Explosive atmospheres -- Part 10-1: Classification of areas - Explosive gas atmospheres

This part of IEC 60079 is concerned with the classification of areas where flammable gas or vapour or mist hazards (see Notes 1, 2 and 3) may arise and may then be used as a basis to support the proper selection and installation of equipment for use in a hazardous area. It is intended to be applied where there may be an ignition hazard due to the presence of flammable gas or vapour, mixed with air under normal atmospheric conditions (see Note 4), but it does not apply to a) mines susceptible to firedamp; b) the processing and manufacture of explosives; c) areas where a hazard may arise due to the presence of combustible dusts or fibres (refer to IEC 61241-10 / IEC 60079-10-2); d) catastrophic failures which are beyond the concept of abnormality dealt with in this standard (see Note 5); e) rooms used for medical purposes; f) domestic premises. This standard does not take into account the effects of consequential damage. Definitions and explanations of terms are given together with the main principles and procedures relating to hazardous area classification. For detailed recommendations regarding the extent of the hazardous areas in specific industries or applications, reference may be made to national or industry codes relating to those applications.

Explosionsfähige Atmosphäre – Teil 10-1: Einteilung der Bereiche – Gasexplosionsgefährdete Bereiche

Atmosphères explosives -- Partie 10-1: Classement des emplacements - Atmosphères explosives gazeuses

La CEI 60079-10-1:2008 est relative au classement des emplacements dans lesquels des risques dus à des gaz, vapeurs ou brouillards inflammables peuvent apparaître, et ainsi constituer une base pour le choix et l'installation corrects du matériel utilisé dans de tels emplacements. Elle est destinée à être appliquée là où il peut exister un danger d'inflammation du fait de la présence de gaz ou vapeurs inflammables, en mélange avec l'air, dans les conditions atmosphériques normales; mais elle ne s'applique pas:  a) aux mines grisouteuses;  b) au traitement et à la fabrication des explosifs;  c) aux emplacements dans lesquels un danger dû à la présence de poussières ou fibres inflammables peut apparaître;  d) aux défaillances catastrophiques, qui dépassent le concept d'anormalité traité dans la présente norme;  e) aux locaux utilisés à  des fins médicales;  f) aux locaux à usage domestique.  Cette première édition de la CEI 60079-10-1 annule et remplace la quatrième édition de la CEI 60079-10, publiée en 2002, et constitue une révision technique. Les principales modifications techniques suivantes ont été apportées par rapport à l'édition précédente:  - introduction de l'Annexe D qui traite du danger d'explosion du brouillard inflammable généré par l'échappement sous pression de liquides au point d'éclair élevé;  - introduction de l'Article A.3 (taux de dégagement) qui donne des équations thermodynamiques pour le taux de dégagement avec des exemples pour l'estimation du taux de dégagement des fluides et de gaz.

Eksplozivne atmosfere - 10-1. del: Razvrstitev prostorov - Eksplozivne plinske atmosfere (IEC 60079-10-1:2008)

General Information

Status
Withdrawn
Publication Date
18-Aug-2009
Withdrawal Date
08-Jan-2018
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
09-Jan-2018
Due Date
01-Feb-2018
Completion Date
09-Jan-2018

Relations

Buy Standard

Standard
EN 60079-10-1:2009 (EN)
English language
69 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day
Standard
EN 60079-10-1:2009 (FR)
French language
75 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 60079-10-1:2009
01-september-2009
1DGRPHãþD
SIST EN 60079-10:2003
Eksplozivne atmosfere - 10-1. del: Razvrstitev prostorov - Eksplozivne plinske
atmosfere (IEC 60079-10-1:2008)
Explosive atmospheres -- Part 10-1: Classification of areas - Explosive gas atmospheres
Explosionsfähige Atmosphäre – Teil 10-1: Einteilung der Bereiche –
Gasexplosionsgefährdete Bereiche
Atmosphères explosives -- Partie 10-1: Classement des emplacements - Atmosphères
explosives gazeuses
Ta slovenski standard je istoveten z: EN 60079-10-1:2009
ICS:
29.260.20 (OHNWULþQLDSDUDWL]D Electrical apparatus for
HNVSOR]LYQDR]UDþMD explosive atmospheres
SIST EN 60079-10-1:2009 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 60079-10-1:2009

---------------------- Page: 2 ----------------------

SIST EN 60079-10-1:2009

EUROPEAN STANDARD
EN 60079-10-1

NORME EUROPÉENNE
March 2009
EUROPÄISCHE NORM

ICS 29.260.20 Supersedes EN 60079-10:2003


English version


Explosive atmospheres -
Part 10-1: Classification of areas -
Explosive gas atmospheres
(IEC 60079-10-1:2008)


Atmosphères explosives -  Explosionsfähige Atmosphäre -
Partie 10-1: Classement Teil 10-1: Einteilung der Bereiche -
des emplacements - Gasexplosionsgefährdete Bereiche
Atmosphères explosives gazeuses (IEC 60079-10-1:2008)
(CEI 60079-10-1:2008)




This European Standard was approved by CENELEC on 2009-03-01. CENELEC members are bound to comply
with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and notified
to the Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the
Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: avenue Marnix 17, B - 1000 Brussels


© 2009 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 60079-10-1:2009 E

---------------------- Page: 3 ----------------------

SIST EN 60079-10-1:2009
EN 60079-10-1:2009 - 2 -
Foreword
The text of document 31J/159/FDIS, future edition 1 of IEC 60079-10-1, prepared by SC 31J,
Classification of hazardous areas and installation requirements, of IEC TC 31, Equipment for explosive
atmospheres, was submitted to the IEC-CENELEC parallel vote and was approved by CENELEC as
EN 60079-10-1 on 2009-03-01.
This European Standard supersedes EN 60079-10:2003.
The significant technical changes with respect to EN 60079-10:2003 are as follows:
– introduction of Annex D which deals with explosion hazard from flammable mists generated by the
release under pressure of high flash point liquids;
– introduction of Clause A.3 (release rate) which gives thermodynamic equations for release rate with a
number of examples for estimating release rate of fluids and gases.
The following dates were fixed:
– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2009-12-01
– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2012-03-01
Annexes ZA and ZB have been added by CENELEC.
__________
Endorsement notice
The text of the International Standard IEC 60079-10-1:2008 was approved by CENELEC as a European
Standard without any modification.
__________

---------------------- Page: 4 ----------------------

SIST EN 60079-10-1:2009
- 3 - EN 60079-10-1:2009
Annex ZA
(normative)

Normative references to international publications
with their corresponding European publications

The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.

