Standard Test Method for Determination of Installed Thickness of Pneumatically Applied Loose-Fill Building Insulation

SIGNIFICANCE AND USE
5.1 This test method was designed to give the manufacturer of loose-fill insulation products a way of determining what the initial installed thickness should be in a horizontal open attic for pneumatic applications.  
5.2 The installed thickness value developed by this test method is intended to provide guidance to the installer in order to achieve a minimum mass/unit area for a given R-value.  
5.3 For the purpose of product design, testing should be done at a variety of R-values. At least three R-values should be used: the lowest R-value on the product label, the highest R-value on the product label, and an R-value near the midpoint of the R-value range.Note 1—For quality control purposes, testing may be done at one R-value of R-19 (h×ft 2×°F/Btu) or higher.  
5.4 Specimens are blown in a manner consistent with the intended installation procedure. Blowing machine settings should be representative of those typically used for field application with that machine.  
5.5 The material blown for a given R-value as part of the installed thickness test equals the installed mass/unit area times the test chamber area. This mass can be calculated from information provided on the package label at the R-value prescribed.
SCOPE
1.1 This test method covers determination of the installed thickness of pneumatically applied loose-fill building insulations prior to settling by simulating an open attic with horizontal blown applications.  
1.2 This test method is a laboratory procedure for use by manufacturers of loose-fill insulation for product design, label development, and quality control testing. The apparatus used produces installed thickness results at a given mass/unit area.  
1.3 This test method is not the same as the design density procedures described in Test Methods C520 or Specifications C739 or C764.  
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.  
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
14-Apr-2014
Technical Committee
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM C1374-14 - Standard Test Method for Determination of Installed Thickness of Pneumatically Applied Loose-Fill Building Insulation
English language
5 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
REDLINE ASTM C1374-14 - Standard Test Method for Determination of Installed Thickness of Pneumatically Applied Loose-Fill Building Insulation
English language
5 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: C1374 − 14
Standard Test Method for
Determination of Installed Thickness of Pneumatically
1
Applied Loose-Fill Building Insulation
This standard is issued under the fixed designation C1374; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope E691Practice for Conducting an Interlaboratory Study to
Determine the Precision of a Test Method
1.1 This test method covers determination of the installed
thickness of pneumatically applied loose-fill building insula-
3. Terminology
tions prior to settling by simulating an open attic with
horizontal blown applications. 3.1 Definitions—Unless otherwise stated, the definitions
listed in Terminology C168 are applicable herein.
1.2 This test method is a laboratory procedure for use by
manufacturers of loose-fill insulation for product design, label 3.2 Definitions of Terms Specific to This Standard:
development, and quality control testing. The apparatus used
3.2.1 installed thickness, n—the average thickness, as mea-
produces installed thickness results at a given mass/unit area. sured immediately after application of blown insulation mate-
rial when applied at a given mass/unit area.
1.3 This test method is not the same as the design density
procedures described in Test Methods C520 or Specifications
4. Summary of Test Method
C739 or C764.
2 2
4.1 Astandardizedtestchamberof80ft (7.4m )isusedas
1.4 Thevaluesstatedininch-poundunitsaretoberegarded
areceptacletoreceiveacalculatedmass/unitareaofpneumati-
as standard. The values given in parentheses are mathematical
cally applied insulation.
conversions to SI units that are provided for information only
and are not considered standard.
4.2 Themassofinsulationtobeblownintothetestchamber
is calculated from the bag label information.
1.5 This standard does not purport to address all of the
safety concerns, if any, associated with its use. It is the
4.3 The mass of insulation prescribed in 4.2 is uniformly
responsibility of the user of this standard to establish appro-
blown into the test chamber.
priate safety and health practices and determine the applica-
4.4 The thickness of the blown insulation is determined at
bility of regulatory limitations prior to use.
13 predetermined locations.
2. Referenced Documents 4.5 The thickness average of three tests is the installed
2 thickness for the mass/unit area being tested.
2.1 ASTM Standards:
C168Terminology Relating to Thermal Insulation
5. Significance and Use
C520Test Methods for Density of Granular Loose Fill
Insulations
5.1 This test method was designed to give the manufacturer
C739Specification for Cellulosic Fiber Loose-Fill Thermal of loose-fill insulation products a way of determining what the
Insulation
initial installed thickness should be in a horizontal open attic
C764Specification for Mineral Fiber Loose-Fill Thermal for pneumatic applications.
