ASTM F1336-20
(Specification)Standard Specification for Poly(Vinyl Chloride) (PVC) Gasketed Sewer Fittings
Standard Specification for Poly(Vinyl Chloride) (PVC) Gasketed Sewer Fittings
ABSTRACT
This specification covers the material, dimensional, and mechanical requirements, and associated test methods for fabricated or molded poly(vinyl chloride) (PVC) gasketed sewer fittings manufactured from pipe, or from a combination of pipe and injection molded parts, or from injection molded parts that are suitable for non-pressure drainage of sewage and surface water, as well as applications involving subsurface drainage. The fittings shall adhere to specified values for outside diameter, wall thickness, socket length, and spigot length. When evaluated according to the test procedures provided herein, the fittings shall meet specified requirements for impact strength, pipe stop load support, internal stress, and branch bending. The products shall also undergo referee testing and quality control tests.
SCOPE
1.1 This specification covers requirements and test methods for fabricated or molded poly(vinyl chloride) (PVC) gasketed sewer fittings to be used with piping manufactured to Specifications D3034, F679, F891 or F1760. Fabricated fittings may be manufactured from pipe, or from a combination of pipe and injection molded parts, or from injection molded parts. Gasketed sewer fitting configurations may include one or more spigot outlets.
1.2 The requirements of this specification are to provide fabricated or molded PVC gasketed fittings suitable for non-pressure drainage of sewage and surface water, as well as applications involving subsurface drainage.
Note 1: Industrial waste lines should be installed only with the specific approval of the governing code authority when using chemicals not commonly found in drains and sewers or temperatures in excess of 140 °F (60 °C), or both.
1.3 Fittings produced to this specification are intended to be installed with pipe, in accordance with Practice D2321.
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.5 The following precautionary caveat pertains to the test method portion only, Section 10, of this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
1.6 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
General Information
Relations
Buy Standard
Standards Content (Sample)
This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
Designation:F1336 −20
Standard Specification for
1
Poly(Vinyl Chloride) (PVC) Gasketed Sewer Fittings
This standard is issued under the fixed designation F1336; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope* 2. Referenced Documents
2
1.1 This specification covers requirements and test methods
2.1 ASTM Standards:
for fabricated or molded poly(vinyl chloride) (PVC) gasketed
D618 Practice for Conditioning Plastics for Testing
sewer fittings to be used with piping manufactured to Specifi-
D1600 Terminology forAbbreviatedTerms Relating to Plas-
cations D3034, F679, F891 or F1760. Fabricated fittings may
tics
be manufactured from pipe, or from a combination of pipe and
D1784 Classification System and Basis for Specification for
injection molded parts, or from injection molded parts. Gas-
Rigid Poly(Vinyl Chloride) (PVC) Compounds and Chlo-
keted sewer fitting configurations may include one or more
rinated Poly(Vinyl Chloride) (CPVC) Compounds
spigot outlets.
D2122 Test Method for Determining Dimensions of Ther-
1.2 The requirements of this specification are to provide
moplastic Pipe and Fittings
fabricated or molded PVC gasketed fittings suitable for non-
D2321 PracticeforUndergroundInstallationofThermoplas-
pressure drainage of sewage and surface water, as well as
tic Pipe for Sewers and Other Gravity-Flow Applications
applications involving subsurface drainage.
D2444 Practice for Determination of the Impact Resistance
of Thermoplastic Pipe and Fittings by Means of a Tup
NOTE 1—Industrial waste lines should be installed only with the
(Falling Weight)
specific approval of the governing code authority when using chemicals
not commonly found in drains and sewers or temperatures in excess of
D2564 Specification for Solvent Cements for Poly(Vinyl
140 °F (60 °C), or both.
Chloride) (PVC) Plastic Piping Systems
1.3 Fittings produced to this specification are intended to be
D2749 Symbols for Dimensions of Plastic Pipe Fittings
installed with pipe, in accordance with Practice D2321.
D3034 Specification for Type PSM Poly(Vinyl Chloride)
(PVC) Sewer Pipe and Fittings
1.4 The values stated in inch-pound units are to be regarded
D3212 Specification for Joints for Drain and Sewer Plastic
as standard. The values given in parentheses are mathematical
Pipes Using Flexible Elastomeric Seals
conversions to SI units that are provided for information only
F412 Terminology Relating to Plastic Piping Systems
and are not considered standard.
F477 Specification for Elastomeric Seals (Gaskets) for Join-
1.5 The following precautionary caveat pertains to the test
ing Plastic Pipe
method portion only, Section 10, of this specification. This
F610/F610M Practice for Evaluating the Quality of Molded
standarddoesnotpurporttoaddressallofthesafetyconcerns,
Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings by the
ifany,associatedwithitsuse.Itistheresponsibilityoftheuser
Heat Reversion Technique
of this standard to establish appropriate safety, health, and
F656 Specification for Primers for Use in Solvent Cement
environmental practices and determine the applicability of
Joints of Poly(Vinyl Chloride) (PVC) Plastic Pipe and
regulatory limitations prior to use.
