Fire detection and fire alarm systems - Part 29: Multi-sensor fire detectors - Point detectors using a combination of smoke and heat sensors

This European Standard EN 54-29 specifies requirements, test methods and performance criteria for point-type multi-sensor fire detectors for use in fire detection systems installed in buildings (see EN 54-1:1996), incorporating in one mechanical enclosure  at least one optical or ionization smoke sensor and at least one heat sensor. The overall fire detection performance is determined utilizing the combination of the detected phenomena.
Multi-sensor fire detectors having special characteristics suitable for the detection of specific fire risks are not covered by this standard. The performance requirements for any additional functions are beyond the scope of this standard (e.g. additional features or enhanced functionality for which this standard does not define a test or assessment method).
NOTE   Certain types of detector contain radioactive materials. The national requirements for radiation protection differ from country to country and they are not specified in this standard.

Brandmeldeanlagen - Teil 29: Mehrfachsensor-Brandmelder - Punktförmige Melder mit kombinierten Rauch- und Wärmesensoren

Diese Europäische Norm EN 54-29 legt Anforderungen, Prüfverfahren und Leistungsmerkmale für punkt-förmige Mehrfachsensor-Brandmelder fest, die in Brandmeldeanlagen für Gebäude eingesetzt werden (siehe EN 54 1:1996) und die in einem Gehäuse mindestens einen Rauchsensor nach dem Durchlicht- oder Ionisationsprinzip und mindestens einen Wärmesensor enthalten. Ihre Gesamtleistung bei der Brandmeldung ergibt sich aus der Kombination der detektierten Brandphänomene.
Mehrfachsensormelder mit speziellen Merkmalen, geeignet für besondere Brandrisiken, sind nicht Gegen-stand dieser Norm. Die Leistungsanforderungen an alle zusätzlichen Funktionen fallen nicht in den Anwen-dungsbereich dieser Norm (z. B. werden in dieser Norm für zusätzliche Merkmale oder für eine verbesserte Funktionstüchtigkeit keine Prüf  oder Bewertungsverfahren festgelegt).
ANMERKUNG   Einige Meldertypen enthalten radioaktive Stoffe. Die nationalen Anforderungen für den Schutz gegen ionisierende Strahlung sind in den Ländern unterschiedlich und werden deshalb in der vorliegenden Norm nicht festgelegt.

Systèmes de détection et d'alarme incendie - Partie 29 : Détecteurs d'incendie multicapteurs - Détecteurs ponctuels utilisant une combinaison de capteurs de fumée et de chaleur

La présente Norme européenne, EN 54-29, spécifie les exigences, les méthodes d'essai et les critères de performance pour les détecteurs d'incendie ponctuels multicapteurs destinés à être utilisés dans les systèmes de détection d'incendie installés dans les bâtiments (voir EN 54-1:1996), incorporant dans une seule enveloppe mécanique au moins un capteur de fumée optique ou à ionisation et au moins un capteur de chaleur. La performance globale de détection du feu est déterminée en utilisant la combinaison des phénomènes détectés.
Les détecteurs d'incendie multicapteurs possédant des caractéristiques particulières adaptées à la détection de risques d'incendie spécifiques ne sont pas pris en compte dans la présente norme. Les exigences de performance relatives à toute autre fonction ne relèvent pas du domaine d'application de la présente norme (par exemple, des caractéristiques supplémentaires ou une fonctionnalité améliorée pour lesquelles la présente norme ne définit pas d'essai ou de méthode d'évaluation).
NOTE   Certains types de détecteurs contiennent des matières radioactives. Les exigences nationales de radioprotection variant d'un pays à l'autre, celles-ci ne sont pas spécifiées dans la présente norme.

