Air conditioners, liquid chilling packages and heat pumps, with electrically driven compressors, for space heating and cooling, commercial and process cooling - Testing and rating at part load conditions and calculation of seasonal performance

This document is applicable to air conditioners, heat pumps and liquid chilling packages, including comfort and process chillers. It applies to factory made units defined in EN 14511-1, except single duct, double duct, control cabinet and close control units. It also covers direct exchange-to-water(brine) heat pumps (DX-to-water(brine)) as defined in EN 15879-1.
This document also applies to hybrid units as defined in this standard.
This document specifies the temperatures, part load conditions and the calculation methods for the determination of seasonal energy efficiency SEER and SEERon, seasonal space cooling energy efficiency ηs,c, seasonal coefficient of performance SCOP, SCOPon and SCOPnet, seasonal space heating energy efficiency ηs,h and seasonal energy performance ratio SEPR.
Such calculation methods can be based on calculated or measured values.
In case of measured values, this document specifies the test methods for determination of capacities, EER and COP values during active mode at part load conditions. It also establishes test methods for power input during thermostat-off mode, standby mode, off mode and crankcase heater mode.
NOTE 1   The word "unit" is used instead of the full terms of the products.
NOTE 2   The word "heating" is used to refer to space heating.

Luftkonditionierer, Flüssigkeitskühlsätze und Wärmepumpen mit elektrisch angetriebenen Verdichtern zur Raumbeheizung und -kühlung - Prüfung und Leistungsbemessung unter Teillastbedingungen und Berechnung der jahreszeitbedingten Leistungszahl

Dieses Dokument behandelt Luftkonditionierer, Wärmepumpen und Flüssigkeitskühlsätze, einschließlich Komfort- und Prozess-Kühler. Sie gilt für fabrikmäßig hergestellte Geräte nach EN 14511-1, mit Ausnahme von Einkanal-Luftkonditionierern, Zweikanal-Luftkonditionierern, Schaltschrank-Kühlgeräten und Verfahrens-Luftkonditionierern. Sie behandelt zudem Direktübertragung-Wasser/Sole-Wärmepumpen, wie sie in EN 15879-1 festgelegt sind.
Dieses Dokument gilt des Weiteren für Hybridgeräte, wie sie in dieser Norm definiert werden.
Dieses Dokument legt die Temperaturen und Teillastbedingungen fest sowie die Berechnungsverfahren zur Ermittlung der saisonalen Arbeitszahl im Kühlbetrieb SEER und SEERon, der jahreszeitbedingten Raumkühlungs-Energieeffizienz ηs,c der saisonalen Arbeitszahl im Heizbetrieb SCOP, SCOPon und SCOPnet, der jahreszeitbedingten Raumheizungs-Energieeffizienz ηs,h sowie der Jahres-Energieeffizienz SEPR.
Derartige Berechnungsverfahren können auf Rechen- oder Messwerten beruhen.
Im Fall von Messwerten legt dieses Dokument die Prüfverfahren zur Ermittlung von Leistungen, EER- und COP-Werten im Aktiv-Modus unter Teillastbedingungen fest. Außerdem bestimmt es Prüfverfahren zur Ermittlung der Leistungsaufnahme im Modus "Temperaturregler AUS", im Bereitschaftsmodus, im Modus "Aus" und im Modus mit Kurbelgehäuseheizung.
ANMERKUNG 1   Das Wort "Gerät" wird anstelle der vollständigen Produktbezeichnungen verwendet.
ANMERKUNG 2   Das Wort "Heizung" bezieht sich auf die Raumheizung.

Climatiseurs, groupes refroidisseurs de liquide et pompes à chaleur avec compresseur entraîné par moteur électrique pour le chauffage et la réfrigération des locaux - Essais et détermination des caractéristiques à charge partielle et calcul de performance saisonnière

