Standard Test Method for Heat and Visible Smoke Release Rates for Materials and Products Using an Oxygen Consumption Calorimeter

SIGNIFICANCE AND USE
This test method is used primarily to determine the heat evolved in, or contributed to, a fire involving products of the test material. Also included is a determination of the effective heat of combustion, mass loss rate, the time to sustained flaming, and smoke production. These properties are determined on small size specimens that are representative of those in the intended end use.
This test method is applicable to various categories of products and is not limited to representing a single fire scenario. Additional guidance for testing is given in X1.2.3 and X1.11.
SCOPE
This test method is not applicable to end-use products that do not have planar, or nearly planar, external surfaces.

General Information

Status
Historical
Publication Date
14-Oct-2011
Technical Committee
Current Stage
Ref Project

Relations

Effective Date
15-Oct-2011

Buy Standard

Standard
ASTM E1354-11b - Standard Test Method for Heat and Visible Smoke Release Rates for Materials and Products Using an Oxygen Consumption Calorimeter
English language
20 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
REDLINE ASTM E1354-11b - Standard Test Method for Heat and Visible Smoke Release Rates for Materials and Products Using an Oxygen Consumption Calorimeter
English language
20 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: E1354 − 11b AnAmerican National Standard
Standard Test Method for
Heat and Visible Smoke Release Rates for Materials and
1
Products Using an Oxygen Consumption Calorimeter
This standard is issued under the fixed designation E1354; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope 1.8 This standard is used to measure and describe the
response of materials, products, or assemblies to heat and
1.1 This fire-test-response standard provides for measuring
flame under controlled conditions, but does not by itself
the response of materials exposed to controlled levels of
incorporate all factors required for fire hazard or fire risk
radiant heating with or without an external ignitor.
assessment of the materials, products, or assemblies under
1.2 This test method is used to determine the ignitability,
actual fire conditions.
heatreleaserates,masslossrates,effectiveheatofcombustion,
1.9 This standard does not purport to address all of the
and visible smoke development of materials and products.
safety concerns, if any, associated with its use. It is the
1.3 The rate of heat release is determined by measurement
responsibility of the user of this standard to establish appro-
of the oxygen consumption as determined by the oxygen
priate safety and health practices and determine the applica-
concentration and the flow rate in the exhaust product stream.
bility of regulatory limitations prior to use. For specific hazard
The effective heat of combustion is determined from a con-
statements, see Section 7.
comitant measurement of specimen mass loss rate, in combi-
nation with the heat release rate. Smoke development is
2. Referenced Documents
measured by obscuration of light by the combustion product
2
2.1 ASTM Standards:
stream.
D5865Test Method for Gross Calorific Value of Coal and
1.4 Specimens shall be exposed to initial test heat fluxes in
Coke
2
the range of 0 to 100 kW/m . External ignition, when used,
E176Terminology of Fire Standards
shall be by electric spark. The value of the initial test heat flux
E177Practice for Use of the Terms Precision and Bias in
and the use of external ignition are to be as specified in the
ASTM Test Methods
relevant material or performance standard (see X1.2). The
E603Guide for Room Fire Experiments
normal specimen testing orientation is horizontal, independent
E662Test Method for Specific Optical Density of Smoke
of whether the end-use application involves a horizontal or a
Generated by Solid Materials
vertical orientation. The apparatus also contains provisions for
E691Practice for Conducting an Interlaboratory Study to
vertical orientation testing; this is used for exploratory or
Determine the Precision of a Test Method
diagnostic studies only.
E906Test Method for Heat and Visible Smoke Release
1.5 Ignitability is determined as a measurement of time
Rates for Materials and Products Using a Thermopile
from initial exposure to time of sustained flaming.
Method
3
1.6 Thistestmethodhasbeendevelopedforuseformaterial 2.2 ISO Standards:
and product evaluations, mathematical modeling, design
ISO 5657-1986(E)Fire Tests—reaction to fire—ignitability
purposes, or development and research. Examples of material of building materials
specimens include portions of an end-use product or the
ISO 5725-2 (1994)Accuracy (trueness and precision) of
various components used in the end-use product. measurementmethodsandresults—Part2:Basicmethod
for the determination of repeatability and reproducibility
1.7 The values stated in SI units are to be regarded as
of a standard measurement method
standard. No other units of measurement are included in this
standard.
1 2
This test method is under the jurisdiction of ASTM Committee E05 on Fire For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Standardsand is the direct responsibility of Subcommittee E05.21 on Smoke and contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Combustion Products. Standards volume information, refer to the standard’s Document Summary page on
Current edition approved Oct. 15, 2011. Published November 2011. Originally the ASTM website.
3
approved in 1990. Last previous edition approved in 2011 as E1354-11a. DOI: Available fromAmerican National Standards Institute (ANSI), 25 W. 43rd St.,
10.1520/E1354-11B. 4th Floor, New York, NY 10036, http://www.ansi.org.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
E1354 − 11b
3. Terminology 3.2.8 orientation, n—the plane i
...