Fittings
1.6 This international standard was developed in accor-
F679 Specification for Poly(Vinyl Chloride) (PVC) Large-
dance with internationally recognized principles on standard-
Diameter Plastic Gravity Sewer Pipe and Fittings
ization established in the Decision on Principles for the
F891 Specification for Coextruded Poly(Vinyl Chloride)
Development of International Standards, Guides and Recom-
(PVC) Plastic Pipe With a Cellular Core
mendations issued by the World Trade Organization Technical
F913 Specification for Thermoplastic Elastomeric Seals
Barriers to Trade (TBT) Committee.
(Gaskets) for Joining Plastic Pipe
1
This specification is under the jurisdiction ofASTM Committee F17 on Plastic
2
Piping Systems and is the direct responsibility of Subcommittee F17.62 on Sewer. For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Current edition approved Nov. 1, 2020. Published December 2020. Originally contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
approved in 1991. Last previous edition approved in 2015 as F1336 – 15. DOI: Standards volume information, refer to the standard’s Document Summary page on
10.1520/F1336-20. the ASTM website.
*A Summary of Changes section appears at the end of this
...
This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: F1336 − 15 F1336 − 20
Standard Specification for
1
Poly(Vinyl Chloride) (PVC) Gasketed Sewer Fittings
This standard is issued under the fixed designation F1336; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope*
1.1 This specification covers requirements and test methods for fabricated or molded poly(vinyl chloride) (PVC) gasketed sewer
fittings to be used with piping manufactured to Specifications D3034, F679, F891 or F1760. Fabricated fittings may be
manufactured from pipe, or from a combination of pipe and injection molded parts, or from injection molded parts. Gasketed sewer
fitting configurations may include one or more spigot outlets.
1.2 The requirements of this specification are to provide fabricated or molded PVC gasketed fittings suitable for non-pressure
drainage of sewage and surface water, as well as applications involving subsurface drainage.
NOTE 1—Industrial waste lines should be installed only with the specific approval of the governing code authority when using chemicals not commonly
found in drains and sewers or temperatures in excess of 140°F (60°C),140 °F (60 °C), or both.
1.3 Fittings produced to this specification are intended to be installed with pipe, in accordance with Practice D2321.
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only and are not considered standard.
1.5 The following precautionary caveat pertains to the test method portion only, Section 10, of this specification. This standard
does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this
standard to establish appropriate safety safety, health, and healthenvironmental practices and determine the applicability of
regulatory limitations prior to use.
1.6 This international standard was developed in accordance with internationally recognized principles on standardization
established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued
by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
2. Referenced Documents
2
2.1 ASTM Standards:
D618 Practice for Conditioning Plastics for Testing
D1600 Terminology for Abbreviated Terms Relating to Plastics
D1784 Classification System and Basis for Specification for Rigid Poly(Vinyl Chloride) (PVC) Compounds and Chlorinated
Poly(Vinyl Chloride) (CPVC) Compounds
D2122 Test Method for Determining Dimensions of Thermoplastic Pipe and Fittings
1
This specification is under the jurisdiction of ASTM Committee F17 on Plastic Piping Systems and is the direct responsibility of Subcommittee F17.62 on Sewer.
Current edition approved Nov. 1, 2015Nov. 1, 2020. Published December 2015December 2020. Originally approved in 1991. Last previous edition approved in 20072015
as F1336 – 07.F1336 – 15. DOI: 10.1520/F1336-15.10.1520/F1336-20.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
*A Summary of Changes section appears at the end of this standard
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1
---------------------- Page: 1 ----------------------
F1336 − 20
D2321 Practice for Underground Installation of Thermoplastic Pipe for Sewers and Other Gravity-Flow Applications
D2444 Practice for Determination of the Impact Resistance of Thermoplastic Pipe and Fittings by Means of a Tup (Falling
Weight)
D2564 Specification for Solvent Cements for Poly(Vinyl Chloride) (PVC) Plastic Piping Systems
D2749 Symbols for Dimensions of Plastic Pipe Fittings
D3034 Specification for Type PSM Poly(Vinyl Chloride) (PVC) Sewer Pipe and Fittings
D3212 Specification for Joints for Drain and Sewer Plastic Pipes Using Flexible Elastomeric Seals
F412 Terminology Relating to Plastic Piping Systems
F477 Specification for Elastomeric Seals (Gaskets) for Joining Plastic Pipe
F610/F610M Practice for Evaluating the Quality of Molded Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings by the Heat