specifies requirements for data rooms and data containers. It includes a method of test for the determination of the ability of data rooms and data containers to protect temperature and humidity sensitive data media (see 3.5) and hardware systems (see 3.6) from the effects of fire. A test method for measuring the resistance to mechanical stress (impact test) provided by data rooms type B and data containers is also specified. Requirements are also specified for test specimens, the technical documentation of the test specimens, materials specimens, physical fittings, the correlation of test specimens with the technical documentation and the preparation for type testing as well as test procedures. In addition, a scheme to classify data rooms and data containers from the test results is given (see Table 2). As well as providing protection against fire, correctly installed data rooms and data containers offer protection against impacts caused by failure during fire of components and objects external to the data room or data container. Data rooms and data containers having the same design, protection and construction features (type and thickness of construction and protective materials, rebate geometry, lockings, doors, etc.) will only be given the same protection classification as that of the test specimen if the tolerances are within the ranges specified in Table 1. NOTE This European Standard does not regulate the use of data rooms in the meaning of the building laws of the respective countries. In the construction of data rooms, the respective national requirements should be considered. SIST EN 1047-2:2009
EN 1047-2:2009 (E) 6
Table 1 — Permitted differences between the series products and the test specimen
Minimum Maximum
Data rooms type A and type B
internal height - 50 % + 50%
internal width - 70 % no limit 1)
internal length - 70 % no limit 1)
Data containers
internal height - 50 % increase not permitted
internal width - 15 % + 50 % 3)
internal length - 15 % + 50 %
Door openings (clear opening dimensions)
height - 50 % increase not permitted
width - 25 % increase not permitted Compact thickness of walls, the ceiling, floor and door - 3 % 2) no limit Openings (outside dimensions) e.g. ventilation openings no limit + 15 %
1) For the type test, load bearing structures may be installed in the test specimen. Proof of an existing load bearing structure in the fire endurance test (see 6.6.1) is required if the dimensions of the series product differ from those of the test specimen.
2) Deviations from the tolerance (- 3 % for walls, ceiling, floor and door) are only allowed upon permission by the certification body and/or testing laboratory. 3) Enlargement of the internal width of the data container (maximum + 50 %) in connection with the installation of additional wall panels is only allowed upon permission by the certification body and/or testing laboratory respectively.
2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 206-1, Concrete — Part 1: Specification, performance, production and conformity EN 1300, Secure storage units — Classification for high security locks according to their resistance to unauthorized opening SIST EN 1047-2:2009
EN 1047-2:2009 (E) 7 EN 1363-1:1999, Fire resistance tests — Part 1: General requirements EN 1363-2:1999, Fire resistance tests — Part 2: Alternative and additional procedures EN 1364-1:1999, Fire resistance tests for non-loadbearing elements — Part 1: Walls EN 1365-1, Fire resistance tests for loadbearing elements — Part 1: Walls EN 1365-2, Fire resistance tests for loadbearing elements — Part 2: Floors and roofs EN 60584-1, Thermocouples — Part 1: Reference tables (IEC 60584-1:1995) EN 61515, Mineral insulated thermocouple cables and thermocouples (IEC 61515:1995) 3 Terms and definitions For the purposes of this document, the following terms and definitions apply. 3.1 test specimen data room type A, data room type B or data container designed to protect media, hardware systems and valuables against the effects of fire, or construction elements (e.g. floor, wall) of the data room or data container 3.2 data room type A room consisting of walls, ceiling and floor which provides the fire resistance specified in this standard (see Table 2) when installed within walls and ceilings fulfilling the requirements for integrity, insulation and load bearing capacity for 90 min according to EN 1365-1 and EN 1365-2, respectively. The floor of the data room type A shall satisfy the fire resistance requirements specified in this standard and provide the same protection against the penetration of water vapour as the wall and ceiling construction 3.2.1 exterior cell construction built for testing to simulate the room into which the internal cell of the data room type A in accordance