Chimneys - Accessories - Part 3: Draught regulators, standstill opening devices and combined secondary air devices - Requirements and test methods

This European standard specifies the requirements and test methods for draught regulators and standstill opening devices that are used as components, carrying flue gases, in order to limit the draught in chimneys and provide secondary air to the chimney.
Draught regulators and standstill opening devices for positive pressure chimneys are not covered by this standard.
It also specifies the requirements for marking, manufacturers’ instruction, product information and evaluation of conformity.

Abgasanlagen - Zubehörteile - Teil 3: Selbsttätig arbeitende, zwangsgesteuerte und kombinierte Nebenluftvorrichtungen - Anforderungen und Prüfmethoden

Diese Europäische Norm legt die Anforderungen und Prüfverfahren für selbständig arbeitende und zwangsgesteuerte Nebenluftvorrichtungen fest, die zum Transport von Abgasen verwendet werden, um den Unterdruck  in Abgasanlagen zu begrenzen und die Abgasanlage mit Nebenluft zu versorgen.
Selbständig arbeitende und zwangsgesteuerte Nebenluftvorrichtungen für Überdruckabgasanlagen werden von dieser Norm nicht abgedeckt.
Sie legt außerdem die Anforderungen an die Kennzeichnung, Herstelleranweisungen, Produktinformationen und Bewertung und Überprüfung der Leistungsbeständigkeit fest.

Conduits de fumée - Accessoires - Partie 3: Régulateurs de tirage, dispositifs d'ouverture pour période d'arrêt et dispositifs combinés d'air secondaire - Exigences et méthodes d'essai

La présente Norme européenne spécifie les exigences et les méthodes d'essai s'appliquant aux régulateurs de tirage et aux dispositifs d’ouverture pour période d’arrêt, utilisés comme composants, transportant les fumées, afin de limiter le tirage dans les conduits et de fournir de l'air secondaire.
Les régulateurs de tirage et les dispositifs d’ouverture pour période d’arrêt destinés aux conduits de fumée en pression positive n'entrent pas dans le domaine d'application de la présente norme.
La présente norme spécifie également les exigences en matière de marquage, d'instructions du fabricant, d'informations produit et d'évaluation de la conformité.

Dimovodne naprave - Oprema - 3. del: Regulatorji vleka, lopute z motornim pogonom in kombinirane lopute za sekundarni zrak - Zahteve in preskusne metode

Ta evropski standard določa zahteve in preskusne metode za regulatorje vleka in lopute z motornim pogonom, ki se uporabljajo kot sestavni deli za odvajanje dimnih plinov, da se omeji vlek v dimovodnih napravah in zagotovi pretok sekundarnega zraka v dimovodno napravo.  Regulatorji vleka in lopute z motornim pogonom za dimovodne naprave s pozitivnim tlakom ne spadajo na področje uporabe tega standarda. Standard določa tudi zahteve za označevanje, navodila proizvajalcev, informacije o proizvodih in vrednotenje skladnosti.

General Information

Status
Withdrawn
Public Enquiry End Date
30-Jul-2013
Publication Date
07-Sep-2016
Withdrawal Date
10-Jan-2019
Technical Committee
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
11-Jan-2019
Due Date
03-Feb-2019
Completion Date
11-Jan-2019

Relations

Buy Standard

Standard
EN 16475-3:2016
English language
40 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Dimovodne naprave - Oprema - 3. del: Regulatorji vleka, lopute z motornim pogonom in kombinirane lopute za sekundarni zrak - Zahteve in preskusne metodeAbgasanlagen - Zubehörteile - Teil 3: Selbsttätig arbeitende, zwangsgesteuerte und kombinierte Nebenluftvorrichtungen - Anforderungen und PrüfmethodenConduits de fumée - Accessoires - Partie 3: Régulateurs de tirage, dispositifs d'ouverture pour période d'arrêt et dispositifs combinés d'air secondaire - Exigences et méthodes d'essaiChimneys - Accessories - Part 3: Draught regulators, standstill opening devices and combined secondary air devices - Requirements and test methods91.060.40Dimniki, jaški, kanaliChimneys, shafts, ductsICS:Ta slovenski standard je istoveten z:EN 16475-3:2016SIST EN 16475-3:2016en,fr,de01-oktober-2016SIST EN 16475-3:2016SLOVENSKI
STANDARD



