Ventilation for Buildings - Performance testing of components for residential buildings - Multifunctional balanced ventilation units for single family dwellings, including heat pumps

This Standard specifies the laboratory test methods and test requirements for aerodynamic, energy rating and acoustic performance, of multifunctional balanced units intended for use in a single dwelling.
In the case of units consisting of several parts, this standard applies only to those designed and supplied as a complete package with the mount instructions.
It covers unit that contain at least, within one or more casing:
   supply and exhaust air fans;
   air filters
   common control system.
And one or more of the additional components
   Air to water heat pump;
   Air to air heat pump
   air-to-air heat exchanger
except units including either an air to air heat exchanger and/or exhaust air to supply air heat pump which are already covered by EN 13141-7.
A non-exhaustive list of possible configurations of multifunctional units covered by this standard is given in Clause 5.
The standard does not cover the thermal aspects of humidity transfer in the air-to-air heat exchanger.
This standard does not deal with non-ducted units on supply and extract air side.
This standard does not deal with collective units (centralised or semi-centralised systems)
These multifunctional balanced units can be connected to ground heat exchanger for air preheating, solar collector or other heating systems. This standard does not cover the testing of these additional components.
This standard does not cover units including combustion engine driven compression heat pumps and sorption heat pump.

Lüftung von Gebäuden - Leistungsprüfung von Bauteilen für Wohnbauten - Multifunktionale Zu-/Abluft-Lüftungseinheiten für Einzelwohnungen, einschließlich Wärmepumpen

Diese Norm legt die Anforderungen an Verfahren und Prüfungen im Labor für aerodynamische Energiebemessungswerte und die akustische Leistung multifunktionaler abgeglichener Lüftungseinheiten fest, die für die Verwendung in Einzelwohnungen bestimmt sind.
Für den Fall, dass die Einheit aus mehreren Bauteilen besteht, gilt diese Norm nur für solche Teile, die als vollständige Gerätebaugruppe mit Bauanleitung konstruiert und geliefert werden.
Diese Norm behandelt Einheiten, die wenigstens das Folgende, in einem oder mehreren Gehäuse, enthalten:
   Zu- und Fortluftventilatoren,
   Luftfilter,
   allgemeine Steuer- und Regeleinrichtungen.
Sowie eines oder mehrere der zusätzlichen Bauteile:
   Luft/Wasser-Wärmepumpe,
   Luft/Luft-Wärmepumpe,
   Luft/Luft-Wärmeübertrager
unter Ausnahme von Einheiten, einschließlich Luft/Luft-Wärmeübertrager und/oder Fortluft/Zuluft-Wärme-pumpen, die durch EN 13141-7 behandelt werden.
Eine nicht vollständige Liste der möglichen Konfigurationen multifunktionaler Einheiten, die in dieser Norm behandelt werden, ist in Abschnitt 5 enthalten.
Diese Norm behandelt keine thermischen Aspekte der Feuchteübertragung in einem Luft/Luft-Wärme¬über-trager.
Diese Norm behandelt keine Einheiten ohne Luftleitungen an der Luftabgabe- und Ansaugseite.
Diese Norm befasst sich nicht mit Sammeleinheiten (Zentral- oder Semizentralsysteme).
Diese multifunktionalen, abgeglichenen Einheiten können zum Zwecke des Vorwärmens der Luft mit einem Erdwärmetauscher, mit Solarkollektoren oder anderen Heizungsanlagen verbunden werden. Diese Norm behandelt nicht das Prüfen dieser zusätzlichen Bauteile.
Diese Norm behandelt keine Einheiten, die Kompressionswärmepumpen mit Antrieb durch Verbrennungs-motor und Sorptionswärmepumpen umfassen.

Ventilation des bâtiments - Essais de performance des composants pour les bâtiments résidentiels - Centrales de ventilation double flux multifonctions pour les logements individuels, comprenant des pompes à chaleur

La présente norme spécifie les méthodes d'essai en laboratoire et les exigences d'essai relatives aux essais de performance aéraulique, acoustique et de détermination de l'énergie de dispositifs équilibrés multifonctionnels destinés à être utilisés dans un logement individuel.
Dans le cas de dispositifs composés d'éléments séparés, la présente norme ne s'applique qu'aux dispositifs conçus et fournis comme un ensemble avec les instructions de montage.
Elle couvre les dispositifs contenant, dans une ou plusieurs enveloppes, au moins :
   des ventilateurs de soufflage et d'extraction d'air ;
   des filtres à air ;
   un système commun de régulation,
et un ou plusieurs des éléments supplémentaires suivants :
   pompe à chaleur air/eau ;
   pompe à chaleur air/air ;
   échangeur thermique air/air,
à l'exception des dispositifs comprenant un échangeur thermique air/air et/ou une pompe à chaleur air extrait/air fourni, déjà couverts par l'EN 13141-7.
Une liste non exhaustive de configurations possibles pour les dispositifs multifonctionnels couverts par la présente norme est donnée à l'Article 5.
La présente norme ne couvre pas les aspects thermiques du transfert de l'humidité dans l'échangeur thermique air/air.
La présente norme ne traite pas des dispositifs non raccordés du côté air fourni et air repris.
La présente norme ne traite pas des dispositifs collectifs (systèmes centralisés ou semi-centralisés).
Ces dispositifs équilibrés multifonctionnels peuvent être raccordés à un échangeur thermique au sol pour préchauffage de l'air, à un capteur solaire ou à d'autres systèmes de chauffage. La présente norme ne couvre pas les essais effectués sur ces éléments supplémentaires.
La présente norme ne couvre pas les dispositifs comprenant des pompes à chaleur entraînées par un moteur à combustion et des pompes à chaleur à sorption.

