ASTM D2321-09
(Practice)Standard Practice for Underground Installation of Thermoplastic Pipe for Sewers and Other Gravity-Flow Applications
Standard Practice for Underground Installation of Thermoplastic Pipe for Sewers and Other Gravity-Flow Applications
SIGNIFICANCE AND USE
This practice is for use by designers and specifiers, installation contractors, regulatory agencies, owners, and inspection organizations who are involved in the construction of sewers and other gravity-flow applications that utilize flexible thermoplastic pipe. As with any standard practice, modifications may be required for specific job conditions or for special local or regional conditions. Recommendations for inclusion of this practice in contract documents for a specific project are given in Appendix X2.
SCOPE
1.1 This practice provides recommendations for the installation of buried thermoplastic pipe used in sewers and other gravity-flow applications. These recommendations are intended to ensure a stable underground environment for thermoplastic pipe under a wide range of service conditions. However, because of the numerous flexible plastic pipe products available and the inherent variability of natural ground conditions, achieving satisfactory performance of any one product may require modification to provisions contained herein to meet specific project requirements.
1.2 The scope of this practice necessarily excludes product performance criteria such as minimum pipe stiffness, maximum service deflection, or long term strength. Thus, it is incumbent upon the product manufacturer, specifier, or project engineer to verify and assure that the pipe specified for an intended application, when installed according to procedures outlined in this practice, will provide a long term, satisfactory performance according to criteria established for that application. A commentary on factors important in achieving a satisfactory installation is included in Appendix X1.
Note 1—Specific paragraphs in the appendix are referenced in the body of this practice for informational purposes.
Note 2—The following ASTM standards may be found useful in connection with this practice: Practice D420, Test Method D1556, Method D2216, Specification D2235, Test Method D2412, Specification D2564, Practice D2657, Practice D2855, Test Methods D2922, Test Method D3017, Practice F402, Specification F477, Specification F545, and Specification F913.
Note 3—Most Plumbing Codes and some Building Codes have provisions for the installation of underground “building drains and building sewers.” See them for plumbing piping applications.
1.3 Units—The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
General Information
Relations
Buy Standard
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
An American National Standard
Designation: D2321 – 09
Standard Practice for
Underground Installation of Thermoplastic Pipe for Sewers
1
and Other Gravity-Flow Applications
This standard is issued under the fixed designation D2321; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the Department of Defense.
1. Scope* 1.4 This standard does not purport to address all of the
safety concerns, if any, associated with its use. It is the
1.1 This practice provides recommendations for the instal-
responsibility of the user of this standard to establish appro-
lation of buried thermoplastic pipe used in sewers and other
priate safety and health practices and determine the applica-
gravity-flow applications. These recommendations are in-
bility of regulatory limitations prior to use.
tended to ensure a stable underground environment for ther-
moplastic pipe under a wide range of service conditions.
2. Referenced Documents
However, because of the numerous flexible plastic pipe prod-
2
2.1 ASTM Standards:
ucts available and the inherent variability of natural ground
D8 Terminology Relating to Materials for Roads and Pave-
conditions, achieving satisfactory performance of any one
ments
product may require modification to provisions contained
D420 Guide to Site Characterization for Engineering De-
herein to meet specific project requirements.
sign and Construction Purposes
1.2 The scope of this practice necessarily excludes product
D653 Terminology Relating to Soil, Rock, and Contained
performance criteria such as minimum pipe stiffness, maxi-
Fluids
mum service deflection, or long term strength. Thus, it is
D698 Test Methods for Laboratory Compaction Character-
incumbent upon the product manufacturer, specifier, or project
3
istics of Soil Using Standard Effort (12 400 ft-lbf/ft (600
engineer to verify and assure that the pipe specified for an
3
kN-m/m ))
intended application, when installed according to procedures
D1556 Test Method for Density and Unit Weight of Soil in
outlined in this practice, will provide a long term, satisfactory
Place by Sand-Cone Method
performance according to criteria established for that applica-
D2216 Test Methods for Laboratory Determination of Wa-
tion. A commentary on factors important in achieving a
ter (Moisture) Content of Soil and Rock by Mass
satisfactory installation is included in Appendix X1.
D2235 Specification for Solvent Cement for Acrylonitrile-
NOTE 1—Specific paragraphs in the appendix are referenced in the
Butadiene-Styrene (ABS) Plastic Pipe and Fittings
body of this practice for informational purposes.
D2412 Test Method for Determination of External Loading
NOTE 2—The following ASTM standards may be found useful in
Characteristics of Plastic Pipe by Parallel-Plate Loading
connectionwiththispractice:PracticeD420,TestMethodD1556,Method
D2487 Practice for Classification of Soils for Engineering
D2216, Specification D2235, Test Method D2412, Specification D2564,
Purposes (Unified Soil Classification System)
Practice D2657, Practice D2855, Test Methods D2922, Test Method
D3017, Practice F402, Specification F477, Specification F545, and D2488 Practice for Description and Identification of Soils
Specification F913.