with 3.2 is installed 3.2.2 internal cell independent and self-supporting construction intended for installation as a data room type A in a building situation which satisfies the requirements for walls, ceiling and floor specified in 3.2 3.3 data room type B room consisting of walls, ceiling and floor which provides the fire resistance specified in this standard (see Table 2) when the floor onto which it is installed fulfils the requirements for integrity, insulation and load bearing capacity for 90 min according to EN 1365-2. The floor of the data room type B shall satisfy the fire resistance requirements specified in this standard and provide the same protection against the penetration of water vapour as the wall and ceiling construction 3.4 data container structure which can be transported in one piece or in modular parts and which provides the fire resistance specified in this standard (see Table 2) when the floor onto which it is installed fulfils the requirements for integrity, insulation and load bearing capacity for 90 min according to EN 1365-2. The floor of the data container shall satisfy the fire resistance requirements specified in this standard and provide the same protection against the penetration of water vapour as the wall and ceiling construction SIST EN 1047-2:2009
EN 1047-2:2009 (E) 8 NOTE Data containers differ from data cabinets according to EN 1047-1 insofar as they contain computer hardware and therefore have fire-resistant sealings and openings. 3.5 data media material holding information, including paper documents, magnetic tapes, films, cassettes, optical disks and video and audio cassettes except those that lose their data at temperatures below 75 °C and relative air humidity above 85 % 3.6 hardware system electronic system which stores, processes, moves or transmits data and/or has an archive function NOTE Types of hardware systems include host computers, master computers, master control modules, PI tape drives, network computers, MB tape drives with robot support, etc. 3.7 door access to, respectively, a data room or data container equipped with at least one lock in accordance with
EN 1300 (Class A) 3.8 fire-retarding sealings permanently sealable openings through which cables and/or pipes enter a data room or data container (see 4.3) 3.9 openings openings for the installation of e.g. ventilation facilities (see 4.4) 3.10 load bearing structure supporting and reinforcing building components which guarantee the load bearing capacity of ceiling and/or wall elements
SIST EN 1047-2:2009
EN 1047-2:2009 (E) 9 4 Requirements and classification 4.1 Data rooms and data containers shall provide protection against fire (see Clause 6) and shall be classified in accordance with Table 2. Table 2 — Protection class requirements Protection class
Fire endurance test (6.6.1) Impact test (6.6.2) Comparison tests 2)
Lock class according to EN 1300
Maximum temperature increase
Maximum relative humidity
Maximum temperature increase
Maximum relative humidity
R60D Type A
50 K
85 %
1)
Assessment according to 2)
Assessment according to 2)
A
R60D Type B
50 K
85 %
Integrity to 3.1.9 and 10.4.5 of EN 1363-1:1999
Assessment according to
2)
Assessment according to
2)
A
C60D
50 K
85 %
Integrity to 3.1.9 and 10.4.5 of EN 1363-1:1999
Assessment according to
2)
Assessment according to
2)
A where
R
refers to data rooms;
C
refers to data containers;
60
refers to the 60 minute fire exposure time;
D characterizes the kind of data media and hardware systems which may be protected and includes all
kinds of data media except those that lose their data at temperatures below 75 °C and relative air
humidity above 85 %. 1) Data rooms of type A are only installed within walls and ceilings with minimum fire integrity (see 3.2) and are therefore not tested for impact resistance. 2) Assessment of comparison test results for floor constructions, alternative constructions for walls and ceiling or other construction variants. If the construction of the floor differs from the wall or ceiling construction (see 5.4 and 6.6.3) or the construction of the walls and ceiling differs from the type-tested construction (see 5.5 and 6.6.3) and for all other construction variants (see 5.6 and 6.6.3), the results of the comparison test conducted on the specimens are assessed according to the following formula: 50 – ûTA ≥ ûTB – ûTC ûTA = temperature rise in K during the type-test of the data room resp. data container; ûTB = temperature rise in K above the floor construction, the alternative construction or other construction variant during the comparison test (see 6.6.3); ûTC = temperature rise in K above the comparison specimen (respectively wall or ceiling panel and construction variant of the type test) during the comparison test.