SIST EN 16475-3:2016



EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 16475-3
April
t r s x ICS
{ sä r x rä v r English Version
Chimneys æ Accessories æ Part
uã Draught regulatorsá standstill opening devices and combined secondary air devices æ Requirements and test methods Conduits de fumée æ Accessoires æ Partie
uã Régulateurs de tirageá dispositifs d 5ouverture pour période d 5arrêt et dispositifs combinés d 5air secondaire æ Exigences et méthodes d 5essai
Abgasanlagen æ Zubehörteile æ Teil
uã Selbsttätig arbeitendeá zwangsgesteuerte und kombinierte Nebenluftvorrichtungen æ Anforderungen und Prüfmethoden This European Standard was approved by CEN on
t y November
t r s wä
egulations which stipulate the conditions for giving this European Standard the status of a national standard without any alterationä Upætoædate lists and bibliographical references concerning such national standards may be obtained on application to the CENæCENELEC Management Centre or to any CEN memberä
translation under the responsibility of a CEN member into its own language and notified to the CENæCENELEC Management Centre has the same status as the official versionsä
CEN members are the national standards bodies of Austriaá Belgiumá Bulgariaá Croatiaá Cyprusá Czech Republicá Denmarká Estoniaá Finlandá Former Yugoslav Republic of Macedoniaá Franceá Germanyá Greeceá Hungaryá Icelandá Irelandá Italyá Latviaá Lithuaniaá Luxembourgá Maltaá Netherlandsá Norwayá Polandá Portugalá Romaniaá Slovakiaá Sloveniaá Spainá Swedená Switzerlandá Turkey andUnited Kingdomä
EUROPEAN COMMITTEE FOR STANDARDIZATION COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre:
Avenue Marnix 17,
B-1000 Brussels
9
t r s x CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Membersä Refä Noä EN
s x v y wæ uã t r s x ESIST EN 16475-3:2016



EN 16475-3:2016 (E) 2 Contents Page European foreword . 5 Introduction . 6 1 Scope . 7 2 Normative references . 7 3 Terms and definitions . 7 4 Product characteristics . 8 4.1 General . 8 4.2 Dimensions and tolerances . 8 4.3 Mechanical resistance and stability . 8 4.4 Thermal performance . 8 4.4.1 Reaction to fire . 8 4.4.2 Fire resistance (internal to external) . 8 4.5 Hygiene, health and environment . 9 4.5.1 Gas tightness . 9 4.5.2 Condensate resistance . 9 4.5.3 Corrosion resistance . 9 4.5.4 Dangerous substances . 9 4.6 Additional criteria for chimney operation. 9 4.6.1 Determination of the draught regulator group . 9 4.6.2 Adjustability and function of the draught regulator . 10 4.6.3 Durability of the standstill opening device . 11 4.7 Electrical requirements . 11 4.7.1 Motor . 11 4.7.2 Limit switches . 11 5 Testing, assessment and sampling methods . 11 5.1 Thermal performance . 11 5.1.1 General . 11 5.1.2 Test Assembly . 12 5.1.3 Test procedure . 13 5.1.4 Standstill opening device durability test . 14 5.2 Gas tightness . 14 5.2.1 Test assembly . 14 5.2.2 Test Procedure . 15 5.2.3 Test results . 15 5.3 Additional criteria for chimney operation. 15 5.3.1 Adjustability of the draught regulator . 15 5.3.2 Draught regulator group test . 16 6 Assessment and verification of constancy of performance (AVCP) . 16 6.1 General . 16 6.2 Type testing . 16 6.2.1 General . 16 6.2.2 Test samples, testing and compliance criteria . 17 6.2.3 Test reports . 18 6.2.4 Shared other party results . 18 SIST EN 16475-3:2016