(Visual-Manual Procedure)
NOTE 3—Most Plumbing Codes and some Building Codes have provi-
D2564 Specification for Solvent Cements for Poly(Vinyl
sions for the installation of underground “building drains and building
Chloride) (PVC) Plastic Piping Systems
sewers.” See them for plumbing piping applications.
D2657 Practice for Heat Fusion Joining of Polyolefin Pipe
1.3 Units—The values stated in inch-pound units are to be
and Fittings
regarded as standard. The values given in parentheses are
mathematical conversions to SI units that are provided for
information only and are not considered standard.
1
This practice is under the jurisdiction of ASTM Committee F17 on Plastic
2
Piping Systems and is the direct responsibility of Subcommittee F17.62 on Sewer. For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Current edition approved Dec. 15, 2009. Published February 2010. Originally contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
approved in 1989. Last previous edition approved in 2008 as D2321 – 08. DOI: Standards volume information, refer to the standard’s Document Summary page on
10.1520/D2321-09. the ASTM website.
*A Summary of Changes section appears at the end of this standard.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, Uni
...
This document is not anASTM standard and is intended only to provide the user of anASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
An American National Standard
Designation:D2321–08 Designation: D2321 – 09
Standard Practice for
Underground Installation of Thermoplastic Pipe for Sewers
1
and Other Gravity-Flow Applications
This standard is issued under the fixed designation D2321; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the Department of Defense.
1. Scope*
1.1 This practice provides recommendations for the installation of buried thermoplastic pipe used in sewers and other
gravity-flow applications.These recommendations are intended to ensure a stable underground environment for thermoplastic pipe
under a wide range of service conditions. However, because of the numerous flexible plastic pipe products available and the
inherent variability of natural ground conditions, achieving satisfactory performance of any one product may require modification
to provisions contained herein to meet specific project requirements.
1.2 The scope of this practice necessarily excludes product performance criteria such as minimum pipe stiffness, maximum
service deflection, or long term strength. Thus, it is incumbent upon the product manufacturer, specifier, or project engineer to
verify and assure that the pipe specified for an intended application, when installed according to procedures outlined in this
practice, will provide a long term, satisfactory performance according to criteria established for that application. A commentary
on factors important in achieving a satisfactory installation is included in Appendix X1.
NOTE 1—Specific paragraphs in the appendix are referenced in the body of this practice for informational purposes.
NOTE 2—The following ASTM standards may be found useful in connection with this practice: Practice D420, Test Method D1556, Method D2216,
Specification D2235, Test Method D2412, Specification D2564, Practice D2657, Practice D2855, Test Methods D2922, Test Method D3017, Practice
F402, Specification F477, Specification F545, and Specification F913.
NOTE 3—Most Plumbing Codes and some Building Codes have provisions for the installation of underground “building drains and building sewers.”
See them for plumbing piping applications.
1.3 Units—The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are
mathematical conversions to SI units that are provided for information only and are not considered standard.
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use.
2. Referenced Documents
2
2.1 ASTM Standards:
D8 Terminology Relating to Materials for Roads and Pavements
D420 Guide to Site Characterization for Engineering Design and Construction Purposes
D653 Terminology Relating to Soil, Rock, and Contained Fluids
3 3
D698 Test Methods for Laboratory Compaction Characteristics of Soil Using Standard Effort (12 400 ft-lbf/ft (600 kN-m/m ))
D1556 Test Method for Density and Unit Weight of Soil in Place by Sand-Cone Method
D2216 Test Methods for Laboratory Determination of Water (Moisture) Content of Soil and Rock by Mass
D2235 Specification for Solvent Cement for Acrylonitrile-Butadiene-Styrene (ABS) Plastic Pipe and Fittings
D2412 Test Method for Determination of External Loading Characteristics of Plastic Pipe by Parallel-Plate Loading
D2487 Practice for Classification of Soils for Engineering Purposes (Unified Soil Classification System)
D2488 Practice for Description and Identification of Soils (Visual-Manual Procedure)
D2564 Specification for Solvent Cements for Poly(Vinyl Chloride) (PVC) Plastic Piping Systems
D2657 Practice for Heat Fusion Joining of Polyolefin Pipe and Fittings
D2855 Practice for Making Solvent-Cemented Joints with Poly(Vinyl Chloride) (PVC) Pipe and Fittings
1
This practice is under the jurisdiction of ASTM Committee F17 on Plastic Piping Systems and is the direct responsibility of Subcommittee F17.62 on Sewer.
Current edition approved Dec. 1, 2008.15, 2009. Published January 2009.February 2010. Originally approved in 1989. Last previous edition approved in 20052008 as
D2321 – 058. DOI: 10.1520/D2321-089.
2
For refere
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.