NOTE  When an international publication has been modified by common modifications, indicated by (mod), the relevant EN/HD
applies.

Publication Year Title EN/HD Year

1)
IEC 60050-426 - International Electrotechnical Vocabulary - -
(IEV) -
Part 426: Equipment for explosive
atmospheres


1) 1)
IEC 60079-0 - Explosive atmospheres - EN 60079-0 -
Part 0: Equipment - General requirements


1)
IEC 60079-4 - Electrical apparatus for explosive gas - -
atmospheres -
Part 4: Method of test for ignition temperature


1)
IEC 60079-4A - Electrical apparatus for explosive gas - -
atmospheres -
Part 4: Method of test for ignition temperature
First supplement to IEC 60079-4A:1966


1)
IEC/TR 60079-20 - Electrical apparatus for explosive gas - -
atmospheres -
Part 20: Data for flammable gases and
vapours, relating to the use of electrical
apparatus



1)
Undated reference.

---------------------- Page: 5 ----------------------

SIST EN 60079-10-1:2009
EN 60079-10-1:2009 - 4 -
Annex ZB
(informative)

ATEX Categories and Equipment Protection Levels (EPLs)
This European Standard has been written to incorporate the concept of Equipment Protection Levels
(EPLs).
EPLs are analogous to the ATEX Categories, indeed the definitions are identical.
Wherever there is a reference to an EPL in the text it should be equated with the corresponding ATEX
Category:
– EPL ‘Ga’ equates to ATEX Category 1G;
– EPL ‘Gb’ equates to ATEX Category 2G;
– EPL ‘Gc’ equates to ATEX Category 3G;
– EPL ‘Da’ equates to ATEX Category 1D;
– EPL ‘Db’ equates to ATEX Category 2D;
– EPL ‘Dc’ equates to ATEX Category 3D.
__________

---------------------- Page: 6 ----------------------

SIST EN 60079-10-1:2009
IEC 60079-10-1
Edition 1.0 2008-12
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE


Explosive atmospheres –
Part 10-1: Classification of areas – Explosive gas atmospheres

Atmosphères explosives –
Partie 10-1: Classement des emplacements – Atmosphères explosives gazeuses

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
XB
CODE PRIX
ICS 29.260.20 ISBN 2-8318-1019-3
® Registered trademark of the International Electrotechnical Commission
Marque déposée de la Commission Electrotechnique Internationale

---------------------- Page: 7 ----------------------

SIST EN 60079-10-1:2009
– 2 – 60079-10-1 © IEC:2008
CONTENTS
FOREWORD.3
INTRODUCTION.5
1 Scope.6
2 Normative references .7
3 Terms and definitions .7
4 General .10
4.1 Safety principles.10
4.2 Area classification objectives .11
5 Area classification procedure.12
5.1 General .12
5.2 Sources of release .12
5.3 Type of zone .13
5.4 Extent of zone .13
5.4.1 Release rate of gas or vapour.13
5.4.2 Lower explosive limit (LEL).14
5.4.3 Ventilation .14
5.4.4 Relative density of the gas or vapour when it is released.15
5.4.5 Other parameters to be considered.15
5.4.6 Illustrative examples.15
6 Ventilation .16
6.1 General .16
6.2 Main types of ventilation.16
6.3 Degree of ventilation .16
6.4 Availability of ventilation.17
7 Documentation .17
7.1 General .17
7.2 Drawings, data sheets and tables.17
Annex A (informative) Examples of sources of release and release rate .18
Annex B (informative) Ventilation.24
Annex C (informative) Examples of hazardous area classification .40
Annex D (informative) Flammable mists .63
Bibliography.65

Figure C.1 – Preferred symbols for hazardous area zones .41
Figure C.2 – Schematic approach to the classification of hazardous areas.62

Table A.1 – Effect of openings on grade of release .19
Table B.1 – Influence of independent ventilation on type of zone .31
Table B.2 – Procedure for summation of multiple releases within location V .32
o
Table B.3 – Procedure for summation of multiple primary grade releases .32
Table C.1 − Hazardous area classification data sheet – Part I: Flammable material list
and characteristics.60
Table C.2 − Hazardous area classification data sheet − Part II: List of sources of
release .61

---------------------- Page: 8 ----------------------

SIST EN 60079-10-1:2009
60079-10-1 © IEC:2008 – 3 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________

EXPLOSIVE ATMOSPHERES –

Part 10-1: Classification of areas –
Explosive gas atmospheres


FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with an IEC Publication.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 60079-10-1 has been prepared by subcommittee 31J:
Classification of hazardous areas and installation requirements, of IEC technical committee
31: Equipment for explosive atmospheres.
This first edition of IEC 60079-10-1 cancels and replaces the fourth edition of IEC 60079-10,
published in 2002, and constitutes a technical revision.
The significant technical changes with respect to the previous edition are as follows:
• Introduction of Annex D which deals with explosion hazard from flammable mists
generated by the release under pressure of high flash point liquids.
• Introduction of Clause A.3 (release rate) which gives thermodynamic equations for release
rate with a number of examples for estimating release rate of fluids and gases.

---------------------- Page: 9 ----------------------

SIST EN 60079-10-1:2009
– 4 – 60079-10-1 © IEC:2008
The text of this standard is based on the following documents:
FDIS Report on voting
31J/159/FDIS 31J/160/RVD

Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
A list of all parts of the IEC 60079 series, under the general title Explosive atmospheres, can
be found on the IEC website.
The committee has decided that the contents of this publication will remain unchanged until
the maintenance result date indicated on the IEC web site under "http://webstore.iec.ch" in
the data related to the specific publication. At this date, the publication will be
• reconfirmed;
• withdrawn;
• replaced by a revised edition, or
• amended.