Prezračevanje stavb - Preskušanje lastnosti sestavnih delov za stanovanjske stavbe - Večnamenske uravnotežene prezračevalne enote za posamična stanovanja, vključno s toplotnimi črpalkami

Ta standard določa laboratorijske preskusne metode in preskusne zahteve za aerodinamične, energetske in akustične lastnosti večnamenskih uravnoteženih enot za uporabo v eni stanovanjski enoti.
Pri enotah, sestavljenih iz več delov, se ta standard uporablja samo za tiste enote, ki so projektirane in dostavljene kot celoten paket z navodili za montažo.
Zajema enote, ki v enem ali več ohišjih vsebujejo vsaj:
dovodne in odvodne zračne ventilatorje,
zračne filtre,
običajni nadzorni sistem.
In enega ali več dodatnih sestavnih delov:
zračno/vodno toplotno črpalko,
zračno toplotno črpalko,
zračni izmenjevalnik toplote,
razen enot, vključno z zračnim izmenjevalnikom toplote in/ali odvodnim zrakom za oskrbo zračne toplotne črpalke, ki so že zajete v standardu EN 13141-7.
Neizčrpen seznam možnih konfiguracij večnamenskih enot, zajetih v tem standardu, je podan v točki 5.
Standard ne zajema toplotnih vidikov prenosa vlage v zračnem izmenjevalniku toplote.
Ta standard ne obravnava brezkanalnih enot na strani za dovod in odvod zraka.
Ta standard ne obravnava kolektivnih enot (centralizirani ali polcentralizirani sistemi).
Te večnamenske uravnotežene enote je mogoče povezati s talnim izmenjevalnikom toplote za predhodno segrevanje zraka, sončni zbiralnik ali druge ogrevalne sisteme. Ta standard ne zajema preskušanja teh dodatnih sestavnih delov.
Ta standard ne zajema enot, vključno s kompresijskimi toplotnimi črpalkami, ki jih poganja motor z notranjim izgorevanjem, ter absorpcijskimi in adsorpcijskimi toplotnimi črpalkami.

General Information

Status
Published
Public Enquiry End Date
30-May-2013
Publication Date
07-Mar-2017
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
10-Feb-2017
Due Date
17-Apr-2017
Completion Date
08-Mar-2017

Buy Standard

Standard
EN 16573:2017 - BARVE
English language
60 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day
Draft
prEN 16573:2013
English language
59 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 16573:2017
01-april-2017
3UH]UDþHYDQMHVWDYE3UHVNXãDQMHODVWQRVWLVHVWDYQLKGHORY]DVWDQRYDQMVNH
VWDYEH9HþQDPHQVNHXUDYQRWHåHQHSUH]UDþHYDOQHHQRWH]DSRVDPLþQD
VWDQRYDQMDYNOMXþQRVWRSORWQLPLþUSDONDPL
Ventilation for Buildings - Performance testing of components for residential buildings -
Multifunctional balanced ventilation units for single family dwellings, including heat
pumps
Lüftung von Gebäuden - Leistungsprüfung von Bauteilen für Wohnbauten -
Multifunktionale Zu-/Abluft-Lüftungseinheiten für Einzelwohnungen, einschließlich
Wärmepumpen
Ventilation des bâtiments - Essais de performance des composants pour les bâtiments
résidentiels - Centrales de ventilation double flux multifonctions pour les logements
individuels, comprenant des pompes à chaleur
Ta slovenski standard je istoveten z: EN 16573:2017
ICS:
91.140.30 3UH]UDþHYDOQLLQNOLPDWVNL Ventilation and air-
VLVWHPL conditioning systems
SIST EN 16573:2017 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 16573:2017

---------------------- Page: 2 ----------------------

SIST EN 16573:2017


EN 16573
EUROPEAN STANDARD

NORME EUROPÉENNE

February 2017
EUROPÄISCHE NORM
ICS 91.140.30
English Version

Ventilation for Buildings - Performance testing of
components for residential buildings - Multifunctional
balanced ventilation units for single family dwellings,
including heat pumps
Ventilation des bâtiments - Essais de performance des Lüftung von Gebäuden - Leistungsprüfung von
composants pour les bâtiments résidentiels - Centrales Bauteilen für Wohnbauten - Multifunktionale Zu-
de ventilation double flux multifonctions pour les /Abluft-Lüftungseinheiten für Einzelwohnungen,
logements individuels, comprenant des pompes à einschließlich Wärmepumpen
chaleur
This European Standard was approved by CEN on 22 July 2016.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.

This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and United Kingdom.





EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2017 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 16573:2017 E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------