EN 16475-3:2016 (E) 3 6.2.5 Cascading determination of the product type results . 19 6.3 Factory production control (FPC) . 20 6.3.1 General . 20 6.3.2 Requirements . 20 6.3.3 Product specific requirements . 23 6.3.4 Initial inspection of factory and of FPC . 23 6.3.5 Continuous surveillance of FPC . 24 6.3.6 Procedure for modifications . 24 7 Manufacturer's declaration for type test . 24 8 Product information . 25 8.1 Manufacturer's instructions . 25 8.2 Minimum information to be included in the manufacturer's instructions . 25 9 Classification and designation . 25 9.1 General . 25 9.2 Temperature classes and test temperature . 26 9.3 Corrosion resistance. 26 9.4 Soot fire resistance and distance to combustible material . 26 9.5 Draught regulator groups and whether it is a standstill opening device . 26 10 Marking, labelling and packaging . 26 10.1 Draught regulator and standstill opening device . 26 10.2 Packaging . 27 Annex A (normative)
Choice of sizes for type test and sampling . 28 A.1 Thermal testing . 28 A.2 Gas tightness . 28 A.3 Condensate resistance . 28 A.4 Determination of the group . 28 A.5 Adjustability . 28 A.6 Durability of standstill opening device . 28 A.7 Samples . 28 A.8 Factory production control system . 28 A.9 Further type testing . 28 Annex B (informative)
Sampling for factory productions control . 29 B.1 Sampling plans . 29 B.1.1 General . 29 B.1.2 Acceptable quality level (AQL) . 29 B.1.3 The inspection level . 29 B.1.4 Normal, tightened or reduce inspection . 29 B.1.5 Single, double, multiple or sequential sampling . 29 B.1.6 Batch quantity . 29 B.2 Inspection levels and procedures . 29 B.2.1 Incoming material . 29 SIST EN 16475-3:2016



EN 16475-3:2016 (E) 4 B.2.2 In-process inspection . 30 B.2.3 Finished goods checks . 30 Annex C (normative)
Factory production control . 31 C.1 Introduction . 31 C.2 Materials, including coatings . 31 C.3 Seals and sealants . 31 C.4 Manufacturing checks . 31 C.4.1 Dimensions . 31 C.4.2 Other checks . 31 Annex D (informative)
Recommended range of application . 32 D.1 Tables for the selection of the draught regulator group Height against diameter . 32 Annex E (informative)
Examples of products . 34 E.1 Without standstill opening device . 34 Annex ZA (informative)
Relationship of this European Standard with Regulation (EU) No.305/2011 . 36 ZA.1 Scope and relevant characteristics . 36 ZA.2 System of Assessment and Verification of Constancy of Performance (AVCP) . 37 ZA.3 Assignment of AVCP tasks . 37 Bibliography . 40
SIST EN 16475-3:2016



EN 16475-3:2016 (E) 5 European foreword This document (EN 16475-3:2016) has been prepared by Technical Committee CEN/TC 166 “Chimneys”, the secretariat of which is held by ASI. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by October 2016, and conflicting national standards shall be withdrawn at the latest by January 2018. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights. This document has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of EU Directive(s). For relationship with EU Regulation, see informative Annex ZA, which is an integral part of this document. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. SIST EN 16475-3:2016