---------------------- Page: 10 ----------------------

SIST EN 60079-10-1:2009
60079-10-1 © IEC:2008 – 5 –
INTRODUCTION
In areas where dangerous quantities and concentrations of flammable gas or vapour may
arise, protective measures are to be applied in order to reduce the risk of explosions. This
part of IEC 60079 sets out the essential criteria against which the ignition hazards can be
assessed, and gives guidance on the design and control parameters which can be used in
order to reduce such a hazard.

---------------------- Page: 11 ----------------------

SIST EN 60079-10-1:2009
– 6 – 60079-10-1 © IEC:2008
EXPLOSIVE ATMOSPHERES –

Part 10-1: Classification of areas –
Explosive gas atmospheres



1 Scope
This part of IEC 60079 is concerned with the classification of areas where flammable gas or
vapour or mist hazards (see Notes 1, 2 and 3) may arise and may then be used as a basis to
support the proper selection and installation of equipment for use in a hazardous area.
It is intended to be applied where there may be an ignition hazard due to the presence of
flammable gas or vapour, mixed with air under normal atmospheric conditions (see Note 4),
but it does not apply to
a) mines susceptible to firedamp;
b) the processing and manufacture of explosives;
c) areas where a hazard may arise due to the presence of combustible dusts or fibres (refer
to IEC 61241-10 / IEC 60079-10-2);
d) catastrophic failures which are beyond the concept of abnormality dealt with in this
standard (see Note 5);
e) rooms used for medical purposes;
f) domestic premises.
This standard does not take into account the effects of consequential damage.
Definitions and explanations of terms are given together with the main principles and
procedures relating to hazardous area classification.
For detailed recommendations regarding the extent of the hazardous areas in specific
industries or applications, reference may be made to national or industry codes relating to
those applications.
NOTE 1 Flammable mists may form or be present at the same time as flammable vapours. Liquids not considered
to be hazardous in terms of this standard (due to the flash point), when released under pressure may also generate
flammable mists. In such cases, the strict application of area classification for gases and vapours may not be
appropriate as the basis for selection of equipment.
Information on flammable mists is provided in Annex D.
NOTE 2 The use of IEC 60079-14 for selection of equipment and installations is not required for mist hazards.
NOTE 3 For the purpose of this standard, an area is a three-dimensional region or space.
NOTE 4 Atmospheric conditions include variations above and below reference levels of 101,3 kPa (1 013 mbar)
and 20 °C (293 K), provided that the variations have a negligible effect on the explosion properties of the
flammable materials.
NOTE 5 Catastrophic failure in this context is applied, for example, to the rupture of a process vessel or pipeline
and events that are not predictable.
NOTE 6 In any process plant, irrespective of size, there may be numerous sources of ignition apart from those
associated with equipment. Appropriate precautions will be necessary to ensure safety in this context. This
standard may be used with judgement for other ignition sources.

---------------------- Page: 12 ----------------------

SIST EN 60079-10-1:2009
60079-10-1 © IEC:2008 – 7 –
2 Normative references
The following referenced documents are indispensable for the application of this document.
For dated references, only the edition cited applies. For undated references, the latest edition
of the referenced document (including any amendments) applies.
IEC 60050-426, International Electrotechnical Vocabulary (IEV) – Part 426: Equipment for
explosive atmospheres
IEC 60079-0, Explosive atmospheres – Part 0: Equipment – General requirements
IEC 60079-4, Electrical apparatus for explosive gas atmospheres – Part 4: Method of test for
ignition temperature
IEC 60079-4A, First supplement to IEC 60079-4 (1966), Electrical apparatus for explosive gas
atmospheres – Part 4: Method of test for ignition temperature
IEC 60079-20, Electrical apparatus for explosive gas atmospheres – Part 20: Data for
flammable gases and vapours, relating to the use of electrical apparatus
3 Terms and definitions
For the purposes of this document, the terms and definitions given in IEC 60079-0 and the
following apply.
NOTE Additional definitions applicable to explosive atmospheres can be found in the IEC 60050-426.
3.1
explosive atmosphere
mixture with air, under atmospheric conditions, of flammable substances in the form of gas,
vapour, dust, fibres, or flyings which, after ignition, permits self-sustaining propagation
[IEC 60079-0, definition 3.22]
3.2
explosive gas atmosphere
mixture with air, under atmospheric conditions, of flammable substances in the form of gas or
vapour, which, after ignition, permits self-sustaining flame propagation
[IEC 60079-0, definition 3.24]
NOTE 1 Although a mixture which has a concentration above the upper explosive limit (UEL) is not an explosive
gas atmosphere, it can readily become so and, in certain cases for area classification purposes, it is advisable to
consider it as an explosive gas atmosphere.
NOTE 2 There are some gases which are explosive with the concentration of 100 %.
3.3
hazardous area (on account of explosive gas atmospheres)
an area in which an explosive gas atmosphere is or may be expected to be present, in
quantities such as to require special precautions for the construction, installation and use of
equipment
3.4
non-hazardous area (on account of explosive gas atmospheres)
an area in which an explosive gas atmosphere is not expected to be present in quantities
such as to require special precautions for the construction, installation and use of equipment

---------------------- Page: 13 ----------------------

SIST EN 60079-10-1:2009
– 8 – 60079-10-1 © IEC:2008
3.5
zones
hazardous areas are classified into zones based upon the frequency of the occurrence and
duration of an explosive gas atmosphere, as follows:
3.6
zone 0
an area in which an explosive gas atmosphere is present continuously or for long periods or
frequently
3.7
zone 1
an area in which an explosive gas atmosphere is likely to occur in normal operation
occasionally
3.8
zone 2
area in which an explosive gas atmosphere is not likely to occur in normal operation but, if it
does occur, will persist for a short period only
[IEV 426-03-05]
NOTE Indications of the frequency of the occurrence and duration may be taken from codes relating to specific
industries or applications.
3.9
source of release
a point or location from which a gas, vapour, mist or liquid may be released into the
atmosphere so that an explosive gas atmosphere could be formed
IEV 426-03-06, modified]
3.10
grades of release
there are three basic grades of release, as listed below in order of decreasing frequency and
likelihood of the explosive gas atmosphere being present:
a) continuous grade;
b) primary grade;
c) secondary grade.
A source of release may give rise to any one of these grades of release, or to a combination
of more than one
3.11
continuous grade of release
release which is continuous or is expected to occur frequently or for long periods
3.12
primary grade of release
release which can be expected to occur periodically or occasionally during normal operation
3.13
secondary grade of release
release which is not expected to occur in normal operation and, if it does occur, is likely to do
so only infrequently and for short periods