SIST EN 16573:2017
EN 16573:2017 (E)
Contents Page
European foreword . 4
1 Scope . 5
2 Normative references . 5
3 Terms, definitions and symbols . 6
3.1 Terms and definitions . 6
3.2 Symbols . 7
4 Functions . 8
5 Description and testing of multifunctional units. 8
6 Performance testing of aerodynamic characteristics . 13
6.1 Leakages . 13
6.1.1 Test method . 13
6.1.2 Requirements . 13
6.2 Air flow/pressure curve . 13
6.3 Reference point for aerodynamic conditions . 13
6.4 Pressure drop setting . 14
7 Performance testing of thermal characteristics . 15
7.1 General . 15
7.2 Air flow settings and uncertainty . 15
7.2.1 General . 15
7.2.2 Configuration without any recirculation . 16
7.2.3 Configuration with recirculation from outdoor air to exhaust air . 16
7.2.4 Configuration with recirculation from extract to supply air . 17
7.2.5 Configuration with two recirculations . 17
7.3 Ventilation heat recovery performance. 18
7.3.1 General . 18
7.3.2 Air flow test conditions . 18
7.3.3 Test procedure . 19
7.3.4 Data to be recorded . 19
7.3.5 Calculations . 21
7.4 Ventilation and domestic hot water production . 21
7.4.1 General . 21
7.4.2 Test procedure . 21
7.4.3 Data to be recorded . 22
7.4.4 Performance rating calculations . 24
7.5 Ventilation with hydronic space heating/cooling . 24
7.5.1 General . 24
7.5.2 Temperature test conditions . 25
7.5.3 Test procedure . 27
7.5.4 Data to be recorded . 27
7.5.5 Performance rating calculations . 29
7.6 Ventilation combined with supply air heating/cooling . 31
7.6.1 General . 31
7.6.2 Temperature test conditions . 31
7.6.3 Test procedure . 31
7.6.4 Data to be recorded . 32
2

---------------------- Page: 4 ----------------------

SIST EN 16573:2017
EN 16573:2017 (E)
7.6.5 Performance rating calculations . 34
7.7 Ventilation combined with both hydronic and supply air heating/cooling . 35
7.7.1 General . 35
7.7.2 Test procedure . 35
7.7.3 Data to be recorded. 36
7.7.4 Performance rating calculations . 39
7.8 Ventilation combined with heating and hot water production . 40
7.8.1 General . 40
7.8.2 Test procedure . 40
7.8.3 Data to be recorded. 42
7.8.4 Performance rating calculations . 45
7.9 Ventilation combined with cooling and hot water production . 48
7.9.1 General . 48
7.9.2 Test procedure . 48
7.9.3 Data to be recorded. 50
7.9.4 Performance rating calculations . 53
8 Performance testing of acoustic characteristics . 57
8.1 General . 57
8.2 Configurations to be tested . 57
8.3 Performance testing ventilation only . 57
8.4 Performance testing ventilation and hydronic heating . 57
8.5 Performance testing ventilation and supply air heating. 57
8.6 Performance testing ventilation and supply air heating and hydronic heating . 57
8.7 Performance testing ventilation and domestic hot water . 58
9 Test report . 58
9.1 General information . 58
9.2 Additional information . 59
9.3 Rating test results . 59
9.3.1 Product specifications. 59
9.3.2 Leakages . 59
9.3.3 Air flow/pressure curve . 59
9.3.4 Temperature ratios of ventilation function . 59
9.3.5 Performance data of ventilation and domestic hot water functions . 59
9.3.6 Performance data of ventilation and hydronic space heating and/or cooling. 59
9.3.7 Performance data of ventilation and air heating and/or cooling . 59
9.3.8 Performance data of ventilation with both hydronic and air heating/cooling . 59
9.3.9 Performance data of ventilation with heating and hot water production . 59
9.3.10 Performance data of ventilation with cooling and hot water production . 59
9.4 Acoustic characteristics . 60

3

---------------------- Page: 5 ----------------------

SIST EN 16573:2017
EN 16573:2017 (E)
European foreword
This document (EN 16573:2017) has been prepared by Technical Committee CEN/TC 156 “Ventilation
for buildings”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by August 2017, and conflicting national standards shall
be withdrawn at the latest by August 2017.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria,
Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia,
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta,
Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.
4

---------------------- Page: 6 ----------------------

SIST EN 16573:2017
EN 16573:2017 (E)
1 Scope
This European Standard specifies the laboratory test methods and test requirements for aerodynamic,
energy rating and acoustic performance, of multifunctional balanced units intended for use in a single
dwelling.
In the case of units consisting of several parts, this standard applies only to those designed and supplied
as a complete package with the mount instructions.
It covers units that contain at least, within one or more casing:
— supply and exhaust air fans;
— air filters
— common control system;
and one or more of the additional components:
— air to water heat pump;
— air to air heat pump;
— air-to-air heat exchanger.
Units including only an air to air heat exchanger and/or an exhaust air to supply air heat pump are
covered by EN 13141-7.
A non-exhaustive list of possible configurations of multifunctional units covered by this standard is
given in Clause 5.
The standard does not cover the thermal aspects of humidity transfer in the air-to-air heat exchanger.
This standard does not deal with non-ducted units on supply and extract air side.
This standard does not deal with collective units (centralized or semi-centralized systems)
These multifunctional balanced units can be connected to ground heat exchanger for air preheating,
solar collector or other heating systems. This standard does not cover the testing with these additional
components.
This standard does not cover units including combustion engine driven compression heat pumps and
sorption heat pump.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any amendments) applies.
EN 12102, Air conditioners, liquid chilling packages, heat pumps and dehumidifiers with electrically
driven compressors for space heating and cooling - Measurement of airborne noise - Determination of the
sound power level
EN 12792, Ventilation for buildings - Symbols, terminology and graphical symbols
EN 13141-7:2010, Ventilation for buildings - Performance testing of components/products for residential
ventilation - Part 7: Performance testing of a mechanical supply and exhaust ventilation units (including
heat recovery) for mechanical ventilation systems intended for single family dwellings
5

