ASTM E2273-03(2011)
(Test Method)Standard Test Method for Determining the Drainage Efficiency of Exterior Insulation and Finish Systems (EIFS) Clad Wall Assemblies
Standard Test Method for Determining the Drainage Efficiency of Exterior Insulation and Finish Systems (EIFS) Clad Wall Assemblies
SIGNIFICANCE AND USE
This test method is a standard procedure for determining the drainage efficiency of an EIFS clad wall assembly.
SCOPE
1.1 This test method determines the drainage efficiency of EIFS clad wall assemblies when subjected to a water spray rate in accordance with Test Method E331.
1.2 The values stated in SI units are to be regarded as the standard. The values given in parentheses are mathematical conversions to inch-pound units that are provided for information only and are not considered standard.
1.3 This standard may involve hazardous materials, operations and equipment. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
General Information
Relations
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: E2273 − 03 (Reapproved 2011)
Standard Test Method for
Determining the Drainage Efficiency of Exterior Insulation
and Finish Systems (EIFS) Clad Wall Assemblies
This standard is issued under the fixed designation E2273; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope 3.2.2 test specimen—theentireassembledunitsubmittedfor
testing as described in Section 7.
1.1 This test method determines the drainage efficiency of
EIFScladwallassemblieswhensubjectedtoawatersprayrate 3.2.3 test specimen slot fault—an opening in the test speci-
in accordance with Test Method E331. men where the insulation board, and other components have
been removed exposing the weather-resistive barrier to which
1.2 The values stated in SI units are to be regarded as the
water spray is directed.
standard. The values given in parentheses are mathematical
conversions to inch-pound units that are provided for informa- 3.2.4 water drainage—the ability of the test specimen to
tion only and are not considered standard. drain water.
1.3 This standard may involve hazardous materials, opera-
4. Summary of Test Method
tions and equipment. This standard does not purport to address
all of the safety concerns, if any, associated with its use. It is
4.1 This test method consists of sealing a spray box to the
the responsibility of the user of this standard to establish
testspecimenandthenconcentratingawatersprayintotheslot
appropriate safety and health practices and determine the
fault of the test specimen.
applicability of regulatory limitations prior to use.
5. Significance and Use
2. Referenced Documents
5.1 Thistestmethodisastandardprocedurefordetermining
2.1 ASTM Standards:
the drainage efficiency of an EIFS clad wall assembly.
E331 Test Method for Water Penetration of Exterior
Windows, Skylights, Doors, and Curtain Walls by Uni-
6. Apparatus
form Static Air Pressure Difference
6.1 Spray Box, a transparent plastic, or equivalent, box
E2110Terminology for Exterior Insulation and Finish Sys-
1 1 1
measuring 622 by241 by184mm (24 ⁄2 by9 ⁄2 by7 ⁄4 in.)
tems (EIFS)
containing a water spray system that is sealed to the test
3. Terminology specimen.
3.1 Definitions used in this standard shall be in accordance
6.2 Water Spray System, two spray nozzles installed in the
with Terminology E2110.
spray box, oriented to apply all the water into the slot fault and
located 13mm ( ⁄2 in.) from the open side of the spray box and
3.2 Definitions of Terms Specific to This Standard:
150mm(6in.)totherightandleftofverticalcenteroftheslot
3.2.1 drainage effıciency—a percentage value based on the
fault.Apressureregulator,flowmeter,andaninlinewaterfilter
amountofwaterthatpassedthroughthetestspecimenandwas
to the spray nozzles control the flow rate of water sprayed into
collected divided by the amount of water sprayed into the slot
the slot fault. The water spray system shall deliver water at a
fault.
rate of 106g (0.234lb) per minute +10%−0%.
6.3 Drained Water Container(s), a container, or containers,
This test method is under the jurisdiction of ASTM Committee E06 on
tared to the nearest 1.0g (0.002lb) of sufficient size to retain
Performance of Buildings and is the direct responsibility of Subcommittee E06.58
the water drained from the test specimen.
on Exterior Insulation and Finish Systems (EIFS).
Current edition approved April 1, 2011. Published May 2011. Originally
6.4 Balance, with a capacity of 20kg (45lb) and accuracy
approved in 2003. Last previous edition approved in 2003 as E2273–03. DOI:
of 1.0g (0.002lb).
10.1520/E2273-03R11.
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
6.5 A means of collection such as a trough, to direct the
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
drained water to the drained water container. The collection
Standards volume information, refer to the standard’s Document Summary page on
the ASTM website. method may also be the tared container.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
E2273 − 03 (2011)
FIG. 1 EIFS Test Specimen
7. Calibration of Flow Rate specimenshallbesealedattheinterfaceoftheinsulationboard
and substrate. This can be accomplished by edge wrapping the
7.1 Collect the water from the water spray system i
...