---------------------- Page: 14 ----------------------

SIST EN 60079-10-1:2009
60079-10-1 © IEC:2008 – 9 –
3.14
release rate
quantity of flammable gas, vapour or mist emitted per unit time from the source of release
3.15
normal operation
situation when the equipment is operating within its designed parameters
NOTE 1 Minor releases of flammable material may be part of normal operation. For example, releases from seals
which rely on wetting by the fluid which is being pumped are considered to be minor releases.
NOTE 2 Failures (such as the breakdown of pump seals, flange gaskets or spillages caused by accidents) which
involve urgent repair or shut-down are not considered to be part of normal operation nor are they considered to be
catastrophic.
NOTE 3 Normal operation includes start-up and shut-down conditions.
3.16
ventilation
movement of air and its replacement with fresh air due to the effects of wind, temperature
gradients, or artificial means (for example, fans or extractors)
3.17
lower explosive limit (LEL)
concentration of flammable gas, vapour or mist in air below which an explosive gas
atmosphere will not be formed
[IEV 426-02-09]
3.18
upper explosive limit (UEL)
concentration of flammable gas, vapour or mist in air, above which an explosive gas
atmosphere will not be formed
[IEV 426-02-10]
3.19
relative density of a gas or a vapour
density of a gas or a vapour relative to the density of air at the same pressure and at the
same temperature (air is equal to 1,0)
3.20
flammable material (flammable substance)
material which is flammable of itself, or is capable of producing a flammable gas, vapour or
mist
3.21
flammable liquid
liquid capable of producing a flammable vapour under any foreseeable operating conditions
NOTE An example of a foreseeable operating condition is one in which the flammable liquid is handled at
temperatures close to or above its flash point.
3.22
flammable gas or vapour
gas or vapour which, when mixed with air in certain proportions, will form an explosive gas
atmosphere
3.23
flammable mist
droplets of liquid, dispersed in air so as to form an explosive atmosphere

---------------------- Page: 15 ----------------------

SIST EN 60079-10-1:2009
– 10 – 60079-10-1 © IEC:2008
3.24
flashpoint
lowest liquid temperature at which, under certain standardized conditions, a liquid gives off
vapours in a quantity such as to be capable of forming an ignitable vapour/air mixture
3.25
boiling point
temperature of a liquid boiling at an ambient pressure of 101,3 kPa (1 013 mbar)
NOTE The initial boiling point that should be used for liquid mixtures is to indicate the lowest value of the boiling
point for the range of liquids present, as determined in a standard laboratory distillation without fractionation.
3.26
vapour pressure
pressure exerted when a solid or liquid is in equilibrium with its own vapour. It is a function of
the substance and of the temperature
3.27
ignition temperature of an explosive gas atmosphere
lowest temperature of a heated surface which, under specified conditions according to
IEC 60079-4, will ignite a flammable substance in the form of a gas or vapour mixture with air
[IEC 60079-0, definition 3.26]
3.28
extent of zone
distance in any direction from the source of release to the point where the gas/air mixture has
been diluted by air to a value below the lower explosive limit
3.29
liquefied flammable gas
flammable material which is stored or handled as a liquid and which at ambient temperature
and atmospheric pressure is a flammable gas
4 General
4.1 Safety principles
Installations in which flammable materials are handled or stored should be designed,
operated and maintained so that any releases of flammable material, and consequently the
extent of hazardous areas, are kept to a minimum, whether in normal operation or otherwise,
with regard to frequency, duration and quantity.
It is important to examine those parts of process equipment and systems from which release
of flammable material may arise and to consider modifying the design to minimise the
likelihood and frequency of such releases and the quantity and rate of release of material.
These fundamental considerations should be examined at an early stage of the design
development of any process plant and should also receive prime attention in carrying out the
area classification study.
In the case of activities other than those of normal operation, e.g. commissioning or
maintenance, the area classification may not be valid. It is expected that this would be dealt
with by a safe system of work.
In a situation in which th
...

SLOVENSKI STANDARD
SIST EN 60079-10-1:2009
01-september-2009
1DGRPHãþD
SIST EN 60079-10:2003
Eksplozivne atmosfere - 10-1. del: Razvrstitev prostorov - Eksplozivne plinske
atmosfere (IEC 60079-10-1:2008)
Explosive atmospheres -- Part 10-1: Classification of areas - Explosive gas atmospheres
Explosionsfähige Atmosphäre – Teil 10-1: Einteilung der Bereiche –
Gasexplosionsgefährdete Bereiche
Atmosphères explosives -- Partie 10-1: Classement des emplacements - Atmosphères
explosives gazeuses
Ta slovenski standard je istoveten z: EN 60079-10-1:2009
ICS:
29.260.20 (OHNWULþQLDSDUDWL]D Electrical apparatus for
HNVSOR]LYQDR]UDþMD explosive atmospheres
SIST EN 60079-10-1:2009 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 60079-10-1:2009

---------------------- Page: 2 ----------------------

SIST EN 60079-10-1:2009

NORME EUROPÉENNE
EN 60079-10-1

EUROPÄISCHE NORM
Mars 2009
EUROPEAN STANDARD

ICS 29.260.20 Remplace EN 60079-10:2003


Version française


Atmosphères explosives -
Partie 10-1: Classement des emplacements -
Atmosphères explosives gazeuses
(CEI 60079-10-1:2008)


Explosionsfähige Atmosphäre -  Explosive atmospheres -
Teil 10-1: Einteilung der Bereiche - Part 10-1: Classification of areas -
Gasexplosionsgefährdete Bereiche Explosive gas atmospheres
(IEC 60079-10-1:2008) (IEC 60079-10-1:2008)




La présente Norme Européenne a été adoptée par le CENELEC le 2009-03-01. Les membres du CENELEC
sont tenus de se soumettre au Règlement Intérieur du CEN/CENELEC qui définit les conditions dans lesquelles
doit être attribué, sans modification, le statut de norme nationale à la Norme Européenne.

