Standard Specification for Aluminum 1350 Drawing Stock for Electrical Purposes

ABSTRACT
This specification covers aluminium 1350 drawing stock for electrical purposes. The stock shall conform to the chemical composition requirements. The stock shall be uniform in quality and temper and shall be suitable for drawing into wire. The tensile strength tests and requirements for the respective tempers of stock are presented in details. The stock shall be furnished in continuous-length coils without joints, unless otherwise agreed upon between the manufacturer and purchaser. The electrical resistivity tests shall be made on full-section samples of the stock.
SCOPE
1.1 This specification covers aluminum 1350 drawing stock 0.375 in. (9.52 mm) to 1.000 in. (25.40 mm) in diameter, in the tempers shown in , for drawing into wire for electrical conductors (Explanatory Note 1 and Note 2).
1.2 The SI values of density and resistivity are to be regarded as the standard. For all other properties the inch-pound values are to be regarded as standard and the SI units may be approximate. Note 1
Prior to 1975, aluminum 1350 was designated as EC aluminum.
Note 2
The aluminum and temper designations conform to ANSI H35.1. Aluminum 1350 corresponds to unified numbering system A91350 in accordance with Practice E 527.

General Information

Status
Historical
Publication Date
30-Sep-2007
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM B233-97(2007) - Standard Specification for Aluminum 1350 Drawing Stock for Electrical Purposes
English language
4 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:B233 −97(Reapproved 2007)
Standard Specification for
1
Aluminum 1350 Drawing Stock for Electrical Purposes
This standard is issued under the fixed designation B233; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
3
1. Scope Point-to-Plane Technique (Withdrawn 2002)
E527 Practice for Numbering Metals and Alloys in the
1.1 This specification covers aluminum 1350 drawing stock
Unified Numbering System (UNS)
0.375 in. (9.52 mm) to 1.000 in. (25.40 mm) in diameter, in the
4
2.3 American National Standard:
tempers shown in Table 1, for drawing into wire for electrical
ANSI H35.1 Alloy and Temper Designation Systems for
conductors (Explanatory Note 1 and Note 2).
Aluminum
1.2 The SI values of density and resistivity are to be
5
2.4 National Bureau of Standards:
regarded as the standard. For all other properties the inch-
Handbook 100Copper Wire Tables
pound values are to be regarded as standard and the SI units
may be approximate.
3. Ordering Information
NOTE 1—Prior to 1975, aluminum 1350 was designated as EC
3.1 Orders for material under this specification shall include
aluminum.
the following information:
NOTE 2—The aluminum and temper designations conform to ANSI
3.1.1 Quantity,
H35.1.Aluminum 1350 corresponds to unified numbering systemA91350
3.1.2 Diameter (see 11.1),
in accordance with Practice E527.
3.1.3 Temper (see Table 1 and Explanatory Note 1 and Note
2. Referenced Documents
2),
3.1.4 Whether joints are permitted (see 8.1),
2.1 The following documents of the issue in effect on date
3.1.5 Whether tests of joints are required and number of
of material purchase form a part of this specification to the
specimens (see 8.2),
extent referenced herein:
3.1.6 Coil size and weight (see 14.2),
2
2.2 ASTM Standards:
3.1.7 Whether wrapping of coils is required (see 14.3),
B193 Test Method for Resistivity of Electrical Conductor
3.1.8 Special marking on tags, if required (see 14.4), and
Materials
3.1.9 Whether inspection or witness of inspection and tests
B354 Terminology Relating to Uninsulated Metallic Electri-
by purchaser’s representative is required prior to shipment (see
cal Conductors
Section 13).
B557 Test Methods for Tension Testing Wrought and Cast
Aluminum- and Magnesium-Alloy Products
4. Manufacture
B830 Specification for Uniform Test Methods and Fre-
4.1 Unless otherwise agreed upon at the time of placing the
quency
order, the manufacturer shall have the option of producing the
E34 Test Methods for Chemical Analysis of Aluminum and
stock from either individually cast ingots or continuously cast
Aluminum-Base Alloys
bars. Only one method of production shall be used on any
E55 Practice for Sampling Wrought Nonferrous Metals and
given order.
Alloys for Determination of Chemical Composition
E227 Test Method for Optical Emission Spectrometric 4.2 Unless otherwise specified, the manufacturer shall have
Analysis of Aluminum and Aluminum Alloys by the the option of supplying stock in the H2X temper when H1X is
specified,andofsupplyingstockintheH1XtemperwhenH2X
is specified. Only one temper shall be supplied in any given
1
This specification is under the jurisdiction of ASTM Committee B01 on
order (see Explanatory Note 3 and ANSI H35.1).
Electrical Conductors and is the direct responsibility of Subcommittee B01.07 on
Conductors of Light Metals.
Current edition approved Oct. 1, 2007. Published October 2007. Originally
3
approved in 1948. Last previous edition approved in 2003 as B233 – 97 (2003). The last approved version of this historical standard is referenced on
DOI: 10.1520/B0233-97R07. www.astm.org.
2 4
For referenced ASTM standards, visit the ASTM website, www.astm.org, or Available from American National Standard Institute, 11 W. 42nd St., 13th
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Floor, New York, NY 10036.
5
Standards volume information, refer to the standard’s Document Summary page on Available from National Technical Information Service (NTIS), 5285 Port
the ASTM website. Royal Rd., Springfield, VA 22161, http://www.ntis.gov.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
B233−97 (2007)
A
TABLE 1 Tensile Property Limits TABLE 5 Diameter Tolerances
Tensile Strength
Tolerance, in. (mm), Plus or Minus
Temper
A
Specified Diameter, in. Deviation of Mean Deviation at Any
ksi MPa
Diameter from
(mm) Point from
1350-O 8.5–14.0 59–97
Specified Diameter
Specified Diameter
1350-H12 and -H22 12.0–17.0 83–117
0.375–0.500 (9.52–12.70) 0.020 (0.51
...

Questions, Comments and Discussion