Sistemi za odkrivanje in javljanje požara ter alarmiranje - 29. del: Večsenzorski javljalniki  požara - Točkovni javljalniki s senzorjema za zaznavanje dima in toplote

General Information

Status
Not Published
Publication Date
21-Nov-2011
Withdrawal Date
21-May-2012
Current Stage
4598 - Decision to abandon - Finalization for Vote
Start Date
10-Feb-2012
Completion Date
10-Feb-2012

Buy Standard

Draft
prEN 54-29:2009
English language
82 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-december-2009
6LVWHPL]DRGNULYDQMHLQMDYOMDQMHSRåDUDWHUDODUPLUDQMHGHO9HþVHQ]RUVNL
MDYOMDOQLNLSRåDUD7RþNRYQLMDYOMDOQLNLVVHQ]RUMHPD]D]D]QDYDQMHGLPDLQWRSORWH
Fire detection and fire alarm systems - Part 29: Multi-sensor fire detectors - Point
detectors using a combination of smoke and heat sensors
Brandmeldeanlagen - Teil 29: Mehrfachsensor-Brandmelder - Punktförmige Melder mit
kombinierten Rauch- und Wärmesensoren
Ta slovenski standard je istoveten z: prEN 54-29
ICS:
13.220.20 3RåDUQD]DãþLWD Fire protection
13.320 Alarmni in opozorilni sistemi Alarm and warning systems
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD
DRAFT
prEN 54-29
NORME EUROPÉENNE
EUROPÄISCHE NORM
October 2009
ICS 13.220.20
English Version
Fire detection and fire alarm systems - Part 29: Multi-sensor fire
detectors - Point detectors using a combination of smoke and
heat sensors
Brandmeldeanlagen - Teil 29: Mehrfachsensor-
Brandmelder - Punktförmige Melder mit kombinierten
Rauch- und Wärmesensoren
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee CEN/TC 72.

If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the
same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to
provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and
shall not be referred to as a European Standard.

EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2009 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 54-29:2009: E
worldwide for CEN national Members.

prEN 54-29:2009 (E)
Contents Page
Foreword .6
Introduction .7
1 Scope .8
2 Normative references .8
3 Terms and definitions .9
4 Requirements .9
4.1 Compliance .9
4.2 Individual alarm indication . 10
4.3 Connection of ancillary devices . 10
4.4 Monitoring of detachable detectors . 10
4.5 Manufacturer's adjustments . 10
4.6 On-site adjustment of response behaviour . 10
4.7 Protection against the ingress of foreign bodies . 10
4.8 Response to slowly developing fires. 10
4.9 Position of the heat sensors . 11
4.10 Marking . 11
4.11 Data . 11
4.12 Additional requirements for software controlled detectors . 12
4.12.1 General . 12
4.12.2 Software documentation . 12
4.12.3 Software design . 13
4.12.4 The storage of programs and data. 13
5 Test methods . 13
5.1 General . 13
5.1.1 Atmospheric conditions for tests . 13
5.1.2 Operating conditions for tests . 13
5.1.3 Mounting arrangements . 14
5.1.4 Tolerances . 14
5.1.5 Measurement of smoke response value . 14
5.1.6 Measurement of heat response value . 15
5.1.7 Provision for tests . 15
5.1.8 Test schedule . 15
5.2 Repeatability of smoke response. 17
5.2.1 Object . 17
5.2.2 Test procedure . 17
5.2.3 Requirements . 17
5.3 Directional dependence of smoke response . 17
5.3.1 Object . 17
5.3.2 Test procedure . 17
5.3.3 Requirements . 17
5.4 Directional dependence of heat response . 18
5.4.1 Object of test . 18
5.4.2 Test procedure . 18
5.4.3 Requirements . 18
5.5 Lower limit of heat sensitivity . 18
5.5.1 Object of the test. 18
5.5.2 Test procedure . 18
5.5.3 Requirements . 18
5.6 Reproducibility of smoke response . 19
prEN 54-29:2009 (E)
5.6.1 Object . 19
5.6.2 Test procedure . 19
5.6.3 Requirements . 19
5.7 Reproducibility of heat response . 19
5.7.1 Object of the test . 19
5.7.2 Test procedure . 19
5.7.3 Requirements . 19
5.8 Variation in supply parameters . 19
5.8.1 Object . 19
5.8.2 Test procedure . 20
5.8.3 Requirements . 20
5.9 Air movement . 20
5.9.1 Object of test . 20
5.9.2 Test procedure . 20
5.9.3 Requirements . 20
5.10 Dazzling . 21
5.10.1 Object of test . 21
5.10.2 Test procedure . 21
5.10.3 Requirements . 21
5.11 Dry heat (operational) . 22
5.11.1 Object . 22
5.11.2 Test procedure . 22
5.11.3 Requirements . 22
5.12 Cold (operational) . 22
5.12.1 Object . 22
5.12.2 Test procedure . 22
5.12.3 Requirements .
...