Standard Test Method for Time of Setting of Grouts for Preplaced-Aggregate Concrete in the Laboratory

SIGNIFICANCE AND USE
This test method determines the setting time of grout mixed to the fluid consistency required for its use in PA concrete.
The time of setting is also useful in determining the acceptability of components of grout that must be mixed to the fluid consistency required for production of PA concrete.
SCOPE
1.1 This method covers the determination test of time of setting of hydraulic cement grout mixtures used in preplaced-aggregate (PA) concrete using the vicat apparatus.
1.2 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
14-Jun-2010
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM C953-10 - Standard Test Method for Time of Setting of Grouts for Preplaced-Aggregate Concrete in the Laboratory
English language
2 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
REDLINE ASTM C953-10 - Standard Test Method for Time of Setting of Grouts for Preplaced-Aggregate Concrete in the Laboratory
English language
2 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
REDLINE ASTM C953-10 - Standard Test Method for Time of Setting of Grouts for Preplaced-Aggregate Concrete in the Laboratory
English language
2 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: C953 − 10
Standard Test Method for
Time of Setting of Grouts for Preplaced-Aggregate Concrete
1
in the Laboratory
This standard is issued under the fixed designation C953; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope* 4. Summary of Method
4.1 The time of setting, initial and final, of a sample of fluid
1.1 This method covers the determination test of time of
grout is determined using the Vicat apparatus.
setting of hydraulic cement grout mixtures used in preplaced-
aggregate (PA) concrete using the vicat apparatus.
5. Significance and Use
1.2 The values stated in SI units are to be regarded as
5.1 This test method determines the setting time of grout
standard. No other units of measurement are included in this
mixed to the fluid consistency required for its use in PA
standard.
concrete.
1.3 This standard does not purport to address all of the
5.2 The time of setting is also useful in determining the
safety concerns, if any, associated with its use. It is the
acceptability of components of grout that must be mixed to the
responsibility of the user of this standard to establish appro-
fluid consistency required for production of PA concrete.
priate safety and health practices and determine the applica-
bility of regulatory limitations prior to use.
6. Apparatus
6.1 Vicat Apparatus, in accordance with Test Method C191.
2. Referenced Documents
2
6.2 Moist Room, maintained in accordance with Specifica-
2.1 ASTM Standards:
tion C511.
C125 Terminology Relating to Concrete and Concrete Ag-
gregates
7. Test Sample
C191 TestMethodsforTimeofSettingofHydraulicCement
by Vicat Needle
7.1 The test sample shall consist of at least 300 mLof grout
C219 Terminology Relating to Hydraulic Cement
taken from a freshly-mixed batch prepared in accordance with
C938 Practice for Proportioning Grout Mixtures for
Practice C938 obtained from a mixer at the laboratory or
Preplaced-Aggregate Concrete
construction site.
C511 Specification for Mixing Rooms, Moist Cabinets,
Moist Rooms, and Water Storage Tanks Used in the
8. Procedure
Testing of Hydraulic Cements and Concretes
8.1 Warm the Vicat conical ring and base plate to approxi-
mately 100 °C.
3. Terminology
8.2 Apply a thin film of paraffin wax to the base of the
3.1 Definitions:
conical ring and place the waxed conical ring on the base plate.
3.1.1 For definitions of terms used in this test method, refer
Place a weight on the conical ring to ensure intimate contact
to Terminologies C125 and C219. with the base plate and allow the conical ring and plate to cool
to room temperature.
8.3 Fill the conical ring apparatus with grout flush with its
1
This test method is under the jurisdiction of ASTM Committee C09 on
top within 2 min after completion of mixing. Strike off the
Concrete and Concrete Aggregatesand is the direct responsibility of Subcommittee
grout flush with the top of the conical ring by a single oblique
C09.41 on Hydraulic Cement Grouts.
stroke of a sharp-edged trowel held at a slight angle to the top
Current edition approved June 15, 2010. Published July 2010. Originally
of the ring. Smooth the top, if necessary, with a few light
approv
...