SIST EN 1047-2:2009
EN 1047-2:2009 (E) 10 4.2 Doors of data rooms shall be self-closing in case of fire. 4.3 Data rooms and data containers may have permanently closed fire-retarding sealings (see 3.8) through which cables and pipes may enter. 4.4 Openings (see 3.9) in data rooms and data containers shall be closed in case of fire (e.g. through self-closing devices). 5 Test specimens, technical documentation, material samples, physical fittings and correlation 5.1 Data room type A test specimens 5.1.1 An exterior cell shall be erected in the furnace, and within it, a data room type A test specimen shall be installed as an internal cell in the manner as if it were a data room being installed within walls and ceilings (see 3.2). The exterior cell shall be positioned in the furnace in accordance with Figure 10.
5.1.2 The walls, ceiling and floor of the exterior cell shall be constructed of individual prefabricated units, each (100 ± 5) mm thick, made of reinforced concrete grade C20/25 to EN 206-1 with a density of
(2 400 ± 200) kg/m3, and shall be connected to one another. The exterior cell shall have the following internal dimensions: height
(2 600 ± 100) mm; width (2 800 ± 100) mm; length (3 800 ± 100) mm. For the installation of the instrumentation for measuring the temperatures and air humidity in the test specimen that wall of the test specimen which is not exposed to fire shall be modified (see 6.3.2 and Figure 4). NOTE 1 In order to minimize the influence of the combined water in the concrete prefabricated units forming the exterior cell, they shall be manufactured at least 100 days before the beginning of the type test and shall be protected from humidity during storage.
NOTE 2 Bolts may be used to connect the concrete prefabricated units and measures taken to protect the bolts against the effects of fire. 5.1.3 The test specimen for the data room type A must at least have one door (see 3.7), fire-retarding sealings (see 3.8) and openings (see 3.9).
NOTE Construction variants may be tested in accordance with 6.6.3. 5.1.4 The walls, ceiling and floor of the internal cell may be of different design and construction. However, these construction elements shall all be of the same materials with the same thickness and construction, and shall have a minimum of two joints (see Figure 1). Where a load bearing structure is used, the ceiling of the internal cell shall be divided in two fields in the longitudinal direction of the test specimen (see Figure 2). The resulting two ceiling segments shall again each have two joints. Additional joints and possible load bearing structures (see 3.10) shall be tested, if this is required for any design for which certification is sought. 5.1.5 Fire-retarding sealings and openings shall be fitted in the top third at the short sides of the test specimen (see 6.3.4 g) and Figure 6). SIST EN 1047-2:2009
EN 1047-2:2009 (E) 11 5.1.6 In case the structure of the floor of the internal cell is different from the design of walls and the ceiling of the internal cell, respectively, a floor construction comparison test in accordance with 6.6.3 shall be made.
Key
1 Exterior cell (precast concrete units) 2 Internal cell 3 Joints Figure 1 — Picture showing a data room Type A SIST EN 1047-2:2009
EN 1047-2:2009 (E) 12
Key
1 Load bearing structure 2 Top element 3 Joints
4 Ceiling segment Figure 2 — Picture showing an example for the testing of a data room Type A or B using a load bearing ceiling structure (horizontal plan with internal dimensions)
5.2 Data room type B test specimens 5.2.1 The structural design of the walls, ceiling and floor of the data room may be different. These construction elements shall all be of the same materials with the same thickness and construction and have at least two joints (see Figure 3). Where a load bearing structure is used, the ceiling shall be divided in two fields in the longitudinal direction of the test specimen (see Figure 2). The resulting two ceiling segments shall again each have two joints. Additional joints and possible load bearing structures (see 3.10) shall be tested if this is required for any design for which certification is sought. SIST EN 1047-2:2009
EN 1047-2:2009 (E) 13 The test specimen shall have the following internal dimensions: Height (2 600 ± 100) mm; Width (2 800 ± 100) mm; Length (3 800 ± 100) mm. For the installation of the instrumentation for measuring the temperatures and air humidity in the test specimen that wall of the test specimen which is not exposed to fire shall be modified (see 6.3.2 and
Figure 4).