Les listes mises à jour et les références bibliographiques relatives à ces normes nationales peuvent être
obtenues auprès du Secrétariat Central ou auprès des membres du CENELEC.

La présente Norme Européenne existe en trois versions officielles (allemand, anglais, français). Une version
dans une autre langue faite par traduction sous la responsabilité d'un membre du CENELEC dans sa langue
nationale, et notifiée au Secrétariat Central, a le même statut que les versions officielles.

Les membres du CENELEC sont les comités électrotechniques nationaux des pays suivants: Allemagne,
Autriche, Belgique, Bulgarie, Chypre, Danemark, Espagne, Estonie, Finlande, France, Grèce, Hongrie, Irlande,
Islande, Italie, Lettonie, Lituanie, Luxembourg, Malte, Norvège, Pays-Bas, Pologne, Portugal, République
Tchèque, Roumanie, Royaume-Uni, Slovaquie, Slovénie, Suède et Suisse.

CENELEC
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
European Committee for Electrotechnical Standardization

Secrétariat Central: avenue Marnix 17, B - 1050 Bruxelles


© 2009 CENELEC - Tous droits d'exploitation sous quelque forme et de quelque manière que ce soit réservés dans le monde entier aux
membres du CENELEC.
Ref. n° EN 60079-10-1:2009 F

---------------------- Page: 3 ----------------------

SIST EN 60079-10-1:2009
EN 60079-10-1:2009 - 2 -
Avant-propos
Le texte du document 31J/159/FDIS, future édition 1 de la CEI 60079-10-1, préparé par le SC 31J,
Classification des emplacements dangereux et règles d'installation, du CE 31 de la CEI, Equipements
pour atmosphères explosives, a été soumis au vote parallèle CEI-CENELEC et a été approuvé par le
CENELEC comme EN 60079-10-1 le 2009-03-01.
Cette Norme Européenne remplace la EN 60079-10:2003.
Les principales modifications techniques suivantes ont été apportées par rapport à la EN 60079-10:2003:
– introduction de l’Annexe D qui traite du danger d’explosion du brouillard inflammable généré par
l’échappement sous pression de liquides au point d’éclair élevé;
– introduction de l’Article A.3 (taux de dégagement) qui donne des équations thermodynamiques pour le
taux de dégagement avec des exemples pour l’estimation du taux de dégagement des fluides et de
gaz.
Les dates suivantes ont été fixées:
– date limite à laquelle la EN doit être mise en application
au niveau national par publication d'une norme
nationale identique ou par entérinement (dop) 2009-12-01
– date limite à laquelle les normes nationales
conflictuelles doivent être annulées (dow) 2012-03-01
Les Annexes ZA et ZB ont été ajoutées par le CENELEC.
__________
Notice d’entérinement
Le texte de la Norme internationale CEI 60079-10-1:2008 a été approuvé par le CENELEC comme
Norme Européenne sans aucune modification.
__________

---------------------- Page: 4 ----------------------

SIST EN 60079-10-1:2009
- 3 - EN 60079-10-1:2009
Annexe ZA
(normative)

Références normatives à d'autres publications internationales
avec les publications européennes correspondantes

Les documents de référence suivants sont indispensables pour l'application du présent document. Pour
les références datées, seule l'édition citée s'applique. Pour les références non datées, la dernière édition
du document de référence s'applique (y compris les éventuels amendements).

NOTE  Dans le cas où une publication internationale est modifiée par des modifications communes, indiqué par (mod), l'EN / le HD
correspondant(e) s'applique.

Publication Année Titre EN/HD Année

1)
CEI 60050-426 - Vocabulaire Electrotechnique International - -
(VEI) -
Partie 426: Matériel pour atmosphères
explosives


1) 1)
CEI 60079-0 - Atmosphères explosives - EN 60079-0 -
Partie 0: Matériel - Exigences générales


1)
CEI 60079-4 - Matériel électrique pour atmosphères - -
explosives gazeuses -
Partie 4: Méthode d'essai pour la
détermination de la température
d'inflammation


1)
CEI 60079-4A - Matériel électrique pour atmosphères - -
explosives gazeuses -
Partie 4: Méthode d'essai pour la
détermination de la température
d'inflammation
Premier complément à la CEI 60079-4:1966


1)
CEI/TR 60079-20 - Matériel électrique pour atmosphères - -
explosives gazeuses -
Partie 20: Données pour gaz et vapeurs
inflammables, en relation avec l'utilisation des
matériels électriques



1)
Référence non datée.

---------------------- Page: 5 ----------------------

SIST EN 60079-10-1:2009
EN 60079-10-1:2009 - 4 -
Annexe ZB
(informative)

Catégories ATEX et niveaux de protection de matériel (EPL)
La présente Norme Européenne à été rédigée pour introduire le concept des niveaux de protection de
matériel (EPLs pour ‘Equipment Protection Levels’).
Les EPL sont analogues aux catégories ATEX et leurs définitions sont identiques.
Chaque fois qu’il est fait référence à un EPL dans le texte, il convient de le considérer équivalent à la
catégorie ATEX correspondante:
– EPL ‘Ga’ est équivalent à la catégorie ATEX 1G;
– EPL ‘Gb’ est équivalent à la catégorie ATEX 2G;
– EPL ‘Gc’ est équivalent à la catégorie ATEX 3G;
– EPL ‘Da’ est équivalent à la catégorie ATEX 1D;
– EPL ‘Db’ est équivalent à la catégorie ATEX 2D;
– EPL ‘Dc’ est équivalent à la catégorie ATEX 3D.
__________

---------------------- Page: 6 ----------------------

SIST EN 60079-10-1:2009
IEC 60079-10-1
Edition 1.0 2008-12
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE


Explosive atmospheres –
Part 10-1: Classification of areas – Explosive gas atmospheres

Atmosphères explosives –
Partie 10-1: Classement des emplacements – Atmosphères explosives gazeuses

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
XB
CODE PRIX
ICS 29.260.20 ISBN 2-8318-1019-3
® Registered trademark of the International Electrotechnical Commission
Marque déposée de la Commission Electrotechnique Internationale