---------------------- Page: 7 ----------------------

SIST EN 16573:2017
EN 16573:2017 (E)
EN 14511 (all parts), Air conditioners, liquid chilling packages and heat pumps with electrically driven
compressors for space heating and cooling
EN 16147, Heat pumps with electrically driven compressors - Testing and requirements for marking of
domestic hot water units
EN ISO 5135, Acoustics - Determination of sound power levels of noise from air-terminal devices, air-
terminal units, dampers and valves by measurement in a reverberation room (ISO 5135)
3 Terms, definitions and symbols
3.1 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 12792, EN 13141-7,
EN 14511-1 and EN 16147, and the following apply.
3.1.1
declared maximum air volume flow
maximum of the removed or fresh air volume flow corresponding to the declared total pressure of the
unit at the maximum setting, without any recirculation, for standard air conditions (20 °C, 101 325 Pa)
[SOURCE: EN 13141-7:2010, 3.1.4, modified — The beginning of the definition has been redrafted and
the expression “without any recirculation” has been added.]
3.1.2
declared total pressure difference
total pressure difference between the outlet and the inlet of the unit, without any recirculation, declared
by the manufacturer, and corresponding to 100 Pa or to a lower total pressure if the intended use
declared by the manufacturer is less than 100 Pa
[SOURCE: EN 13141-7:2010, 3.1.6, modified — The original term was “Ptud/2” and it was defined with
the beginning of the present definition.]
3.1.3
multifunctional balanced ventilation unit
unit intended for use in a single family dwelling to primary provide balanced ventilation and in addition
heating and/or cooling and/or hot water production and contains at least, within one or more modular
casing supply and exhaust air fans, air filters, common control system and one more of the additional
components, air to water heat pump, air to air heat pump, air-to-air heat exchanger
3.1.4
hydronic heating/cooling
heating or cooling supplied by a water or brine circuit
3.1.5
air heating/cooling
heating or cooling supplied by an air stream
3.1.6
air supply free cooling
recovering of cooling energy produced by the heat pump while producing hot water
Note 1 to entry: Hot water has priority.
6

---------------------- Page: 8 ----------------------

SIST EN 16573:2017
EN 16573:2017 (E)
3.1.7
reference fresh air volume flow
fresh air volume flow q at the reference point defined at p and 70 % of declared maximum air
V,ref,fresh tUd/2
volume flow
3.2 Symbols
ODA, 21 Outdoor Air
SUP, 22 Supply Air
RCA, Recirculation air (additional airflow for example for air heating or air cooling function)
ETA, 11 Extract Air
EHA, 12 Exhaust Air
OEA Outdoor to Exhaust Air (additional airflow for example to raise the thermal capacity of
the heat pump)
List of symbols
P capacity or power input, in kW
p declared total pressure, in Pa
tUd
Q thermal energy, in kWh
t time duration, in s or in h
W electrical work, in kWh
h specific enthalpy in kJ/kg
q mass flow rate, in kg/s
m
3
q volume flow rate, in m /h
v
T temperature in °C
List of indices used for the individual and combined functions in the symbols:
AC supply Air Cooling
AH supply Air Heating
AFC supply air free cooling
C cooling
WH (Domestic) hot water production
el electric
H heating
HC Hydronic Cooling
HH Hydronic Heating
HR heat recovery
V Ventilation
es stand by
The combination of indices indicates simultaneous operation of the corresponding functions.
7

---------------------- Page: 9 ----------------------

SIST EN 16573:2017
EN 16573:2017 (E)
4 Functions
A multifunctional ventilation unit provides ventilation for single dwelling as a leading function. This
means, that all additional functions:
— hydronic heating/air heating;
— hydronic cooling/air cooling;
— hot water production;
shall be operating only when ventilation is operating.
The multifunctional ventilation unit shall be designed and controlled to provide the hygienic ventilation
rate for a dwelling or part of a dwelling. That means for example, that the ventilation rate shall not be
controlled according to the hydronic heating demand.
If specified by the manufacturer, the unit may use an additional outdoor air volume flow, to provide a
higher thermal capacity if needed. This leads to two alternatives:
1) The higher outdoor air volume flow (outdoor exhaust air) does not affect the ventilation function
(fresh air and removed air).
Additional tests shall be performed according to the declaration of manufacturer. No further
correction needed
2) The air volume flows for ventilation (fresh air and/or removed air) increase. In this case the air
volume flows shall be measured and documented as a percentage of reference air volume flow.
NOTE This may be needed to allow a correction of system performance according to the EPBD calculation.
5 Description and testing of multifunctional units
Table 1 shows a non-exhaustive list of relevant combinations of multifunctional units with the
corresponding applicable test procedures according to Clause 6, 7 and 8 for thermal and acoustic
performance.
The leading function is ventilation at reference air volume flow. The heat pump can use any air source:
outdoor air, exhaust air, recirculation air or any mixture of these.
For testing the unit shall be installed according to the manufacturer instructions given in the
installation manuals unless otherwise specified in the referred standards for specific tests.
8

---------------------- Page: 10 ----------------------

SIST EN 16573:2017
EN 16573:2017 (E)
Table 1 — Units and test procedures
 Description Function scheme Test procedure
Balanced ventilation (sub)clause:
including:
1. + Air to air heat Fully covered by
exchanger EN 13141–7

2. + Air to air heat pump Fully covered by
EN 13141–7

3. + Air to air heat Fully covered by
exchanger EN 13141–7
+ Air to supply air heat
pump


4. + Air to water heat Clause 6
pump for the
7.4
domestic hot water
8.3
production
8.7
Key
1 domestic hot
water

5. + Air to water heat Clause 6
pump for hydronic
7.5
heating or cooling
8.3
8.4
Key
1 water heating or
cooling