5.2.2 The test specimen for a data room type B shall at least have one door (see 3.7), fire-retarding sealings (see 3.8) and openings (see 3.9). NOTE Construction variants may be tested in accordance with 6.6.3. 5.2.3 Fire-retarding sealings and openings shall be fitted in the top third at the short sides of the test specimen (see 6.3.4 g and Figure 6). 5.2.4 An additional wall or ceiling panel with the dimensions 3,0 m x 3,0 m shall be specified by the testing laboratory for the impact test (see 6.6.2). The panel shall have the same construction, materials and thickness as the data room test specimen wall and ceiling, respectively. Each and any gap shall be considered in the test specimen. 5.2.5
In case the structure of the walls and the ceiling, respectively, is different from that of the floor, a floor construction comparison test in accordance with 6.6.3 shall be made.
Key
1 Wall construction (single- and/or multi-wall) 2 Joints Figure 3 — Picture showing a data room Type B (horizontal plan)
SIST EN 1047-2:2009
EN 1047-2:2009 (E) 14 5.3 Data container test specimens 5.3.1 The test specimen must be modified at the base (see 6.3.2 and Figure 4) for the installation of the instrumentation for measuring the temperatures and air humidity in the test specimen. The structure of the walls, ceiling and floor may be of different design. These construction elements shall, however, be of the same material with the same thickness and construction. In case of a modular design, joints in the test specimen may need to be considered. The test specimen shall have the following maximum internal dimensions:
Height (2 000 ± 50) mm;
Width (
800 ± 50) mm;
Length (1 050 ± 50) mm. 5.3.2 The data container test specimen shall at least have one door (see 3.7), fire-retarding sealings (see 3.8) and openings (see 3.9).
NOTE Construction variants may be tested in accordance with 6.6.3. 5.3.3 An additional wall or ceiling panel with the maximum dimensions of the series products according to the technical documentation (see 5.7) shall be specified by the testing laboratory for the impact test (see 6.6.2). The panel shall have the same construction with the same materials and thickness as the data container test specimen wall and ceiling, respectively. In case of a modular design, joints in the test specimen may need to be considered. 5.3.4
In case the structure of the walls and the ceiling, respectively, is different from that of the floor, a floor construction comparison test in accordance with 6.6.3 shall be made. 5.4 Test specimen with floor constructions other than according to 5.1, 5.2 and 5.3
Data rooms and data containers having a floor construction different from that of the walls and the ceiling, respectively, shall be subjected to a type test for a comparison of floor constructions in accordance with 6.6.3 for the measurement of temperature and air humidity. For this purpose, two specimens are erected side by side on a furnace and exposed to flames from below (see 6.3.7, Figure 9). The comparison test specimen shall comply with the type-tested wall or ceiling construction, as decided by the applicant. The second test specimen shall comply with the differing floor construction erected on a 140 mm thick reinforced concrete base. On both test specimens, the temperatures and the air humidity shall be measured in the isolated rooms arranged above the specimen of the type-tested construction and the specimen of the planned floor construction respectively. During the floor comparison test, both test specimens under assessment shall be tested together with at least one joint and where applicable the connection between floor and walls. The concrete base does not have a joint.
5.5 Test specimen for walls and/or ceiling constructions different from those specified in 5.1, 5.2 and 5.3 Alternative constructions for walls and/or ceilings which differ from those type-tested may be assessed by me
...