Standard Specification for ACSR Twisted Pair Conductor (ACSR/TP)

ABSTRACT
This specification covers ACSR twisted pair conductor for use as overhead electric conductors. The conductors shall conform to the required values of equivalent size AWG, outer dimensions, nominal mass, rated strength, resistance and shall conform to the required component composition of aluminum and steel. . Tests for the electrical and mechanical properties shall be made on the component conductors.
SCOPE
1.1 This specification covers ACSR Twisted Pair Conductor (ACSR/TP) for use as overhead electric conductors (see Note 0Note 0).Note 0
The conductor is fabricated from two component ACSR conductors of the same size twisted helically around each other. This conductor is identified by the code name of the component ACSR conductor followed by /TP or the size and type of the component ACSR conductor followed by /TP.Note 0
There are registered trademark symbols that are also used to identify the twisted pair notation. Consult cable manufacturers for additional details.
1.2 The values stated in inch-pound or SI units are to be regarded separately as standard. Each system shall be used independently of the other. Combining values from the two systems may result in nonconformance with the specification. For conductor sizes designated by AWG or kcmil, the requirements in SI units have been numerically converted from corresponding values stated or derived in inch-pound units. For conductor sizes designated by SI units only, the requirements are stated or derived in SI units.
1.2.1 For density, resistivity, and temperature, the values stated in SI units are to be regarded as standard.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
30-Sep-2005
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM B911/B911M-05 - Standard Specification for ACSR Twisted Pair Conductor (ACSR/TP)
English language
4 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: B911/B911M – 05
Standard Specification for
1
ACSR Twisted Pair Conductor (ACSR/TP)
This standard is issued under the fixed designation B911/B911M; the number immediately following the designation indicates the year
of original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval.
A superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope B232/B232M Specification for Concentric-Lay-Stranded
Aluminum Conductors, Coated-Steel Reinforced (ACSR)
1.1 This specification coversACSR Twisted Pair Conductor
(ACSR/TP) for use as overhead electric conductors (see Notes
3. Terminology
1 and 2).
3.1 Definitions of Terms Specific to This Standard:
NOTE 1—The conductor is fabricated from two component ACSR
3.1.1 component conductors—thetwoconductorstwistedto
conductors of the same size twisted helically around each other. This
fabricate the finished ACSR/TP.
conductor is identified by the code name of the component ACSR
conductor followed by /TP or the size and type of the component ACSR
4. Ordering Information
conductor followed by /TP.
4.1 Orders for material under this specification shall include
NOTE 2—There are registered trademark symbols that are also used to
identify the twisted pair notation. Consult cable manufacturers for the following information:
additional details.
4.1.1 Quantity of each size,
4.1.1.1 Conductor Size—kcmil area of the fabricated
1.2 The values stated in inch-pound or SI units are to be
ACSR/TP (2 3 kcmil area of one of the component conduc-
regarded separately as standard. Each system shall be used
tors),
independently of the other. Combining values from the two
4.1.2 Conductor type and the number of wires of the
systems may result in nonconformance with the specification.
component conductors,
For conductor sizes designated byAWG or kcmil, the require-
4.1.3 The type of steel core wire and type of coating,
ments in SI units have been numerically converted from
4.1.4 Place of inspection,
correspondingvaluesstatedorderivedininch-poundunits.For
4.1.5 Package size and type,
conductor sizes designated by SI units only, the requirements
4.1.6 Special package markings, if required, and
are stated or derived in SI units.
4.1.7 Heavy wood lagging, if required.
1.2.1 For density, resistivity, and temperature, the values
stated in SI units are to be regarded as standard.
5. Requirements for Component Conductors
1.3 This standard does not purport to address all of the
5.1 Before twisting, the component conductors shall con-
safety concerns, if any, associated with its use. It is the
form to the requirements of Specification B232/B232M.
responsibility of the user of this standard to establish appro-
priate safety and health practices and determine the applica-
6. Twist
bility of regulatory limitations prior to use.
6.1 The component conductors shall be twisted about them-
2. Referenced Documents
selves with a complete twist every 9 ft 6 1 ft.This twist length
shall be measured between the twisting machine and the
2.1 The following documents of the issue in effect on the
take-up reel with normal take-up tension on the ACSR/TP.
date of material purchase form a part of this specification to the
extent referenced herein:
NOTE 3—The twist length can be altered as the ACSR/TP is wound up
2
2.2 ASTM Standards:
onto the take-up reel. It may not have the same twist length as when the
TP is removed from the reel.
1 6.2 The direction of the twist shall be left hand.
This specification is under the jurisdiction of ASTM Committee B01 on
Electrical Conductors and is the direct responsibility of Subcommittee B01.07 on
7. Construction Requirements
Conductors of Light Metals.
Current edition approved Oct.1, 2005. Published November 2005. Originally
7.1 Construction requirements are given in Table 1 for
approved in 2000. Last previous edition approved in 2000 as B911/B911M – 00.
ACSR/TP.
DOI: 10.1520/B0911_B0911M-05.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Standards volume information, refer to the standard’s Document Summary page on
the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
B911/B911M – 05
TABLE 1 Construction Requirements for TP Type Conductor Using Aluminum Conductor, Steel Reinforced (ACSR)
A
Code Word Component Composition Outer Dimensions in.
D
Equivalent
Resistance
Size AWG or B
AWG or Nominal Mass Ohms/1000ft
C
kcmil
kcmil Aluminum Steel minor major lb/1000ft Rated Strg. lb dc at 20°C
Swan / TP 1 4 6 3 0.0834 1 3 0.0834 0.250 3 0.500 115 3700 0.2016
Swanate / TP 1 4 7 3 0.0772 1 3 0
...