Standard Specification for Vermiculite Loose Fill Thermal Insulation

ABSTRACT
This specification covers the chemical and physical property requirements and acceptability testing procedures of expanded or exfoliated vermiculite loose fill thermal insulation. This also includes vermiculite that has been surface-treated to produce water repellency for use in installations where liquid moisture may be a factor. Vermiculite insulation is specified by two types according to treatments and five classes according to the range of particle size distribution. The insulation should conform to the specified values of bulk density, grading, water properties, thermal resistance, moisture absorption, combustibility, and surface-burning characteristics. Tests to determine the physical properties should also be in accordance with the specified test procedures.
SCOPE
1.1 This specification covers the composition and physical properties of expanded or exfoliated vermiculite loose fill insulation. The specification also includes the testing procedures by which the acceptability of the material may be determined. These testing procedures deal primarily with material performance in the temperature range associated with the thermal envelope of buildings; however, the commercially usable temperature range for this insulation is from -119 to 850°F (-84 to 454°C). For specialized applications, refer to manufacturer's instructions.
1.2 The specification also covers the composition and properties of vermiculite that has been surface-treated to produce water repellency for installations where liquid moisture may be a factor.
1.3 When the installation or use of thermal insulation materials, accessories, and systems may pose safety or health problems, the manufacturer shall provide the user with appropriate current information regarding any known problems associated with the recommended use of the company's products, and shall also recommend protective measures to be employed in their safe utilization.
1.4 The following safety hazards caveat pertains only to the test methods portion, Section 9, of this specification: This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific hazard statements, see Section 12.

General Information

Status
Historical
Publication Date
09-Oct-2002
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM C516-02 - Standard Specification for Vermiculite Loose Fill Thermal Insulation
English language
4 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: C 516 – 02
Standard Specification for
1
Vermiculite Loose Fill Thermal Insulation
This standard is issued under the fixed designation C516; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the Department of Defense.
3
1. Scope C168 Terminology Relating to Thermal Insulation
C177 Test Method for Steady-State Heat Flux Measure-
1.1 This specification covers the composition and physical
ments and Thermal Transmission Properties by Means of
properties of expanded or exfoliated vermiculite loose fill
3
the Guarded-Hot-Plate Apparatus
insulation. The specification also includes the testing proce-
C390 Practice for Sampling and Acceptance of Preformed
dures by which the acceptability of the material may be
3
Thermal Insulation Lots
determined. These testing procedures deal primarily with
C518 Test Method for Steady-State Thermal Transmission
material performance in the temperature range associated with
3
Properties by Means of the Heat Flow Meter Apparatus
the thermal envelope of buildings; however, the commercially
C520 Test Methods for Density of Granular Loose Fill
usable temperature range for this insulation is from−119 to
3
Insulations
850°F (−84 to 454°C). For specialized applications, refer to
E84 Test Method for Surface Burning Characteristics of
manufacturer’s instructions.
4
Building Materials
1.2 The specification also covers the composition and prop-
E136 Test Method for Behavior of Materials in a Vertical
erties of vermiculite that has been surface-treated to produce
4
Tube Furnace at 750°C
waterrepellencyforinstallationswhereliquidmoisturemaybe
a factor.
3. Terminology
1.3 When the installation or use of thermal insulation
3.1 The terms used in this specification are defined in
materials, accessories, and systems may pose safety or health
Terminology C168.
problems, the manufacturer shall provide the user with appro-
priate current information regarding any known problems
4. Classification
associated with the recommended use of the company’s
4.1 Vermiculite insulation shall be specified by two type
products, and shall also recommend protective measures to be
designations and five classes, as follows:
employed in their safe utilization.
4.1.1 Vermiculite Loose Fill Insulation—Type I—The prod-
1.4 The following safety hazards caveat pertains only to the
uct that results from the expanding or exfoliating of natural
test methods portion, Section 9, of this specification: This
vermiculite ore by grading and heating to meet the require-
standarddoesnotpurporttoaddressallofthesafetyconcerns,
ments of this specification.
ifany,associatedwithitsuse.Itistheresponsibilityoftheuser
4.1.2 VermiculiteLooseFillInsulation—TypeII—Expanded
of this standard to establish appropriate safety and health
vermiculite that has been surface-treated to produce water
practices and determine the applicability of regulatory limita-
repellency and limit absorption of moisture from both liquid
tions prior to use. For specific hazard statements, see Section
and vapor phase.
12.
4.1.3 Vermiculite loose fill insulation has five grade desig-
2. Referenced Documents nations established by range of particle size distribution as
shown in Table 1.
2.1 ASTM Standards:
C136 Test Method for Sieve Analysis of Fine and Coarse
5. Ordering Information
2
Aggregates
5.1 All purchase orders should designate both type and
gradeofinsulationdesired.Iftypedesignationisomitted,Type
1
This specification is under the jurisdiction of ASTM Committee C16 on
I will be furnished. The type and grade classifications in this
Thermal Insulation and is the direct responsibility of Subcommittee C16.23 on
Blanket and Loose Fill Insulation.
Current edition approved October 10, 2002. Published November 2002. Origi-
e1 3
nally published as C516–63T. Last previous edition C516–80(1996) . Annual Book of ASTM Standards, Vol 04.06.
2 4
Annual Book of ASTM Standards, Vol 04.02. Annual Book of ASTM Standards, Vol 04.07.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
C516–02
TABLE 1 Density Specifications 2
Thermal resistance, °F·h·ft /Btu See Table 2
2
3 3
(K·m /W)
Bulk Density, lb/ft (kg/m )
Grade Designation Moisture absorption, max, % by weight/ 3.5 3.5
min max
14 days
Combustibility No flaming, glowing,
0—Premium 3.0 (48) 5.0 (80)
or smoking
1—Large 3.7 (59) 5.5 (88)
Surface-burning characteristics (Test Method
2—Medium 4.0 (64) 6.0 (96)
E 84):
3—Fine 4.5 (72) 7.0 (112)
Flame spread, max 0 0
4
...