ASTM E779-10
(Test Method)Standard Test Method for Determining Air Leakage Rate by Fan Pressurization
Standard Test Method for Determining Air Leakage Rate by Fan Pressurization
SIGNIFICANCE AND USE
Air leakage accounts for a significant portion of the thermal space conditioning load. In addition, it affects occupant comfort and indoor air quality.
In most commercial or industrial buildings, outdoor air is often introduced by design; however, air leakage is a significant addition to the designed outdoor airflow. In most residential buildings, indoor-outdoor air exchange is attributable primarily to air leakage through cracks and construction joints and is induced by pressure differences due to temperature differences, wind, operation of auxiliary fans (for example, kitchen and bathroom exhausts), and the operation of combustion equipment in the building.
The fan-pressurization method is simpler than tracer gas measurements and is intended to characterize the air tightness of the building envelope. It is used to compare the relative air tightness of several similar buildings to identify the leakage sources and rates of leakage from different components of the same building envelope, and to determine the air leakage reduction for individual retrofit measures applied incrementally to an existing building, and to determine ventilation rates when combined with weather and leak location information.
SCOPE
1.1 This test method measures air-leakage rates through a building envelope under controlled pressurization and de-pressurization.
1.2 This test method is applicable to small temperature differentials and low-wind pressure differential, therefore strong winds and large indoor-outdoor temperature differentials shall be avoided.
1.3 This test method is intended to quantify the air tightness of a building envelope. This test method does not measure air change rate or air leakage rate under normal weather conditions and building operation.
Note 1—See Test Method E741 to directly measure air-change rates using the tracer gas dilution method
1.4 This test method is intended to be used for measuring the air tightness of building envelopes of single-zone buildings. For the purpose of this test method, many multi-zone buildings can be treated as single-zone buildings by opening interior doors or by inducing equal pressures in adjacent zones.
1.5 Only metric SI units of measurement are used in this standard. If a value for measurement is followed by a value in other units in parentheses, the second value may be approximate. The first stated value is the requirement.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific hazard statements see Section 7.
General Information
Relations
Buy Standard
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: E779 − 10
Standard Test Method for
1
Determining Air Leakage Rate by Fan Pressurization
This standard is issued under the fixed designation E779; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope E741Test Method for Determining Air Change in a Single
Zone by Means of a Tracer Gas Dilution
1.1 This test method measures air-leakage rates through a
E1258Test Method for Airflow Calibration of Fan Pressur-
building envelope under controlled pressurization and de-
ization Devices
pressurization.
3. Terminology
1.2 This test method is applicable to small temperature
differentials and low-wind pressure differential, therefore
3.1 Fordefinitionsoftermsusedinthistestmethod,referto
strong winds and large indoor-outdoor temperature differen-
Terminology E631.
tials shall be avoided.
3.2 Definitions of Terms Specific to This Standard:
1.3 Thistestmethodisintendedtoquantifytheairtightness
3.2.1 air-change rate, n—air-leakage rate in volume units/h
of a building envelope. This test method does not measure air
divided by the building space volume with identical volume
changerateorairleakagerateundernormalweatherconditions
units, normally expressed as air changes/h, ACH.
and building operation.
3.2.2 air-leakage, n—the movement/flow of air through the
NOTE 1—See Test Method E741 to directly measure air-change rates building envelope, which is driven by either or both positive
using the tracer gas dilution method.
(infiltration) and negative (exfiltration) pressure differences
across the envelope.
1.4 This test method is intended to be used for measuring
theairtightnessofbuildingenvelopesofsingle-zonebuildings.
3.2.3 air-leakage graph, n—the graph that shows the rela-
Forthepurposeofthistestmethod,manymulti-zonebuildings
tionship of measured airflow rates to the corresponding mea-
can be treated as single-zone buildings by opening interior
sured pressure differences, plotted on a log-log scale.
doors or by inducing equal pressures in adjacent zones.
3.2.4 air-leakage rate, n—the volume of air movement/unit
1.5 Only metric SI units of measurement are used in this
time across the building envelope including airflow through
standard. If a value for measurement is followed by a value in
joints, cracks, and porous surfaces, or a combination thereof
other units in parentheses, the second value may be approxi-
driven by mechanical pressurization and de-pressurization,
mate. The first stated value is the requirement.
naturalwindpressures,orairtemperaturedifferentialsbetween
the building interior and the outdoors, or a combination
1.6 This standard does not purport to address all of the
thereof.
safety concerns, if any, associated with its use. It is the
responsibility of the user of this standard to establish appro-
3.2.5 building envelope, n—the boundary or barrier separat-
priate safety and health practices and determine the applica-
ing different environmental conditions within a building and
bility of regulatory limitations prior to use. For specific hazard
from the outside environment.
statements see Section 7.