Le présent document s’applique aux climatiseurs, les pompes à chaleur et les groupes refroidisseurs de liquide, y compris les refroidisseurs de confort et industriels. Il s'applique aux appareils fabriqués en usine définis dans l'EN 14511-1, excepté les appareils à simple et à double conduit, les appareils pour armoire de commande et les appareils pour enceinte contrôlée. Il couvre également les pompes à chaleur à échange direct avec l'eau(glycolée) (DX/eau(glycolée)) telles que définies dans l'EN 15879-1.
Le présent document s’applique également aux appareils hybrides tels que définis dans le présent document.
Le présent document spécifie les températures, les conditions de charge partielle et les méthodes de calcul permettant de déterminer l'efficacité énergétique saisonnière SEER et SEERon, l'efficacité énergétique saisonnière du refroidissement des locaux ηs,c, le coefficient de performance saisonnier SCOP, SCOPon et SCOPnet, l'efficacité énergétique saisonnière du chauffage des locaux ηs,h et le coefficient d'efficacité énergétique saisonnier SEPR.
Ces méthodes de calcul peuvent être fondées sur des valeurs mesurées ou calculées.
Dans le cas de valeurs mesurées, le présent document spécifie les méthodes d'essai relatives à la détermination des puissances et des valeurs d'EER et de COP pendant le mode actif, dans les conditions de charge partielle. Il établit également les méthodes d'essai relatives à la puissance absorbée en mode arrêt par thermostat, en mode veille, en mode arrêt et en mode dispositif de chauffage de carter.
NOTE 1   Le mot « appareil » est utilisé à la place des termes complets des produits.
NOTE 2   Le mot « chauffage » est utilisé pour la référence au chauffage des locaux.

Klimatske naprave, enote za hlajenje kapljevine ter toplotne črpalke za ogrevanje in hlajenje prostora z električnimi kompresorji, profesionalno in procesno hlajenje prostora - Preskušanje in ocenitev ob delni obremenitvi ter izračun letnega učinka

General Information

Status
Not Published
Current Stage

RELATIONS

Buy Standard

Draft
prEN 14825:2020 - BARVE na PDF-str 109,116,129
English language
142 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (sample)

SLOVENSKI STANDARD
oSIST prEN 14825:2020
01-oktober-2020

Klimatske naprave, enote za hlajenje kapljevine ter toplotne črpalke za ogrevanje

in hlajenje prostora z električnimi kompresorji - Preskušanje in ocenitev ob delni

obremenitvi ter izračun letnega učinka

Air conditioners, liquid chilling packages and heat pumps, with electrically driven

compressors, for space heating and cooling - Testing and rating at part load conditions

and calculation of seasonal performance
Luftkonditionierer, Flüssigkeitskühlsätze und Wärmepumpen mit elektrisch
angetriebenen Verdichtern zur Raumbeheizung und -kühlung - Prüfung und
Leistungsbemessung unter Teillastbedingungen und Berechnung der
jahreszeitbedingten Leistungszahl

Climatiseurs, groupes refroidisseurs de liquide et pompes à chaleur avec compresseur

entraîné par moteur électrique pour le chauffage et la réfrigération des locaux - Essais et

détermination des caractéristiques à charge partielle et calcul de performance
Ta slovenski standard je istoveten z: prEN 14825
ICS:
23.120 Zračniki. Vetrniki. Klimatske Ventilators. Fans. Air-
naprave conditioners
27.080 Toplotne črpalke Heat pumps
91.140.30 Prezračevalni in klimatski Ventilation and air-
sistemi conditioning systems
oSIST prEN 14825:2020 en,fr,de

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
oSIST prEN 14825:2020
---------------------- Page: 2 ----------------------
oSIST prEN 14825:2020
DRAFT
EUROPEAN STANDARD
prEN 14825
NORME EUROPÉENNE
EUROPÄISCHE NORM
October 2020
ICS 27.080; 91.140.30 Will supersede EN 14825:2018
English Version
Air conditioners, liquid chilling packages and heat pumps,
with electrically driven compressors, for space heating and
cooling - Testing and rating at part load conditions and
calculation of seasonal performance

Climatiseurs, groupes refroidisseurs de liquide et Luftkonditionierer, Flüssigkeitskühlsätze und

pompes à chaleur avec compresseur entraîné par Wärmepumpen mit elektrisch angetriebenen

moteur électrique pour le chauffage et la réfrigération Verdichtern zur Raumbeheizung und -kühlung -

des locaux - Essais et détermination des Prüfung und Leistungsbemessung unter

caractéristiques à charge partielle et calcul de Teillastbedingungen und Berechnung der

performance jahreszeitbedingten Leistungszahl

This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee

CEN/TC 113.