9

---------------------- Page: 11 ----------------------

SIST EN 16573:2017
EN 16573:2017 (E)
 Description Function scheme Test procedure
Balanced ventilation (sub)clause:
including:
6. + Air to water heat Clause 6
pump for
7.4
alternative:
7.5
– hydronic heating
8.3
and cooling
8.4
– domestic hot
Key
water production
1 water heating or
cooling/domestic
hot water

7. + Air to water heat Clause 6
pump for
7.8
simultaneous:
8.3
– hydronic heating
8.6
or cooling
Key
– domestic hot
1 water heating or
water
cooling
2 domestic hot
water

8. + air to air heat Clause 6
exchanger
7.3
+ Air source heat
7.6
pump for heating or
8.3
cooling with
8.5
recirculating air


9. + air to air heat Clause 6
exchanger
7.3
+ Air to water heat
7.4
pump for domestic
8.3
hot water
8.7
production
Key
1 domestic hot
water

10. + air to air heat Clause 6
exchanger
7.3
+ Air to water heat
7.5
pump for hydronic
8.3
heating or cooling
8.4
Key
1 water heating or
cooling

10

---------------------- Page: 12 ----------------------

SIST EN 16573:2017
EN 16573:2017 (E)
 Description Function scheme Test procedure
Balanced ventilation (sub)clause:
including:
11. + air to air heat Clause 6
exchanger
7.3
+ Air to water heat
7.4
pump for
7.5
alternative:
8.3
– hydronic heating
8.4
or cooling
Key
– domestic hot
water production 1 water heating or

cooling/domestic
hot water
12. + air to air heat Clause 6
exchanger
7.3
+ air to water heat
7.8
pump for
8.3
simultaneous:
8.4
– hydronic heating
Key
or cooling
1 water heating or
– domestic hot
cooling
water production

2 domestic hot
water
13. + air to air heat Clause 6
exchanger
7.3
+ Air source heat
7.6
pump for:
7.7
– supply air heating
7.8
or cooling
8.3
– for alternative:
8.6
– hydronic heating
Key
or cooling
1 water heating or
– domestic hot

cooling/ domestic
water
hot water
production
14. + air to air heat Clause 6
exchanger
7.3
+ Air source heat
7.8
pump for:
8.3
– supply air heating
8.5
or cooling
Key
– domestic hot
1 domestic hot
water production
water

11

---------------------- Page: 13 ----------------------

SIST EN 16573:2017
EN 16573:2017 (E)
 Description Function scheme Test procedure
Balanced ventilation (sub)clause:
including:
15. + air to air heat Clause 6
exchanger
7.3
+ Air source heat
7.6.
pump for:
7.7
– supply air heating
7.8
or cooling
8.3
– for simultaneous:
8.6
– hydronic heating
Key
– domestic hot
1 water heating/
water

domestic hot water
production
16. + air to air heat Clause 6
exchanger
7.3
+ Air source heat
7.7
pump for:
7.8
– supply air heating
8.3
or cooling
8.5
– domestic hot
Key
water production
1 domestic hot
With recirculation air
water

17. + air to air heat Clause 6
exchanger
7.3
+ Air source heat
7.6
pump for:
7.7
– supply air heating
7.8
or cooling
8.3
– for alternative:
8.6
– domestic hot
Key
water
production 1 water heating or

cooling/Domestic
– hydronic heating
hot water
or cooling
With recirculation air
18. + air to air heat Clause 6
exchanger
7.3
+ Air source heat
7.4
pump for:
7.6
– supply air heating
7.9
or cooling and
8.3
simultaneous or
alternative 8.5
domestic hot
Key
water production
1 domestic hot
With recirculation air
water
NOTE EHA – Exhaust a
...

SLOVENSKI STANDARD
oSIST prEN 16573:2013
01-maj-2013
3UH]UDþHYDQMHVWDYE3UHVNXãDQMHODVWQRVWLNRPSRQHQW]DVWDQRYDQMVNHVWDYEH
9HþQDPHQVNHXUDYQRWHåHQHSUH]UDþHYDOQHHQRWH]DSRVDPH]QDVWDQRYDQMD
YNOMXþQRVWRSORWQLPLþUSDONDPL
Ventilation for Buildings - Performance testing of components for residential buildings -
Multifunctional balanced ventilation units for single family dwellings, including heat
pumps
Lüftung von Gebäuden - Leistungsprüfung von Bauteilen für Wohnbauten -
Multifunktionale Zu-/Abluft-Lüftungseinheiten für Einzelwohnungen, einschließlich
Wärmepumpen
Ventilation des bâtiments - Essais de performance des composants pour les bâtiments
résidentiels - Dispositifs multifonctionnels de ventilation équilibrée pour les logements
individuels, comprenant des pompes à chaleur
Ta slovenski standard je istoveten z: prEN 16573
ICS:
91.140.30 3UH]UDþHYDOQLLQNOLPDWVNL Ventilation and air-
VLVWHPL conditioning
oSIST prEN 16573:2013 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
oSIST prEN 16573:2013

---------------------- Page: 2 ----------------------
oSIST prEN 16573:2013


EUROPEAN STANDARD
DRAFT
prEN 16573
NORME EUROPÉENNE

EUROPÄISCHE NORM

March 2013
ICS 91.140.30
English Version
Ventilation for Buildings - Performance testing of components for
residential buildings - Multifunctional balanced ventilation units
for single family dwellings, including heat pumps
Ventilation des bâtiments - Essais de performance des Lüftung von Gebäuden - Leistungsprüfung von Bauteilen
composants pour les bâtiments résidentiels - Dispositifs für Wohnbauten - Multifunktionale Zu-/Abluft-
multifonctionnels de ventilation équilibrée pour les Lüftungseinheiten für Einzelwohnungen, einschließlich
logements individuels, comprenant des pompes à chaleur Wärmepumpen
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee CEN/TC 156.