EN 16475-3:2016 (E) 6 Introduction This standard forms a part of the series of standards for chimney accessories: — Part 1: Silencers — Part 2: Chimney fans — Part 3: Draught regulators, standstill opening devices and combined secondary air devices (this part) — Part 4: Flue dampers — Part 5: Explosion/implosion relief devices — Part 6: Access components — Part 7: Rain caps Independent draught regulators are for the purpose of reducing negative pressure that is too large in the chimney, which can result through the use of commercially available cross-section dimensions, despite being designed e.g. according to EN 13384-1:2015, Calculation method for chimneys serving single appliance. They serve to increase the flue gas speed and the ventilation of the chimney, for the purpose of drying out (see explanations). Standstill opening devices interlocked with the combustion system are exclusively for the purpose of ventilating the chimney during standby. SIST EN 16475-3:2016



EN 16475-3:2016 (E) 7 1 Scope This European Standard specifies the requirements and test methods for draught regulators, standstill opening devices and combined secondary air devices that are used as components, carrying flue gases, in order to limit the draught in chimneys and provide secondary air to the chimney. Draught regulators, standstill opening devices and combined secondary air devices for positive pressure chimneys are not covered by this standard. It also specifies the requirements for marking, manufacturers’ instruction, product information and attestation and verification of constancy of performance (AVCP). 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 1443, Chimneys — General requirements EN 10088-1, Stainless steels — Part 1: List of stainless steels EN 10346, Continuously hot-dip coated steel flat products for cold forming — Technical delivery conditions EN 13216-1, Chimneys — Test methods for system chimneys — Part 1: General test methods EN 60730-2-14, Automatic electrical controls for household and similar use — Part 2-14: Particular requirements for electric actuators (IEC 60730-2-14) EN 61058-1, Switches for appliances — Part 1: General requirements (IEC 61058-1) 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 1443, and the following apply. 3.1 draught regulator device with a hinged flap in a flue opening to allow entry of secondary air into the flue to regulate the draught 3.2 standstill opening device device which is opened motorised to allow air to enter the flue during the standstill period of the heating appliance 3.3 combined secondary air device combination of a draught regulator and standstill opening device SIST EN 16475-3:2016



EN 16475-3:2016 (E) 8 3.4 sootfire safe accessory (As) accessory that may not perform its intended function during and after a sootfire but does not prevent the safe operation or change the designation “G” of the chimney or connecting flue pipe Note 1 to entry: “As” can only be used for accessories and not for chimneys, flue liners and connecting flue pipes. Note 2 to entry: Measures to be taken after the event of a sootfire are to be found in the relevant product standard. 4 Product characteristics 4.1 General The draught regulator, and if appropriate the standstill opening device, housing and flap in contact with combustion products shall have a material with 0,6 mm minimum thickness, and a specification for steel according to EN 10088-1 of 1.4301, and 1.4404, and 1.0306 according to EN 10346 for any corrosion class for dry applications, and for wet applications, only for corrosion class 1 and 2, a steel according to EN 10088-1 of 1.4404 or higher. The draught regulator and standstill opening devices shall fulfil the following requirements, if appropriate. The combined secondary air devices shall fulfil the requirements of both, if appropriate. 4.2 Dimensions and tolerances The manufacturer is free to choose dimensions and tolerances for the manufacture of draught regulators and if appropriate standstill opening devices. 4.3 Mechanical resistance and stability The draught regulator, and standstill opening device, shall be able to move freely before and after the thermal tests except for a product designated As after a soot fire test. 4.4 Thermal performance 4.4.1 Reaction to fire As the fire reaction is not relevant for draught regulators and/or standstill opening devices, no declaration is necessary. 4.4.2 Fire resistance (internal to external) 4.4.2.1 General The manufacturer shall declare the minimum distance of the draught regulator, and if appropriate standstill opening device, to combustible material and the requirement of 4.4.2.2 and if appropriate 4.4.2.3 shall be met at the distance declared by the manufacturer. For a temperature designation up to T450, a declaration of at least 400 mm for the distance to combustible material is deemed to satisfy this requirement without testing. 4.4.2.2 Heat stress The draught regulator, and if appropriate standstill opening device, shall be tested in accordance with 5.1.3.2 and the requirements of 4.3 and 4.5.1 shall be met, and one of the flow rates of the group determination of 4.6.1, at the lowest declared setting, is within 10 % of the original value determined before thermal exposure. SIST EN 16475-3:2016