If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations

which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other

language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC

Management Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,

Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,

Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and

United Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are

aware and to provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without

notice and shall not be referred to as a European Standard.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels

© 2020 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 14825:2020 E

worldwide for CEN national Members.
---------------------- Page: 3 ----------------------
oSIST prEN 14825:2020
prEN 14825:2020 (E)
Contents
Page

European foreword ....................................................................................................................................................... 7

Introduction .................................................................................................................................................................... 9

1 Scope ................................................................................................................................................................. 10

2 Normative references ................................................................................................................................. 10

3 Terms, definitions, symbols, abbreviated terms and units .......................................................... 11

3.1 Terms and definitions ................................................................................................................................ 11

3.2 Symbols, abbreviated terms and units ................................................................................................. 24

4 Part load conditions for space cooling ................................................................................................. 28

4.1 General ............................................................................................................................................................. 28

4.2 Air-to-air units .............................................................................................................................................. 28

4.3 Water(brine)-to-air units .......................................................................................................................... 29

4.4 Air-to-water(brine) units .......................................................................................................................... 29

4.5 Water(brine)-to-water(brine) units ..................................................................................................... 30

5 Calculation methods for seasonal space cooling efficiency η , SEER and SEER ................. 31

s,c on

5.1 General ............................................................................................................................................................. 31

5.2 Calculation of the seasonal space cooling efficiency η ................................................................ 31

s,c

5.3 General formula for calculation of SEER .............................................................................................. 32

5.4 Calculation of the reference annual cooling demand Q ................................................................ 32

5.5 Calculation of the reference annual energy consumption for space cooling Q .................. 32

5.6 Calculation of SEER ................................................................................................................................... 33

5.7 Calculation procedure for determination of EERbin values at part load conditions A,

B, C, D ................................................................................................................................................................ 34

5.7.1 General ............................................................................................................................................................. 34

5.7.2 Calculation procedure for fixed capacity units ................................................................................. 34

5.7.3 Calculation procedure for staged and variable capacity units .................................................... 35

6 Part load conditions for space heating ................................................................................................. 35

6.1 General ............................................................................................................................................................. 35

6.2 Air-to-air units .............................................................................................................................................. 36

6.3 Water(brine)-to-air-units ......................................................................................................................... 37

6.4 Air-to-water(brine) units .......................................................................................................................... 38

6.4.1 General ............................................................................................................................................................. 38

6.4.2 Low temperature application .................................................................................................................. 38

6.4.3 Intermediate temperature application ................................................................................................ 39

6.4.4 Medium temperature application .......................................................................................................... 40

6.4.5 High temperature application ................................................................................................................. 41

6.5 DX-to-water(brine) and water(brine)-to-water(brine) units ..................................................... 42

6.5.1 General ............................................................................................................................................................. 42

6.5.2 Low temperature application .................................................................................................................. 42

6.5.3 Intermediate temperature application ................................................................................................ 43

6.5.4 Medium temperature application .......................................................................................................... 44

6.5.5 High temperature application ................................................................................................................. 45

7 Calculation methods for seasonal space heating efficiency η , SCOP, SCOP and
s,h on

SCOP of heat pumps ................................................................................................................................. 46

net
---------------------- Page: 4 ----------------------
oSIST prEN 14825:2020
prEN 14825:2020 (E)

7.1 General ............................................................................................................................................................. 46

7.2 Calculation of the seasonal space heating efficiency η ................................................................ 46

s,h

7.3 General formula for calculation of SCOP .............................................................................................. 47

7.4 Calculation of the reference annual heating demand Q ................................................................ 47

7.5 Calculation of the annual energy consumption for heating Q ................................................... 48

7.6 Calculation of SCOP and SCOP ............................................................................................................ 48

on net

7.7 Calculation procedure for determination of COP values at part load conditions A to

bin

G .......................................................................................................................................................................... 50

7.7.1 General ............................................................................................................................................................. 50

7.7.2 Calculation procedure for fixed capacity units .................................................................................. 50

7.7.3 Calculation procedure for staged and variable capacity units ..................................................... 51

8 Test methods for hybrid units ................................................................................................................. 51

8.1 General ............................................................................................................................................................. 51

8.2 Separated method ........................................................................................................................................ 52