3.2.6 effective leakage area, n—the area of a hole, with a
discharge coefficient of 1.0, which, witha4Pa pressure
2. Referenced Documents
difference, leaks the same as the building, also known as the
2
2.1 ASTM Standards:
sum of the unintentional openings in the structure.
E631Terminology of Building Constructions
3.2.7 height, building, n—the vertical distance from grade
plane to the average height of the highest ceiling surface.
1
This test method is under the jurisdiction of ASTM Committee E06 on
Performance of Buildings and is the direct responsibility of Subcommittee E06.41 3.2.8 interior volume, n—deliberately conditioned space
on Air Leakage and Ventilation Performance.
within a building, generally not including attics and attached
Current edition approved Jan. 15, 2010. Published April 2010. Originally
structures, for example, garages, unless such spaces are con-
approved in 1981. Last previous edition approved in 2003 as E779–03. DOI:
nected to the heating and air conditioning system, such as a
10.1520/E0779-10.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
crawl space plenum.
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
3.2.9 single zone, n—a space in which the pressure differ-
Standards volume information, refer to the standard’s Document Summary page on
the ASTM website. ences between any two places, differ by no more than 5% of
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United S
...
This document is not anASTM standard and is intended only to provide the user of anASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation:E779–03 Designation: E779 – 10
Standard Test Method for
1
Determining Air Leakage Rate by Fan Pressurization
This standard is issued under the fixed designation E779; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1This test method covers a standardized technique for measuring air-leakage rates through a building envelope under
controlled pressurization and de-pressurization.
1.2Thistestmethodisapplicabletosmalltemperaturedifferentialsandlow-windpressureconditions.Fortestsconductedinthe
field, it must be recognized that field conditions may be less than ideal. Nevertheless, strong winds and large indoor-outdoor
temperature differentials should be avoided.
1.3This test method is intended to produce a measure of air tightness of a building envelope.This test method does not measure
airleakageratesundernormalconditionsofweatherandbuildingoperation.Tomeasureair-changeratedirectly,usethetracergas
dilution method (see Test Method E1258).
1.4This test method is intended for the measurement of the airtightness of building envelopes of single-zone buildings. For the
purpose of this test method, many multi-zone buildings can be treated as single-zone buildings by opening interior doors or by
inducing equal pressures in adjacent zones.
1.5
1.1 This test method measures air-leakage rates through a building envelope under controlled pressurization and de-
pressurization.
1.2 This test method is applicable to small temperature differentials and low-wind pressure differential, therefore strong winds
and large indoor-outdoor temperature differentials shall be avoided.
1.3 This test method is intended to quantify the air tightness of a building envelope. This test method does not measure air
change rate or air leakage rate under normal weather conditions and building operation.
NOTE 1—See Test Method E741 to directly measure air-change rates using the tracer gas dilution method
1.4 This test method is intended to be used for measuring the air tightness of building envelopes of single-zone buildings. For
the purpose of this test method, many multi-zone buildings can be treated as single-zone buildings by opening interior doors or
by inducing equal pressures in adjacent zones.
1.5 Only metric SI units of measurement are used in this standard. If a value for measurement is followed by a value in other
units in parentheses, the second value may be approximate. The first stated value is the requirement.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use. For specific hazard statements see Section 7.
2. Referenced Documents
2
2.1 ASTM Standards: ASTM Standards:
E631 Terminology of Building Constructions
E741 Test Method for Determining Air Change in a Single Zone by Means of a Tracer Gas Dilution
E1258 Test Method for Airflow Calibration of Fan Pressurization Devices
3. Terminology
3.1
1
ThistestmethodisunderthejurisdictionofASTMCommitteeE06onPerformanceofBuildingsandisthedirectresponsibilityofSubcommitteeE06.41onAirLeakage
and Ventilation.
Current edition approved Oct. 1, 2003. Published November 2003. Originally approved in 1981. Last previous edition approved in 1999 as E779–99. DOI:
10.1520/E0779-03.on Air Leakage and Ventilation Performance.
Current edition approved Jan. 15, 2010. Published September 2010. Originally approved in 1981. Last previous edition approved in 2003 as E779–03. DOI:
10.1520/E0779-10.
2
ForreferencedASTMstandards,visittheASTMwebsite,www.astm.org,orcontactASTMCustomerServiceatservice@astm.org.ForAnnualBookofASTMStandards
volume information, refer to the standard’s Document Summary page on the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1
---------------------- Page: 1 ----------------------
E779 – 10
3.1 For definitions of terms used in this test method, refer to Terminology E631.
3.2 Definitions of Terms Specific to This Standard:
3.1.1.
3.2.1 air-change rate, n—air-leakage rate in volume units/h divided by the building space volume with identical volume units,
normally expressed as air cha
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.