---------------------- Page: 7 ----------------------

SIST EN 60079-10-1:2009
– 66 – 60079-10-1 © CEI:2008
SOMMAIRE
AVANT-PROPOS.68
INTRODUCTION.70
1 Domaine d’application .71
2 Références normatives.72
3 Termes et définitions .72
4 Généralités.76
4.1 Principes de sécurité.76
4.2 Objectifs du classement des emplacements dangereux .76
5 Procédure de classement des emplacements dangereux .77
5.1 Généralités.77
5.2 Sources de dégagement.78
5.3 Type de zone .79
5.4 Étendue de la zone .79
5.4.1 Taux de dégagement de gaz ou vapeur .79
5.4.2 Limite inférieure d’explosivité (LIE).80
5.4.3 Ventilation .80
5.4.4 Densité relative du gaz ou de la vapeur au moment de son
dégagement .80
5.4.5 Autres paramètres à considérer.81
5.4.6 Exemples .81
6 Ventilation .82
6.1 Généralités.82
6.2 Principaux types de ventilation .82
6.3 Degré de ventilation .82
6.4 Disponibilité de la ventilation .83
7 Documentation .83
7.1 Généralités.83
7.2 Plans, feuilles de données et tableaux .83
Annexe A (informative) Exemples de sources de dégagement et de taux de
dégagement.85
Annexe B (informative) Ventilation .92
Annexe C (informative) Exemples de classements d’emplacements dangereux .109
Annexe D (informative) Brouillards inflammables .133
Bibliographie.135

Figure C.1 – Symboles préférés pour les zones d’emplacements dangereux.110
Figure C.2 – Approche schématique pour le classement des emplacements dangereux.132

Tableau A.1 – Effet des ouvertures sur le degré de dégagement .86
Tableau B.1 – Influence de la ventilation sur le type de zone .100
Tableau B.2 – Procédure pour la sommation de plusieurs dégagements dans un
volume V .101
o
Tableau B.3 – Procédure pour la sommation de plusieurs dégagements de premier
degré .101

---------------------- Page: 8 ----------------------

SIST EN 60079-10-1:2009
60079-10-1 © CEI:2008 – 67 –
Tableau C.1 − Feuille de données de classement des emplacements dangereux −
Partie I: Liste des matières inflammables et de leurs caractéristiques .130
Tableau C.2 − Feuille de données de classement des emplacements dangereux −
Partie II: Liste des sources de dégagement .131

---------------------- Page: 9 ----------------------

SIST EN 60079-10-1:2009
– 68 – 60079-10-1 © CEI:2008
COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE
____________

ATMOSPHÈRES EXPLOSIVES –

Partie 10-1: Classement des emplacements –
Atmosphères explosives gazeuses


AVANT-PROPOS
1) La Commission Electrotechnique Internationale (CEI) est une organisation mondiale de normalisation
composée de l'ensemble des comités électrotechniques nationaux (Comités nationaux de la CEI). La CEI a
pour objet de favoriser la coopération internationale pour toutes les questions de normalisation dans les
domaines de l'électricité et de l'électronique. A cet effet, la CEI – entre autres activités – publie des Normes
internationales, des Spécifications techniques, des Rapports techniques, des Spécifications accessibles au
public (PAS) et des Guides (ci-après dénommés "Publication(s) de la CEI"). Leur élaboration est confiée à des
comités d'études, aux travaux desquels tout Comité national intéressé par le sujet traité peut participer. Les
organisations internationales, gouvernementales et non gouvernementales, en liaison avec la CEI, participent
également aux travaux. La CEI collabore étroitement avec l'Organisation Internationale de Normalisation (ISO),
selon des conditions fixées par accord entre les deux organisations.
2) Les décisions ou accords officiels de la CEI concernant les questions techniques représentent, dans la mesure
du possible, un accord international sur les sujets étudiés, étant donné que les Comités nationaux de la CEI
intéressés sont représentés dans chaque comité d’études.
3) Les Publications de la CEI se présentent sous la forme de recommandations internationales et sont agréées
comme telles par les Comités nationaux de la CEI. Tous les efforts raisonnables sont entrepris afin que la CEI
s'assure de l'exactitude du contenu technique de ses publications; la CEI ne peut pas être tenue responsable
de l'éventuelle mauvaise utilisation ou interprétation qui en est faite par un quelconque utilisateur final.
4) Dans le but d'encourager l'uniformité internationale, les Comités nationaux de la CEI s'engagent, dans toute la
mesure possible, à appliquer de façon transparente les Publications de la CEI dans leurs publications
nationales et régionales. Toutes divergences entre toutes Publications de la CEI et toutes publications
nationales ou régionales correspondantes doivent être indiquées en termes clairs dans ces dernières.
5) La CEI n’a prévu aucune procédure de marquage valant indication d’approbation et n'engage pas sa
responsabilité pour les équipements déclarés conformes à une de ses Publications.
6) Tous les utilisateurs doivent s'assurer qu'ils sont en possession de la dernière édition de cette publication.
7) Aucune responsabilité ne doit être imputée à la CEI, à ses administrateurs, employés, auxiliaires ou
mandataires, y compris ses experts particuliers et les membres de ses comités d'études et des Comités
nationaux de la CEI, pour tout préjudice causé en cas de dommages corporels et matériels, ou de tout autre
dommage de quelque nature que ce soit, directe ou indirecte, ou pour supporter les coûts (y compris les frais
de justice) et les dépenses découlant de la publication ou de l'utilisation de cette Publication de la CEI ou de
toute autre Publication de la CEI, ou au crédit qui lui est accordé.
8) L'attention est attirée sur les références normatives citées dans cette publication. L'utilisation de publications
référencées est obligatoire pour une application correcte de la présente publication.
9) L’attention est attirée sur le fait que certains des éléments de la présente Publication de la CEI peuvent faire
l’objet de droits de propriété intellectuelle ou de droits analogues. La CEI ne saurait être tenue pour
responsable de ne pas avoir identifié de tels droits de propriété et de ne pas avoir signalé leur existence.
La Norme internationale CEI 60079-10-1 a été établie par le sous-comité 31J: Classification
des emplacements dangereux et règles d’installation, du comité d'études 31 de la CEI:
Equipements pour atmosphères explosives.
Cette première édition de la CEI 60079-10-1 annule et remplace la quatrième édition de la
CEI 60079-10, publiée en 2002, et constitue une révision technique.
Les principales modifications techniques suivantes ont été apportées par rapport à l’édition
précédente:
• Introduction de l’Annexe D qui traite du danger d’explosion du brouillard inflammable
généré par l’échappement sous pression de liquides au point d’éclair élevé.
• Introduction de l’Article A.3 (taux de dégagement) qui donne des équations
thermodynamiques pour le taux de dégagement avec des exemples pour l’estimation du
taux de dégagement des fluides et de gaz.