Insulation
5.2 The installed thickness value developed by this test
methodisintendedtoprovideguidancetotheinstallerinorder
to achieve a minimum mass/unit area for a given R-value.
1
ThistestmethodisunderthejurisdictionofASTMCommitteeC16onThermal
Insulation and is the direct responsibility of Subcommittee C16.32 on Mechanical 5.3 For the purpose of product design, testing should be
Properties.
doneatavarietyof R-values.Atleastthree R-valuesshouldbe
Current edition approved April 15, 2014. Published May 2014. Originally
used: the lowest R-value on the product label, the highest
approvedin1997.Lastpreviouseditionapprovedin2009asC1374–03(2009).DOI:
R-valueontheproductlabel,andan R-valuenearthemidpoint
10.1520/C1374-14.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
of the R-value range.
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Standards volume information, refer to the standard’s Document Summary page on NOTE 1—For quality control purposes, testing may be done at one
2
the ASTM website. R-value of R-19 (h×ft ×°F/Btu) or higher.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
C1374 − 14
FIG. 1 Installed Thickness Test Chamber
5.4 Specimens are blown in a manner consistent with the
intended installation procedure. Blowing machine settings
should be representative of those typically used for field
FIG. 2 Dowel Placement in Chamber Floor
application with that machine.
5.5 The material blown for a given R-value as part of the
installedthicknesstestequalstheinstalledmass/unitareatimes
6.5 Specimen Preparation Room—An enclosed area where
the tes
...

This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: C1374 − 03 (Reapproved 2009) C1374 − 14
Standard Test Method for
Determination of Installed Thickness of Pneumatically
1
Applied Loose-Fill Building Insulation
This standard is issued under the fixed designation C1374; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This test method covers determination of the installed thickness of pneumatically applied loose-fill building insulations prior
to settling by simulating an open attic with horizontal blown applications.
1.2 This test method is a laboratory procedure for use by manufacturers of loose-fill insulation for product design, label
development, and quality control testing. The apparatus used produces installed thickness results at a given mass/unit area.
1.3 This test method is not the same as the design density procedures described in Test Methods C520 or Specifications C739
or C764.
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only and are not considered standard.
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use.
2. Referenced Documents
2
2.1 ASTM Standards:
C168 Terminology Relating to Thermal Insulation
C520 Test Methods for Density of Granular Loose Fill Insulations
C739 Specification for Cellulosic Fiber Loose-Fill Thermal Insulation
C764 Specification for Mineral Fiber Loose-Fill Thermal Insulation
E691 Practice for Conducting an Interlaboratory Study to Determine the Precision of a Test Method
3. Terminology
3.1 Definitions—Unless otherwise stated, the definitions listed in Terminology C168 are applicable herein.
3.2 Definitions of Terms Specific to This Standard:
3.2.1 installed thickness, n—the average thickness, as measured immediately after application of blown insulation material
when applied at a given mass/unit area.
4. Summary of Test Method
2 2
4.1 A standardized test chamber of 80 ft (7.4 m ) is used as a receptacle to receive a calculated mass/unit area of pneumatically
applied insulation.
4.2 The mass of insulation to be blown into the test chamber is calculated from the bag label information.
4.3 The mass of insulation prescribed in 4.2 is uniformly blown into the test chamber.
4.4 The thickness of the blown insulation is determined at 13 predetermined locations.
4.5 The thickness average of three tests is the installed thickness for the mass/unit area being tested.
1
This test method is under the jurisdiction of ASTM Committee C16 on Thermal Insulation and is the direct responsibility of Subcommittee C16.32 on Mechanical
Properties.
Current edition approved Nov. 1, 2009April 15, 2014. Published March 2010May 2014. Originally approved in 1997. Last previous edition approved in 20032009 as
C1374–03.C1374–03(2009). DOI: 10.1520/C1374-03R09.10.1520/C1374-14.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
C1374 − 14
FIG. 1 Installed Thickness Test Chamber
5. Significance and Use
5.1 This test method was designed to give the manufacturer of loose-fill insulation products a way of determining what the
initial installed thickness should be in a horizontal open attic for pneumatic applications.
5.2 The installed thickness value developed by this test method is intended to provide guidance to the installer in order to
achieve a minimum mass/unit area for a given R-value.
5.3 For the purpose of product design, testing should be done at a variety of R-values. At least three R-values should be used:
the lowest R-value on the product label, the highest R-value on the product label, and an R-value near the midpoint of the R-value
range.
2
NOTE 1—For quality control purposes, testing may be done at one R-value of R-1
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.