EN 16475-3:2016 (E) 9 4.4.2.3 Sootfire The draught regulator, and if appropriate the standstill opening device, designated sootfire resistant shall be tested in accordance with 5.1.3.3 and the requirements of 4.3 and 4.5.1 shall be met, and one of the flow rates of the group determination of 4.6.1, at the lowest declared setting, is within 10 % of the original value determined before thermal exposure. If the product satisfies all criteria it may be designated G. If it only satisfies the criteria of 4.5.1 it may be designated As. Otherwise it may only be designated O. 4.5 Hygiene, health and environment 4.5.1 Gas tightness When a draught regulator, and if appropriate standstill opening device, is tested according to the test methods described in 5.1, the individual values of leakage rate shall not be vary by more than 10 % of the average of the three samples tested for each size of draught regulator, and the average leakage rate shall not be greater than 0,06 m3/h per cm2 of free opening area, based on a pressure differential of (10 ± 1) Pa. The draught regulator and/or the standstill opening device tested for thermal performance shall meet this requirement both before and after the thermal performance tests (heat stress test and if appropriate soot fire test). The draught regulator and/or the standstill opening device designated As, shall have a leakage rate not greater than 0,18 m3/h/cm2 of free opening area, based on a pressure differential of (10 ± 1) Pa after the sootfire test. 4.5.2 Condensate resistance When tested in accordance with the condensate test of EN 13216-1 no condensate shall appear on the outer surface of the draught regulator/standstill opening device. The draught regulator shall be installed in accordance with the manufacturer’s instructions in the thermal test assembly of Figure 2, attaching the spray assembly to the top of the test chimney, and providing a drain for the condensate at the bottom. 4.5.3 Corrosion resistance Draught regulators shall be designated a corrosion class as defined in EN 1443 in accordance with 4.1. 4.5.4 Dangerous substances National regulations on dangerous substances may require verification and declaration on release, and sometimes content, when construction products covered by this standard are placed on those markets. In the absence of European harmonized test methods, verification and declaration on release/content should be done taking into account national provisions in the place of use. NOTE An informative database covering European and national provisions on dangerous substances is available at the Construction website on EUROPA accessed through: http://ec.europa.eu/enterprise/construction/cpd-ds/ . 4.6 Additional criteria for chimney operation 4.6.1 Determination of the draught regulator group When tested in accordance with 5.3.2 the draught regulator shall be assigned a group according to Figure 1. The curves are determined from the following formula. SIST EN 16475-3:2016



EN 16475-3:2016 (E) 10 2211000210002⋅+⋅=⋅YaYaX in Pa (1) where a1 and a2 are factors obtained from Table 1. Table 1 — Characteristic values for draught regulators draught regulator group a1 Pa„s/kg a2 Pa„(s/kg)2 1 400 120 000 2 200 30 000 3 140 11 400 4 97 5 000 5 74 2 800 6 48 1 260
Key Numbers 1 to 6 group number assigned to draught regulators X deviation from the setting point in Pa Y1 secondary air volume flow in m3/h Y2 secondary air mass flow in g/s Figure 1 — Limit curves of the determination for draught regulator group 4.6.2 Adjustability and function of the draught regulator When tested in accordance with 5.3.1 the adjustability of the settings shall be in maximum 5 Pa steps. SIST EN 16475-3:2016



EN 16475-3:2016 (E) 11 When tested in accordance with 5.3.1 the second value of the volume flow may be a maximum of 80 % above the first value. 4.6.3 Durability of the standstill opening device When tested in accordance with 5.1.4 the stands
...