If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United
Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to
provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and
shall not be referred to as a European Standard.


EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2013 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 16573:2013: E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------
oSIST prEN 16573:2013
prEN 16573:2013 (E)
Contents Page
Foreword .4
1 Scope .4
2 Normative references .5
3 Terms, definitions and symbols .5
3.1 Terms and definitions .5
3.2 Symbols .6
4 Functions .7
5 Description of multifunctional units .7
6 Performance testing of aerodynamic characteristics . 12
6.1 Leakages . 12
6.1.1 Test method . 12
6.1.2 Requirements . 12
6.2 Air flow/pressure curve . 13
6.3 Reference point for aerodynamic conditions . 13
6.4 Pressure drop setting . 14
7 Performance testing of thermal characteristics . 14
7.1 General . 14
7.2 Air flow settings and uncertainty . 14
7.2.1 General . 14
7.2.2 Situation without any recirculation . 15
7.2.3 Situation with recirculation from outdoor air to exhaust air . 15
7.2.4 Situation with recirculation from extract to supply air . 16
7.2.5 Situation with two recirculations . 16
7.3 Ventilation heat recovery performance . 16
7.3.1 General . 16
7.3.2 Air flow test conditions . 17
7.3.3 Test procedure . 18
7.3.4 Data to be recorded . 18
7.3.5 Calculations . 19
7.4 Ventilation and domestic hot water production . 19
7.4.1 General . 19
7.4.2 Test procedure . 20
7.4.3 Data to be recorded . 21
7.4.4 Performance rating calculations . 22
7.5 Ventilation with hydronic space heating/cooling . 23
7.5.1 General . 23
7.5.2 Temperature test conditions . 24
7.5.3 Test procedure . 26
7.5.4 Data to be recorded . 26
7.5.5 Performance rating calculations . 28
7.6 Ventilation combined with supply air heating/cooling . 30
7.6.1 General . 30
7.6.2 Temperature test conditions . 30
7.6.3 Test procedure . 31
7.6.4 Data to be recorded . 31
7.6.5 Performance rating calculations . 33
7.7 Ventilation combined with both hydronic and supply air heating/cooling . 34
7.7.1 General . 34
7.7.2 Test procedure . 35
7.7.3 Data to be recorded . 35
2

---------------------- Page: 4 ----------------------
oSIST prEN 16573:2013
prEN 16573:2013 (E)
7.7.4 Performance rating calculations . 38
7.8 Ventilation combined with heating and hot water production . 39
7.8.1 General . 39
7.8.2 Test procedure . 40
7.8.3 Data to be recorded . 41
7.8.4 Performance rating calculations . 44
7.9 Ventilation combined with cooling and hot water production . 47
7.9.1 General . 47
7.9.2 Test procedure . 47
7.9.3 Data to be recorded . 49
7.9.4 Performance rating calculations . 53
8 Performance testing of acoustic characteristics . 55
8.1 General . 55
8.2 Configurations to be tested . 56
8.3 Performance testing ventilation only . 56
8.4 Performance testing ventilation and hydronic heating . 56
8.5 Performance testing ventilation and supply air heating . 56
8.6 Performance testing ventilation and supply air heating and hydronic heating . 56
8.7 Performance testing ventilation and domestic hot water . 57
9 Test report . 57
9.1 General information . 57
9.2 Additional information . 57
9.3 Rating test results . 58
9.3.1 Product specifications . 58
9.3.2 Leakages . 58
9.3.3 Air flow/pressure curve . 58
9.3.4 Temperature ratios of ventilation function . 58
9.3.5 Performance data of ventilation and domestic hot water functions . 58
9.3.6 Performance data of ventilation and hydronic space heating and/or cooling . 58
9.3.7 Performance data of ventilation and air heating and/or cooling . 58
9.3.8 Performance data of ventilation with both hydronic and air heating/cooling . 58
9.3.9 Performance data of ventilation with heating and hot water production . 58
9.3.10 Performance data of ventilation with cooling and hot water production . 58
9.4 Acoustic characteristics . 58

3

---------------------- Page: 5 ----------------------
oSIST prEN 16573:2013
prEN 16573:2013 (E)
Foreword
This document (prEN 16573:2013) has been prepared by Technical Committee CEN/TC 156 “Ventilation for
buildings”, the secretariat of which is held by BSI.
This document is currently submitted to the CEN Enquiry.
1 Scope
This Standard specifies the laboratory test methods and test requirements for aerodynamic, energy rating and
acoustic performance, of multifunctional balanced units intended for use in a single dwelling.
In the case of units consisting of several parts, this standard applies only to those designed and supplied as a
complete package with the mount instructions.
It covers unit that contain at least, within one or more casing:
 supply and exhaust air fans;
 air filters
 common control system.
And one or more of the additional components
 Air to water heat pump;
 Air to air heat pump
 air-to-air heat exchanger
except units including either an air to air heat exchanger and/or exhaust air to supply air heat pump which are
already covered by EN 13141-7.
A non-exhaustive list of possible configurations of multifunctional units covered by this standard is given in
Clause 5.
The standard does not cover the thermal aspects of humidity transfer in the air-to-air heat exchanger.
This standard does not deal with non-ducted units on supply and extract air side.
This standard does not deal with collective units (centralised or semi-centralised systems)
These multifunctional balanced units can be connected to ground heat exchanger for air preheating, solar
collector or other heating systems. This standard does not cover the testing of these additional components.
This standard does not cover units including combustion engine driven compression heat pumps and sorption
heat pump.
4