---------------------- Page: 10 ----------------------

SIST EN 60079-10-1:2009
60079-10-1 © CEI:2008 – 69 –
Le texte de cette norme est issu des documents suivants:
FDIS Rapport de vote
31J/159/FDIS 31J/160/RVD

Le rapport de vote indiqué dans le tableau ci-dessus donne toute information sur le vote ayant
abouti à l'approbation de cette norme.
Cette publication a été rédigée selon les Directives ISO/CEI, Partie 2.
Une liste de toutes les parties de la série CEI 60079, présentée sous le titre général
Atmosphères explosives, peut être consultée sur le site web de la CEI.
Le comité a décidé que le contenu de cette publication ne sera pas modifié avant la date de
maintenance indiquée sur le site web de la CEI sous "http://webstore.iec.ch" dans les
données relatives à la publication recherchée. A cette date, la publication sera
• reconduite,
• supprimée,
• remplacée par une édition révisée, ou
• amendée.

---------------------- Page: 11 ----------------------

SIST EN 60079-10-1:2009
– 70 – 60079-10-1 © CEI:2008
INTRODUCTION
Dans les emplacements où des quantités et concentrations dangereuses de gaz ou vapeurs
inflammables peuvent apparaître, des mesures préventives pour réduire le risque
d'explosions seront appliquées. La présente partie de la CEI 60079 expose les critères
essentiels par rapport auxquels les dangers d'inflammation peuvent être évalués et donne des
lignes directrices, relatives aux paramètres de conception et d'exploitation, que l'on peut
utiliser pour réduire ce danger.

---------------------- Page: 12 ----------------------

SIST EN 60079-10-1:2009
60079-10-1 © CEI:2008 – 71 –
ATMOSPHÈRES EXPLOSIVES –

Partie 10-1: Classement des emplacements –
Atmosphères explosives gazeuses



1 Domaine d’application
La présente partie de la CEI 60079 est relative au classement des emplacements dans
lesquels des risques dus à des gaz, vapeurs ou brouillards inflammables (voir Notes 1, 2 et 3)
peuvent apparaître, et ainsi constituer une base pour le choix et l’installation corrects du
matériel utilisé dans de tels emplacements.
Elle est destinée à être appliquée là où il peut exister un danger d'inflammation du fait de la
présence de gaz ou vapeurs inflammables, en mélange avec l'air, dans les conditions
atmosphériques normales (voir Note 4); mais elle ne s'applique pas:
a) aux mines grisouteuses;
b) au traitement et à la fabrication des explosifs;
c) aux emplacements dans lesquels un danger dû à la présence de poussières ou fibres
inflammables peut apparaître (voir la CEI 61241-10 / CEI 60079-10-2);
d) aux défaillances catastrophiques, qui dépassent le concept d'anormalité traité dans la
présente norme (voir Note 5);
e) aux locaux utilisés à des fins médicales;
f) aux locaux à usage domestique.
La présente norme ne prend pas en compte les effets des sinistres induits.
Des définitions et explications des termes y sont données ainsi que les grands principes et
procédures relatifs au classement des emplacements dangereux.
On pourra se référer aux réglementations nationales ou industrielles relatives à des
applications particulières pour trouver des recommandations détaillées, quant à l'étendue des
emplacements dangereux dans ces industries ou applications.
NOTE 1 Des brouillards inflammables peuvent se former ou être présents en même temps que les vapeurs
inflammables. Les liquides qui ne sont pas considérés comme dangereux suivant les termes de cette norme (en
raison du point d’éclair), lorsqu'ils sortent sous pression, peuvent également générer des brouillards inflammables.
Dans de tels cas, l’application stricte de classement des zones pour les gaz et les vapeurs peut ne pas être
appropriée comme base pour la sélection du matériel.
Des informations relatives aux brouillards inflammables sont données à l’Annexe D.
NOTE 2 L’utilisation de la CEI 60079-14 pour la sélection du matériel et des installations n’est pas nécessaire
pour les dangers dus au brouillard.
NOTE 3 Pour les besoins de la présente norme, un emplacement désigne un secteur ou un espace
tridimensionnel.
NOTE 4 Les conditions atmosphériques englobent les écarts au-dessus et au-dessous des niveaux de référence
de 101,3 kPa (1 013 mbar) et 20 °C (293 K) à condition que cela ait un effet négligeable sur les propriétés
explosives des matières inflammables.
NOTE 5 Le terme « défaillance catastrophique » s'applique ici, par exemple, à l’éclatement d’une cuve ou d'une
canalisation et aux événements imprévisibles.
NOTE 6 Dans toute usine, quelle que soit son importance, il peut y avoir de nombreuses sources d'inflammation
en dehors de celles qui sont associées au matériel électrique. Il sera nécessaire dès lors de prendre les
précautions appropriées pour garantir la sécurité. On pourra utiliser avec prudence la présente norme pour ces
autres sources d'inflammation.