This document is not anASTM standard and is intended only to provide the user of anASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
An American National Standard
Designation:E1354–11a Designation:E1354–11b
Standard Test Method for
Heat and Visible Smoke Release Rates for Materials and
1
Products Using an Oxygen Consumption Calorimeter
This standard is issued under the fixed designation E1354; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This fire-test-response standard provides for measuring the response of materials exposed to controlled levels of radiant
heating with or without an external ignitor.
1.2 This test method is used to determine the ignitability, heat release rates, mass loss rates, effective heat of combustion, and
visible smoke development of materials and products.
1.3 The rate of heat release is determined by measurement of the oxygen consumption as determined by the oxygen
concentration and the flow rate in the exhaust product stream.The effective heat of combustion is determined from a concomitant
measurement of specimen mass loss rate, in combination with the heat release rate. Smoke development is measured by
obscuration of light by the combustion product stream.
2
1.4 Specimens shall be exposed to initial test heat fluxes in the range of 0 to 100 kW/m . External ignition, when used, shall
be by electric spark. The value of the initial test heat flux and the use of external ignition are to be as specified in the relevant
material or performance standard (see X1.2). The normal specimen testing orientation is horizontal, independent of whether the
end-use application involves a horizontal or a vertical orientation. The apparatus also contains provisions for vertical orientation
testing; this is used for exploratory or diagnostic studies only.
1.5 Ignitability is determined as a measurement of time from initial exposure to time of sustained flaming.
1.6 Thistestmethodhasbeendevelopedforuseformaterialandproductevaluations,mathematicalmodeling,designpurposes,
or development and research. Examples of material specimens include portions of an end-use product or the various components
used in the end-use product.
1.7 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard.
1.8 This standard is used to measure and describe the response of materials, products, or assemblies to heat and flame under
controlled conditions, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the materials,
products, or assemblies under actual fire conditions.
1.9 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use. For specific hazard statements, see Section 7.
2. Referenced Documents
2
2.1 ASTM Standards:
D5865 Test Method for Gross Calorific Value of Coal and Coke
E176 Terminology of Fire Standards
E177 Practice for Use of the Terms Precision and Bias in ASTM Test Methods
E603 Guide for Room Fire Experiments
E662 Test Method for Specific Optical Density of Smoke Generated by Solid Materials
E691 Practice for Conducting an Interlaboratory Study to Determine the Precision of a Test Method
E906 Test Method for Heat and Visible Smoke Release Rates for Materials and Products Using a Thermopile Method
3
2.2 ISO Standards:
ISO 5657-1986(E) Fire Tests—reaction to fire—ignitability of building materials
1
ThistestmethodisunderthejurisdictionofASTMCommitteeE05onFireStandardsandisthedirectresponsibilityofSubcommitteeE05.21onSmokeandCombustion
Products.
Current edition approved July 1,Oct. 15, 2011. Published AugustNovember 2011. Originally approved in 1990. Last previous edition approved in 2011 as E1354-11a.
DOI: 10.1520/E1354-11AB.
2
ForreferencedASTMstandards,visittheASTMwebsite,www.astm.org,orcontactASTMCustomerServiceatservice@astm.org.ForAnnualBookofASTMStandards
volume information, refer to the standard’s Document Summary page on the ASTM website.
3
Available from American National Standards Institute (ANSI), 25 W. 43rd St., 4th Floor, New York, NY 10036, http://www.ansi.org.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 -------
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.