---------------------- Page: 6 ----------------------
oSIST prEN 16573:2013
prEN 16573:2013 (E)
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated references,
the latest edition of the referenced document (including any amendments) applies.
EN 12102, Air conditioners, liquid chilling packages, heat pumps and dehumidifiers with electrically driven
compressors for space heating and cooling  Measurement of airborne noise  Determination of the sound
power level
EN 12792, Ventilation for buildings  Symbols, terminology and graphical symbols
EN 13141-7, Ventilation for buildings  Performance testing of components/products for residential ventilation
 Part 7: Performance testing of a mechanical supply and exhaust ventilation units (including heat recovery)
for mechanical ventilation systems intended for single family dwellings
EN 14511-1, Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for
space heating and cooling  Part 1: Terms and definitions
EN 14511-2, Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for
space heating and cooling  Part 2: Test conditions
EN 14511-3, Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for
space heating and cooling  Part 3: Test methods
EN 16147, Heat pumps with electrically driven compressors  Testing and requirements for marking of
domestic hot water units
EN ISO 5135, Acoustics  Determination of sound power levels of noise from air-terminal devices, air-
terminal units, dampers and valves by measurement in a reverberation room (ISO 5135)
3 Terms, definitions and symbols
3.1 Terms and definitions
For the purposes of this document, the following terms and definitions given in EN 12792, EN 13141-7,
EN 14511-1 and EN 16147 apply.
3.1.1
declared maximum air volume flow
maximum of the removed or fresh air volume flow corresponding to the declared total pressure of the unit at
the maximum setting for standard air conditions (20°C, 101325 Pa).
3.1.2
multifunctional balanced ventilation unit
unit intended for use in a single family dwelling to primary provide balanced ventilation and in addition heating
and/or cooling and/or hot water production
NOTE It contains at least, within one or more modular casing supply and exhaust air fans, air filters, common control
system and one more of the additional components, air to water heat pump, air to air heat pump, air-to-air heat exchanger.
Units including either an air to air heat exchanger and/or air to air heat pump are already covered by EN 13141-7 and
excluded.
3.1.3
hydronic heating/cooling
heating or cooling supplied by a water or brine circuit
5

---------------------- Page: 7 ----------------------
oSIST prEN 16573:2013
prEN 16573:2013 (E)
3.1.4
air heating/cooling
heating or cooling supplied by an air stream
3.1.5
Air supply free cooling
recovering of cooling energy produced by the heat pump while producing hot water.
NOTE Hot water has priority.
3.1.6
reference fresh air volume flow
fresh air volume flow q at the reference point defined at P and 70 % of declared maximum air
V,ref,fresh tUd/2
volume flow according EN 13141-7.

3.2 Symbols
ODA, 21 Outdoor Air
SUP, 22 Supply Air
RCA, Recirculation air (add airflow for example for air heating or air cooling function)
ETA, 11 Extract Air
EHA, 12 Exhaust Air
OEA Outdoor to Exhaust Air (add airflow for example to raise the thermal capacity of the heat
pump)
List of symbols
P capacity or power input, in kW
Q thermal energy, in kWh
t time duration, in s
W electrical work, in kWh
h spec. enthalpy in kJ/kg
q mass flow rate kg/s
m
3
q volume flow rate m /h
v
T temperature in °C
List of indices used for the individual and combined functions in the symbols:
AC supply Air Cooling
AH supply Air Heating
AFC supply air free cooling
6

---------------------- Page: 8 ----------------------
oSIST prEN 16573:2013
prEN 16573:2013 (E)
C cooling
WH (Domestic) hot water production
el electric
H heating
HC Hydronic Cooling
HH Hydronic Heating
HR heat recovery
V Ventilation
es stand by
The combination of indices indicates simultaneous operation of the corresponding functions.
4 Functions
A multifunctional ventilation unit provides ventilation for single dwelling as a leading function. This means, that
all additional functions
• Hydronic Heating/Air Heating
• Hydronic Cooling/Air Cooling
• Hot water production
shall be only operating if ventilation is operating.
The multifunctional ventilation unit shall be designed and controlled to provide the hygienic ventilation rate for
a dwelling or part of a dwelling. That means for example, that the ventilation rate shall not be controlled
according to the hydronic heating demand.
According to the declaration of the manufacturer, the unit can use an additional outdoor air volume flow, to
provide a higher thermal capacity if needed.
1. The higher outdoor air volume flow does not affect the ventilation function (fresh air volume ventilation
flow and balance of the fresh air volume flow for the dwelling).
Additional tests shall be performed according to the declaration of manufacturer. No further correction
needed
2. The air volume flows for ventilation increase. In this case the air volume flows shall be measured and
documented as a percentage of reference air volume flow.
NOTE This may be needed to allow a correction of system performance according to the EPBD calculation.
5 Description of multifunctional units
Table 1 shows a non-exhaustive list of relevant combinations of multifunctional units with the corresponding
applicable test procedures according to clause 7 and 8 for thermal and acoustic performance.
The leading function is ventilation at reference air volume flow. The heat pump can use any air source:
outdoor air, exhaust air, recirculation air or any mixture.
7

---------------------- Page: 9 ----------------------
oSIST prEN 16573:2013
prEN 16573:2013 (E)
Table 1 — Units and test procedures (1 of 5)
Description Function scheme Test procedure
Balanced ventilation clause:
including:
1. + Air to air heat exchanger Fully covered by
EN 13141-7

