Standard Specification for Vitrified Clay Pipe, Extra Strength, Standard Strength, and Perforated

SCOPE
1.1 This specification establishes the criteria for acceptance, prior to installation, of extra strength and standard strength vitrified clay pipe and fittings to be used for the conveyance of sewage, industrial wastes, and storm water; and extra strength perforated and standard strength perforated vitrified clay pipe to be used for underdrainage, filter fields, leaching fields, and similar subdrainage installations.
1.2 The values stated in inch-pound units are to be regarded as the standard. The values given in parentheses are for information only. Note 1Attention is called to Specification C 425, Test Method C 828, Test Method C 1091, Test Methods C 301, and Terminology C 896.
The following precautionary caveat pertains only to the Test Method portion, of this standard: This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
31-Mar-2007
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM C700-07e1 - Standard Specification for Vitrified Clay Pipe, Extra Strength, Standard Strength, and Perforated
English language
4 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
e1
Designation: C 700 – 07
Standard Specification for
Vitrified Clay Pipe, Extra Strength, Standard Strength, and
1
Perforated
This standard is issued under the fixed designation C 700; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the Department of Defense.
1
e NOTE—Table 1 was editorially corrected in September 2007.
1. Scope C 1091 Test Method for Hydrostatic Infiltration Testing of
Vitrified Clay Pipe Lines
1.1 This specification establishes the criteria for acceptance,
prior to installation, of extra strength and standard strength
3. Terminology
vitrified clay pipe and fittings to be used for the conveyance of
3.1 Definitions—Clay, fire clay, shale, and surface clay are
sewage, industrial wastes, and storm water; and extra strength
as defined in Terminology C 896.
perforated and standard strength perforated vitrified clay pipe
to be used for underdrainage, filter fields, leaching fields, and
4. Materials and Manufacture
similar subdrainage installations.
4.1 Vitrified clay pipe shall be manufactured from fire clay,
1.2 The values stated in inch-pound units are to be regarded
shale, surface clay, or a combination of these materials that,
as the standard. The values given in parentheses are for
when formed into pipe and fired to suitable temperatures,
information only.
yields a product that conforms to this specification.
NOTE 1—AttentioniscalledtoSpecificationC 425,TestMethodC 828,
Test Method C 1091, Test Methods C 301, and Terminology C 896.
5. Physical Properties
1.3 The following precautionary caveat pertains only to the 5.1 Bearing Strength:
TestMethodportion,5.2-5.2.3.2ofthisstandard: This standard 5.1.1 Pipe shall meet the bearing strength requirements of
does not purport to address all of the safety concerns, if any, Table 1.
associated with its use. It is the responsibility of the user of this 5.1.2 The number of specimens to be tested shall not exceed
standard to establish appropriate safety and health practices 0.5 % of the number of pipe of each size furnished, except that
and determine the applicability of regulatory limitations prior no less than two specimens shall be tested.
to use. 5.1.3 If any of the test specimens fail to meet the require-
ments, the manufacturer will be allowed a retest on two
2. Referenced Documents
additional specimens for each one that failed. The pipe will be
2
2.1 ASTM Standards: acceptable if all the retest specimens meet the test requirement.
C 301 Test Methods for Vitrified Clay Pipe
5.1.4 If, subsequent to an initial pipe strength failure, the
C 425 Specification for Compression Joints for Vitrified accuracy of the testing equipment is questioned, at the request
Clay Pipe and Fittings
of the manufacturer, the equipment shall be recalibrated and a
C 828 Test Method for Low-Pressure Air Test of Vitrified retest made or a retest made upon equipment of known
Clay Pipe Lines
accuracy.
C 896 Terminology Relating to Clay Products 5.2 Hydrostatic Pressure Test or Absorption Test:
5.2.1 The manufacturer shall at his option, apply either a
hydrostatic pressure test or an absorption test to all of the test
1
This specification is under the jurisdiction of ASTM Committee C04 on
specimens in each size and run of the pipe.
Vitrified Clay Pipe and is the direct responsibility of Subcommittee C04.20 on
5.2.2 Hydrostatic Pressure Test:
Methods of Test and Specifications
5.2.2.1 When the pipe is subjected to an internal hydrostatic
Current edition approved April 1, 2007. Published May 2007. Originally
approved in 1971. Last previous edition approved in 2005 as C 700 – 05.
pressure of 10 psi (68.9 KPa) for the elapsed time shown in the
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
following table, there shall be no leaking on the exterior of the
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
pipe. Moisture appearing on the surface of the pipe in the form
Standards volume information, refer to the standard’s Document Summary page on
the ASTM website. of beads adhering to the surface shall not be considered
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
e1
C700–07
TABLE 1 Minimum Strength (3-Edge Bearing)
Perforated Vitrified Clay Pipe
Extra Strength Standard Strength
Nominal
Vitrified Clay Pipe Vitrified Clay Pipe
Extra Strength Standard Strength
Size, in.
(mm) lbf/linear kN/linear lbf/linear kN/linear lbf/linear kN/linear lbf/linear kN/linear
ft m ft m ft m
...