Standard Guide for Flood Testing Horizontal Waterproofing Installations

SCOPE
1.1 This guide provides the user with a method for testing the watertightness of waterproofing installations applied to horizontal surfaces having a slope not greater than 20 mm/m (2 % slope) (1/4 in. per ft).
1.2 This guide is intended for waterproofing installation on parking garages and plaza deck type applications over habitable spaces or on elevated structures, but is not intended for use on building roofing systems. Applicable waterproofing membrane installations that may be tested using this guide are fully adhered or bonded sheet membranes, liquid or fluid applied membranes, or loose laid sheet membranes.
1.3 The procedures presented here are not intended for use on those waterproofing installation applications that are for long-term water storage or continuously submerged environments, such as swimming pools, fountains, tank liners with hydrostatic pressure, or water storage units (storage period greater than 48 h).
1.4 The values stated in SI units are to be regarded as the standard. The values given in parentheses are for information only.
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
30-Jun-2005
Current Stage
Ref Project

Relations

Buy Standard

Guide
ASTM D5957-98(2005) - Standard Guide for Flood Testing Horizontal Waterproofing Installations
English language
5 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:D5957 −98(Reapproved 2005)
Standard Guide for
1
Flood Testing Horizontal Waterproofing Installations
This standard is issued under the fixed designation D5957; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope 2.2 ACI Document:
ACI 515 Guide to the Use of Waterproofing, Dampproofing,
1.1 This guide provides the user with a method for testing
3
Protective, and Decorative Barrier Systems for Concrete
the watertightness of waterproofing installations applied to
horizontal surfaces having a slope not greater than 20 mm/m
3. Terminology
1
(2 % slope) ( ⁄4 in. per ft).
3.1 For definitions of terms relating to roofing and
1.2 This guide is intended for waterproofing installation on
waterproofing, see Terminology D1079.
parking garages and plaza deck type applications over habit-
3.2 Definitions of Terms Specific to This Standard:
ablespacesoronelevatedstructures,butisnotintendedforuse
3.2.1 sacrificial sheet—a material used to form a temporary
on building roofing systems. Applicable waterproofing mem-
seal between a containment assembly and the waterproofing
brane installations that may be tested using this guide are fully
system. The material used for a sacrificial sheet shall not cause
adhered or bonded sheet membranes, liquid or fluid applied
damage nor be detrimental to the primary system.
membranes, or loose laid sheet membranes.
1.3 The procedures presented here are not intended for use
4. Summary of Guide
on those waterproofing installation applications that are for
4.1 This guide uses a series of temporary containment
long-term water storage or continuously submerged
assemblies of pond water on horizontal surfaces to determine
environments, such as swimming pools, fountains, tank liners
the watertightness of waterproofing installations.
with hydrostatic pressure, or water storage units (storage
period greater than 48 h). 4.2 The area to be tested is subdivided as required by the
containment assemblies, and drains within the subdivided area
1.4 The values stated in SI units are to be regarded as the
are temporarily blocked to prevent water leakage into the
standard. The values given in parentheses are for information
drainage system.
only.
4.3 Water is ponded in the subdivided area and maintained
1.5 This standard does not purport to address all of the
for a minimum period of 24 h. The space below the test
safety concerns, if any, associated with its use. It is the
location is monitored for leakage during the test period.
responsibility of the user of this standard to establish appro-
priate safety and health practices and determine the applica-
5. Significance and Use
bility of regulatory limitations prior to use.
5.1 This guide describes the techniques used to test for
2. Referenced Documents
watertightness of waterproofing installations on horizontal
2
services having a slope not greater than 20 mm/m (2 % slope)
2.1 ASTM Standards:
1
( ⁄4 in./ft). See also ACI 515.
D1079 Terminology Relating to Roofing and Waterproofing
5.2 The structural capacity of the substrate to which the
waterproofing system is to be installed should be reviewed by
a licensed structural engineer to verify that the loads associated
with the use of procedures described in this guide do not
exceed code and design restrictions. Lateral loads will be
1
This guide is under the jurisdiction of ASTM Committee D08 on Roofing and
imposed on curbs or walls used for containment of the water
Waterproofing and is the direct responsibility of Subcommittee D08.22 on Water-
proofing and Dampproofing Systems. during the test procedures and their effect should be accounted
Current edition approved July 1, 2005. Published July 2005. Originally approved
for. The effects of equipment, planters, or other movable
in 1996. Last previous edition approved in 1998 as D5957 – 98. DOI: 10.1520/
objects present within the test area should be considered.
D5957-98R05.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
3
Standards volume information, refer to the standard’s Document Summary page on Available fromAmerican Concrete Institute (ACI), P.O. Box 9094, Farmington
the ASTM website. Hills, MI 48333.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
D5957−98 (2005)
NOTE1—Potablewaterweighsapproximately1000kg/cubicm(62.3lb
6.3 Vertical-Sided Shallow Pan .
2 2
per cubic ft) at 22°C (71.6°F) or 1 g/cm /cm depth (5.19 lbs/ft per in.
6.4 Conta
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.