---------------------- Page: 13 ----------------------

SIST EN 60079-10-1:2009
– 72 – 60079-10-1 © CEI:2008
2 Références normatives
Les documents référencés suivants sont indispensables pour l’application de ce document.
Pour les références datées, seule l’édition citée s’applique. Pour les références non datées,
la dernière édition du document référencé (incluant tout amendement) s’applique.
CEI 60050-426, Vocabulaire Electrotechnique International (VEI) – Chapitre 426: Matériel
pour atmosphères explosives
CEI 60079-0, Atmosphères explosives – Partie 0: Matériel – Exigences générales
CEI 60079-4, Matériel électrique pour atmosphères explosives gazeuses – Partie 4: Méthode
d’essai pour la détermination de la température d’inflammation
CEI 60079-4A, Premier complément à la CEI 60079-4 (1966), Matériel électrique pour
atmosphères explosives gazeuses – Partie 4: Méthode d’essai pour la détermination de la
température d’inflammation
CEI 60079-20, Matériel électrique pour atmosphères explosives gazeuses – Partie 20:
Données pour gaz et vapeurs inflammables, en relation avec l'utilisation des matériels
électriques
3 Termes et définitions
Pour les besoins du présent document, les termes et définitions donnés dans la CEI 60079-0
et les suivants s’appliquent.
NOTE Des définitions supplémentaires applicables aux atmosphères explosives se trouvent dans la CEI 60050-
426.
3.1
atmosphère explosive
mélange d'air, dans des conditions atmosphériques, avec des substances inflammables sous
forme de gaz, de vapeur, de poussières, de fibres ou de particules en suspension dans
lequel, après inflammation, la combustion se propage à l’ensemble du mélange non brûlé
[définition 3.22 de la CEI 60079-0]
3.2
atmosphère explosive gazeuse
mélange avec l'air, dans des conditions atmosphériques, de substances inflammables sous
forme de gaz, vapeurs ou brouillards dans lequel, après inflammation, la combustion se
propage à l’ensemble du mélange non brûlé
[définition 3.24 de la CEI 60079-0]
NOTE 1 Bien qu'un mélange où la concentration est supérieure à la limite supérieure d'explosivité (LSE) ne soit
pas une atmosphère explosive gazeuse, il peut aisément le devenir et il est recommandé de le considérer comme
tel dans certains cas aux fins de classement des emplacements dangereux.
NOTE 2 Certains gaz sont explosifs pour une concentration de 100 %.
3.3
emplacement dangereux (en raison d’atmosphères explosives gazeuses)
emplacement dans lequel une atmosphère explosive gazeuse est présente, ou dans lequel on
peut s'attendre à ce qu'elle soit présente, en quantités suffisantes pour nécessiter des
précautions particulières pour la construction, l'installation et l'utilisation d’équipements

---------------------- Page: 14 ----------------------

SIST EN 60079-10-1:2009
60079-10-1 © CEI:2008 – 73 –
3.4
emplacement non dangereux (en raison d’atmosphères explosives gazeuses)
emplacement dans lequel on ne prévoit pas qu’une atmosphère explosive gazeuse soit
présente en quantités suffisantes pour nécessiter des précautions particulières pour la
construction, l'installation et l'utilisation d’équipements
3.5
zones
les emplacements dangereux sont classés en zones, d'après la fréquence et la durée de la
présence d'une atmosphère explosive gazeuse, comme suit:
3.6
zone 0
emplacement dans lequel une atmosphère explosive est présente en permanence, ou
pendant de longues périodes ou encore fréquemment
3.7
zone 1
emplacement dans lequel il est probable qu'une atmosphère explosive gazeuse apparaîtra
occasionnellement en fonctionnement normal
3.8
zone 2
emplacement dans lequel une atmosphère explosive gazeuse n’est pas susceptible de se
présenter en fonctionnement normal mais qui si c’est le cas, peut persister uniquement sur
une durée courte
[VEI 426-03-05]
NOTE On peut obtenir des indications intéressant la fréquence d’apparition et la durée dans les réglementations
propres à certaines industries ou applications.
3.9
source de dégagement
point ou endroit d'où un gaz, une vapeur, un brouillard ou un liquide inflammable peut être
libéré dans l'atmosphère, de telle sorte qu'une atmosphère explosive gazeuse soit créée
[VEI 426-03-06, modifiée]
3.10
degrés de dégagement
il y a trois degrés de dégagement de base, énumérés ci-dessous par ordre décroissant de
probabilité de présence d'une atmosphère explosive gazeuse:
a) degré continu;
b) premier degré;
c) deuxième degré.
Une source de dégagement peut donner lieu à n'importe lequel de ces degrés de dégagement
ou à une combinaison de plusieurs d'entre eux
3.11
dégagement de degré continu
dégagement qui se produit en permanence ou dont on s'attend à ce qu'il se produise pendant
de longues périodes

---------------------- Page: 15 ----------------------

SIST EN 60079-10-1:2009
– 74 – 60079-10-1 © CEI:2008
3.12
dégagement de premier degré
dégagement dont on peut s'attendre à ce qu'il se produise de façon périodique ou
occasionnelle en fonctionnement normal
3.13
dégagement de deuxième degré
dégagement dont on ne prévoit pas qu’il se produise en fonctionnement normal et dont il est
probable que, s'il se produit, ce sera seulement à une faible fréquence et pour de courtes
périodes
3.14
taux de dégagement
quantité de gaz, de vapeur ou de brouillard inflammable émise par unité de temps par la
source de dégagement
3.15
fonctionnement normal
situation dans laquelle l'installation fonctionne selon ses paramètres nominaux
NOTE 1 De petits dégagements de matière inflammable peuvent faire partie du fonctionnement normal. Par
exemple, des fuites des garnitures d'étanchéité lubrifiées par le liquide pompé sont considérées comme de petits
dégagements.
NOTE 2 Des défaillances (telles que la rupture de garnitures d'étanchéité de pompe ou de joints de brides ou des
épandages provoqués par des accidents) qui entraînent une réparation ou un arrêt urgent, ne sont pas
considérées comme faisant partie du fonctionnement normal, ni comme étant catastrophiques.
NOTE 3 Un fonctionnement normal comprend des conditions de démarrage et de fermeture.
3.16
ventilation
mouvement de l'air et remplacement de cet air par de l'air frais sous l'action du vent et de
gradients de température ou de moyens artificiels (par exemple ventilateurs ou extracteurs)
3.17
limite inférieure d'explosivité (LEL)
concentration de gaz, de vapeur ou de brouillard inflammable dans l’air, au-dessous de
laquelle une atmosphère explosive gazeuse ne peut pas être formée
[VEI 426-02-09]
3.18
limite supérieure d'explosivité (UEL)
concentration de gaz, de vapeur ou de brouillard inflammable dans l’air, au-dessus de
laquelle une atmosphère inflammable gazeuse ne peut pas être formée
[VEI 426-02-10]
3.19
densité relative d'un gaz ou d'une vapeur
rapport de la densité d'un gaz ou d'une vapeur à la densité de l'air à la même pression et à la
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.