2. + Air to air heat pump Fully covered by
EN 13141-7

3. + Air to air heat exchanger Fully covered by
EN 13141-7
+ Air to supply air heat
pump


4. + Air to water heat pump 6
for the domestic hot
7.4
water production
8.3
8.7

Key
1 Water system

5. + Air to water heat pump 6
for hydronic heating or
7.5
cooling
8.3
8.4

Key
1 Water system







8

---------------------- Page: 10 ----------------------
oSIST prEN 16573:2013
prEN 16573:2013 (E)
Table 1 — Units and test procedures (2 of 5)

Description Function scheme Test procedure
Balanced ventilation clause:
including:
6. + Air to water heat pump 6
for alternative:
7.4
– hydronic heating and
7.5
cooling
8.3
– domestic hot water
8.4
production

Key
1 Water system

7. + Air to water heat pump 6
for simultaneous:
7.8
– hydronic heating or
8.3
cooling
8.6
– domestic hot water

Key
1 Water system
2 Domestic hot water

8. + air to air heat exchanger 6
+ Air source heat pump 7.3
heating or cooling
7.6
8.3
8.5


9. + air to air heat exchanger 6
+ Air to water heat pump 7.3
for domestic hot water
7.4
production
8.3
8.7

Key
1 Water system








9

---------------------- Page: 11 ----------------------
oSIST prEN 16573:2013
prEN 16573:2013 (E)
Table 1 — Units and test procedures (3 of 5)

Description Function scheme Test procedure
Balanced ventilation clause:
including:
10. + air to air heat exchanger 6
+ Air to water heat pump 7.3
for hydronic heating or
7.5
cooling
8.3
8.4

Key
1 Water system

11. + air to air heat exchanger 6
+ Air to water heat pump 7.3
for alternative:
7.4
– hydronic heating or
7.5
cooling
8.3
– domestic hot water
8.4
production

Key
1 Water system

12. + air to air heat exchanger 6
+ air to water heat pump for 7.3
simultaneous:
7.8
– hydronic heating or
8.3
cooling
8.4
– domestic hot water

production
Key
1 Water system
2 Domestic hot water

13. + air to air heat exchanger 6
+ Air source heat pump for: 7.3
– supply air heating or 7.6
cooling
7.7
– for alternative:
7.8
– hydronic heating or
8.3
cooling
8.6
– domestic hot water

production
Key
1 Water system or
Domestic hot water






10

---------------------- Page: 12 ----------------------
oSIST prEN 16573:2013
prEN 16573:2013 (E)
Table 1 — Units and test procedures (4 of 5)

Description Function scheme Test procedure
Balanced ventilation clause:
including:
14. + air to air heat exchanger 6
+ Air source heat pump for: 7.3
– supply air heating or 7.8
cooling
8.3
– domestic hot water
8.5
production

Key
1 Domestic hot water

15. + air to air heat exchanger 6
+ Air source heat pump for: 7.3
– supply air heating or 7.6.
cooling
7.7
– for simultaneous:
7.8
– hydronic heating
8.3
– domestic hot water
8.6
production

Key
1 Water system and/or
Domestic hot water

16. + air to air heat exchanger 6
+ Air source heat pump for: 7.3
– supply air heating or
7.7
cooling
7.8
– domestic hot water
8.3
production
8.5

Key
1 Split system
2 Domestic hot water

17. + air to air heat exchanger 6
+ Air source heat pump for: 7.3
– supply air heating or 7.6
cooling
7.7
– for alternative:
7.8
– domestic hot water
8.3
production
8.6
– hydronic heating or

cooling
Key
1 Split system

2 Water system or
Domestic hot water


11

---------------------- Page: 13 ----------------------
oSIST prEN 16573:2013
prEN 16573:2013 (E)
Table 1 — Units and test procedures (5 of 5)

Description Function scheme Test procedure
Balanced ventilation clause:
including:
18. + air to air heat exchanger 6
+ Air source heat pump for: 7.3
– supply air heating or 7.4
cooling and
7.6
simultaneous domestic
7.9
hot water production
8.3

8.5

Key
1 2 Domestic hot water

NOTE EHA – Exhaust air, ETA – Extract air, ODA - Outdoor air, RCA – Recirculation air, SUP – Supply air

6 Performance testing of aerodynamic characteristics
6.1 Leakages
6.1.1 Test method
Pressure testing method applies to classify leakages of the unit as defined in Annex B of EN 13141-7.
For internal leakage, if the pressure method is not applicable, e.g. units using recirculation air, the unit shall be
tested as category 2 heat exchanger (tracer gas method).
6.1.2 Requirements
To set the declared maximum air volume flow, the declared total pressure shall correspond to 100 Pa, or to a
lower total pressure if the intended use declared by the manufacturer is less than 100 Pa.
The declared maximum air volume flow shall be equal to the smaller in case the supply and extract air volume
flows are different.
In addition, to assess correctly the thermal performance, aerodynamic characteristics, shall be tested before
or together with any thermal characteristics testing.
Aerodynamic characteristics shall include:
 external leakage or total recirculated fraction in supply air;
 internal leakage or recirculated fraction from extract to supply air or total recirculated fraction in
supply air.
The tests for air flow/pressure curve and thermal performances shall not be made because of measurement
uncertainty when leakages according to 6.1.1 are too high. The external and internal leakage of the unit shall
comply with Class A1 or A2, B1 or B2, C1 or C2 depending on
...