This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation:C953–06 Designation:C953–10
Standard Test Method for
Time of Setting of Grouts for Preplaced-Aggregate Concrete
1
in the Laboratory
This standard is issued under the fixed designation C953; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope*
1.1 This method covers the determination test of time of setting of hydraulic cement grout mixtures used in preplaced-aggregate
(PA) concrete using the vicat apparatus.
1.2The values stated in SI units are to be regarded as the standard.
1.2 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use.
2. Referenced Documents
2
2.1 ASTM Standards:
C125 Terminology Relating to Concrete and Concrete Aggregates
C191 Test Methods for Time of Setting of Hydraulic Cement by Vicat Needle
C219 Terminology Relating to Hydraulic Cement
C938 Practice for Proportioning Grout Mixtures for Preplaced-Aggregate Concrete
C511 Specification for Mixing Rooms, Moist Cabinets, Moist Rooms, and Water Storage Tanks Used in the Testing of
Hydraulic Cements and Concretes
3. Summary of Method
3.1The time of setting, initial and final, of a sample of fluid grout is determined using the Vicat apparatus. Terminology
3.1 Definitions:
3.1.1 For definitions of terms used in this test method, refer to Terminologies C125 and C219.
4. Significance and Use
4.1This test method determines the setting time of grout mixed to the fluid consistency required for its use in PA concrete.
4.2The time of setting is also useful in determining the acceptability of components of grout that must be mixed to the fluid
consistency required for production of PA concrete. Summary of Method
4.1 The time of setting, initial and final, of a sample of fluid grout is determined using the Vicat apparatus.
5. Significance and Use
5.1 This test method determines the setting time of grout mixed to the fluid consistency required for its use in PA concrete.
5.2 The time of setting is also useful in determining the acceptability of components of grout that must be mixed to the fluid
consistency required for production of PA concrete.
6. Apparatus
5.1
6.1 Vicat Apparatus, in accordance with Test Method C191.
5.2
1
This test method is under the jurisdiction of ASTM Committee C09 on Concrete and Concrete Aggregates and is the direct responsibility of Subcommittee C09.41 on
Concrete for Radiation Shielding.
Current edition approved Feb. 1, 2006. Published February 2006. Originally approved in 1981. Last previous edition approved in 1997 as C953–87(1997). DOI:
10.1520/C0953-06.on Hydraulic Cement Grouts.
Current edition approved June 15, 2010. Published July 2010. Originally approved in 1981. Last previous edition approved in 2006 as C953–06. DOI: 10.1520/C0953-10.
2
For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
*A Summary of Changes section appears at the end of this standard.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
C953–10
6.2 Moist Room, maintained in accordance with Specification C511.
6.
7. Test Sample
6.1The7.1 The test sample shall consist of at least 300 mL of grout taken from a freshly-mixed batch prepared in accordance
with Practice C938 obtained from a mixer at the laboratory or construction site.
7.
8. Procedure
7.1Warm8.1 Warm the Vicat conical ring and base plate to approximately 100 °C.
7.2Apply8.2 Apply a thin film of paraffin wax to the base of the conical ring and place the waxed conical ring on the base plate.
Place a weight on the conical ring to ensure intimate contact with the base plate and allow the conical ring and plate to cool to
room temperature.
7.3Fill8.3 Fill the conical ring apparatus with grout flush with its top within 2 min after completion of mixing. Stri
...

This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation:C953–06 Designation:C953–10
Standard Test Method for
Time of Setting of Grouts for Preplaced-Aggregate Concrete
1
in the Laboratory
This standard is issued under the fixed designation C953; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope*
1.1 This method covers the determination test of time of setting of hydraulic cement grout mixtures used in preplaced-aggregate
(PA) concrete using the vicat apparatus.
1.2The values stated in SI units are to be regarded as the standard.
1.2 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use.
2. Referenced Documents
2
2.1 ASTM Standards:
C125 Terminology Relating to Concrete and Concrete Aggregates
C191 Test Methods for Time of Setting of Hydraulic Cement by Vicat Needle
C219 Terminology Relating to Hydraulic Cement
C938 Practice for Proportioning Grout Mixtures for Preplaced-Aggregate Concrete
C511 Specification for Mixing Rooms, Moist Cabinets, Moist Rooms, and Water Storage Tanks Used in the Testing of
Hydraulic Cements and Concretes
3. Summary of Method
3.1The time of setting, initial and final, of a sample of fluid grout is determined using the Vicat apparatus. Terminology
3.1 Definitions:
3.1.1 For definitions of terms used in this test method, refer to Terminologies C125 and C219.
4. Significance and Use
4.1This test method determines the setting time of grout mixed to the fluid consistency required for its use in PA concrete.
4.2The time of setting is also useful in determining the acceptability of components of grout that must be mixed to the fluid
consistency required for production of PA concrete. Summary of Method
4.1 The time of setting, initial and final, of a sample of fluid grout is determined using the Vicat apparatus.
5. Significance and Use
5.1 This test method determines the setting time of grout mixed to the fluid consistency required for its use in PA concrete.
5.2 The time of setting is also useful in determining the acceptability of components of grout that must be mixed to the fluid
consistency required for production of PA concrete.
6. Apparatus
5.1
6.1 Vicat Apparatus, in accordance with Test Method C191.
5.2
1
This test method is under the jurisdiction of ASTM Committee C09 on Concrete and Concrete Aggregates and is the direct responsibility of Subcommittee C09.41 on
Concrete for Radiation Shielding.
Current edition approved Feb. 1, 2006. Published February 2006. Originally approved in 1981. Last previous edition approved in 1997 as C953–87(1997). DOI:
10.1520/C0953-06.on Hydraulic Cement Grouts.
Current edition approved June 15, 2010. Published July 2010. Originally approved in 1981. Last previous edition approved in 2006 as C953–06. DOI: 10.1520/C0953-10.
2
For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
*A Summary of Changes section appears at the end of this standard.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
C953–10
6.2 Moist Room, maintained in accordance with Specification C511.
6.
7. Test Sample
6.1The7.1 The test sample shall consist of at least 300 mL of grout taken from a freshly-mixed batch prepared in accordance
with Practice C938 obtained from a mixer at the laboratory or construction site.
7.
8. Procedure
7.1Warm8.1 Warm the Vicat conical ring and base plate to approximately 100 °C.
7.2Apply8.2 Apply a thin film of paraffin wax to the base of the conical ring and place the waxed conical ring on the base plate.
Place a weight on the conical ring to ensure intimate contact with the base plate and allow the conical ring and plate to cool to
room temperature.
7.3Fill8.3 Fill the conical ring apparatus with grout flush with its top within 2 min after completion of mixing. Stri
...