ASTM C1290-00
(Specification)Standard Specification for Flexible Fibrous Glass Blanket Insulation Used to Externally Insulate HVAC Ducts
Standard Specification for Flexible Fibrous Glass Blanket Insulation Used to Externally Insulate HVAC Ducts
SCOPE
1.1 This specification covers the composition, size, dimensions, and physical properties of flexible fiber glass blanket, ductwrap, used to externally insulate HVAC ducts used for the distribution of condition air with a temperature up to 250oF (121oC).
1.2 The values stated in inch-pound units are to be regarded as the standard. The values given in parentheses are for information only and may be approximate.
1.3 When the installation and use of thermal insulation materials, accessories, and systems may pose safety and health problems, the manufacturer shall provide the user appropriate current information regarding any known problems associated with the recommended use of the company's products, and shall also recommend protective measures to be employed in their safe utilization. The user shall establish appropriate safety and health practices and determine the applicability of regulatory requirements prior to use.
1.4 The following safety hazards caveat pertains only to the test methods, Section 13, in this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
General Information
Relations
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or discontinued.
Contact ASTM International (www.astm.org) for the latest information.
Designation: C 1290 – 00
Standard Specification for
Flexible Fibrous Glass Blanket Insulation Used to Externally
1
Insulate HVAC Ducts
This standard is issued under the fixed designation C 1290; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
1. Scope C 411 Test Method for Hot-Surface Performance of High-
2
Temperature Thermal Insulation
1.1 This specification covers the composition, size, dimen-
C 518 Test Method for Steady-State Heat Flux Measure-
sions, and physical properties of flexible fiber glass blanket,
ments and Thermal Transmission Properties by Means of
ductwrap, used to externally insulate HVAC ducts used for the
2
the Heat Flow Meter Apparatus
distribution of condition air with a temperature up to 250°F
C 665 Specification for Mineral-Fiber Blanket Thermal In-
(121°C).
sulation for Light Frame Construction and Manufactured
1.2 The values stated in inch-pound units are to be regarded
2
Housing
as the standard. The values given in parentheses are for
C 1104/1104M Test Method for Determining the Water
information only and may be approximate.
2
Vapor Sorption of Unfaced Fiber Insulation
1.3 When the installation and use of thermal insulation
C 1136 Specification for Flexible, Low Permeance Vapors
materials, accessories, and systems may pose safety and health
2
Retarders for Thermal Insulation
problems, the manufacturer shall provide the user appropriate
C 1045 Practice for Calculating Thermal Transmission
current information regarding any known problems associated
2
Properties from Steady-State Heat Flux Measurements
with the recommended use of the company’s products, and
E 84 Test Method for Surface Burning Characteristics of
shall also recommend protective measures to be employed in
3
Buildings Materials
their safe utilization. The user shall establish appropriate safety
E 96 Test Methods for Water Vapor Transmission of Mate-
and health practices and determine the applicability of regula-
2
rials
tory requirements prior to use.
1.4 The following safety hazards caveat pertains only to the
3. Terminology
test methods, Section 13, in this specification. This standard
3.1 Definitions—For definitions of terms defined in this
does not purport to address all of the safety concerns, if any,
specification, see Terminology C 168.
associated with its use. It is the responsibility of the user of this
standard to establish appropriate safety and health practices
4. Classification
and determine the applicability of regulatory limitations prior
4.1 Fibrous glass flexible blanket HVAC duct external
to use.
insulation consists of the following three types:
2. Referenced Documents 4.1.1 Type I—Blankets without membrane facing.
4.1.2 Type II—Blankets faced with a vapor-retarder mem-
2.1 ASTM Standards:
brane having a water vapor permeance no higher than 1.30
C 167 Test Methods for Thickness and Density of Blanket
2 Perm.
or Batt Thermal Insulations
4.1.3 Type III—Flexible blankets faced with a vapor-
C 168 Terminology Relating to Thermal Insulating Materi-
2 retarder membrane with a water vapor permeance no higher
als
than 0.02 Perm that meet all physical property requirements of
C 177 Test Method for Steady-State Heat Flux Measure-
Specification C 1136.
ments and Thermal Transmission Properties by Means of
2
the Guarded-Hot-Plate Apparatus
5. Ordering Information
C 390 Criteria for Sampling and Acceptance of Preformed
5.1 Specific installation, insulation type, thermal resistance,
2
Thermal Insulation Lots
thickness, length, and width suited for the intended use shall be
specified by the purchaser.
1
This specification is under the jurisdiction of ASTM Committee C-16 on
Thermal Insulation and is under the direct responsibility of Subcommittee C16.23
on Blanket and Loose Fill Insulation.
Current edition approved Nov. 10, 2000. Published February 2001.
Originally published as C 1290–95. Last previous edition C 1290–95.
2 3
Annual Book of ASTM Standards, Vol 04.06. Annual Book of ASTM Standards, Vol 04.07.
Copyright © ASTM, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959, United States.
1
---------------------- Page: 1 ----------------------
C 1290
6. Materials and Manufacture 8. Dimensional Tolerances
6.1 Basic Material— The basic material shall be fibers 8.1 After conditioning for a minimum of 24 h at 70 6 3°F
made from glass processed from the molten state into fibrous (21 6 1.6°C) and 50 6 5 % relative humidity, the insulation
form. shall conform to the dimensional tolerances listed in Table 1.
6.2 Manufacture— Insulation shall consist of bonded fibers All measurements shall be made in accordance with 12.1.
...