8.2.1 General ............................................................................................................................................................. 52

8.2.2 Heat pump testing ........................................................................................................................................ 52

8.2.3 Boiler testing .................................................................................................................................................. 52

8.2.4 Energy efficiency and seasonal coefficient of performance calculations ................................. 52

8.3 Combined test method ................................................................................................................................ 54

8.3.1 General ............................................................................................................................................................. 54

8.3.2 Test conditions .............................................................................................................................................. 54

8.3.3 Test installation ............................................................................................................................................ 54

8.3.4 Calculation of gas input .............................................................................................................................. 54

8.3.5 Calculation of liquid fuel input ................................................................................................................ 55

8.3.6 Calculation of annual fossil fuel consumption ................................................................................... 55

8.3.7 Energy efficiency and seasonal coefficient of performance calculations ................................. 56

9 Part load conditions for process cooling .............................................................................................. 58

10 Calculation method for SEPR .................................................................................................................... 59

10.1 General formula for calculation of SEPR .............................................................................................. 59

10.2 Calculation procedure for determination of EER values at part load conditions A, B,

bin

C, D ...................................................................................................................................................................... 60

10.2.1 General ............................................................................................................................................................. 60

10.2.2 Calculation procedure for fixed capacity process chillers ............................................................. 61

10.2.3 Calculation procedure for variable capacity process chillers ...................................................... 61

11 Test methods for testing capacities, EER and COP values during active mode at
bin bin

part load conditions ..................................................................................................................................... 61

11.1 General ............................................................................................................................................................. 61

11.2 Refrigerant piping ........................................................................................................................................ 62

11.3 Basic principles ............................................................................................................................................. 62

11.4 Uncertainties of measurement ................................................................................................................ 64

11.5 Test procedures for units with fixed capacity .................................................................................... 65

11.5.1 General ............................................................................................................................................................. 65

11.5.2 Air-to-air and water(brine)-to-air units – Determination of the degradation

coefficient Cd .................................................................................................................................................. 66

11.5.3 Air-to-water(brine), water(brine)-to-water(brine) and DX-to-water(brine) units –

Determination of the degradation coefficient Cd .............................................................................. 68

11.6 Test procedure for staged and variable capacity units ................................................................... 69

11.6.1 General ............................................................................................................................................................. 69

11.6.2 Settings for the required capacity ratio ................................................................................................ 69

11.6.3 Compensation method ................................................................................................................................ 69

---------------------- Page: 5 ----------------------
oSIST prEN 14825:2020
prEN 14825:2020 (E)

12 Test methods for electric power input during thermostat-off mode, standby mode

and crankcase heater mode and off mode .......................................................................................... 69

12.1 Uncertainties of measurement ................................................................................................................ 69

12.2 Measurement of electric power input during thermostat-off mode ......................................... 70

12.3 Measurement of the electric power input during standby mode ............................................... 70

12.4 Measurement of the electric power input during crankcase heater mode ............................. 70

12.5 Measurement of the electric power input during off mode .......................................................... 71

13 Test report ...................................................................................................................................................... 71

14 Technical documentation .......................................................................................................................... 71

15 Testing and rating of individual indoor units .................................................................................... 71

Annex A (normative) Applicable climate bins and hours for air conditioners with rated

capacity of ≤ 12 kW for cooling, or heating if the product has no cooling function ............. 72

A.1 Climate bins .................................................................................................................................................... 72

A.1.1 Bin limit temperature ................................................................................................................................. 72

A.1.2 Cooling.............................................................................................................................................................. 72

A.1.3 Heating ............................................................................................................................................................. 73

A.2 Hours for active mode, thermostat-off, standby, off mode ........................................................... 75

A.2.1 Cooling.............................................................................................................................................................. 75

A.2.2 Heating ............................................................................................................................................................. 75

A.3 Hours used for crankcase heater mode ............................................................................................... 75

A.3.1 Cooling.............................................................................................................................................................. 75

A.3.2 Heating ............................................................................................................................................................. 76

Annex B (normative) Applicable climate bins and hours for air/water(brine)/DX-to-

water(brine) heat pumps with a rated heat output ≤ 400 kW .................................................... 77

B.1 Climate bins .................................................................................................................................................... 77

B.1.1 Bin limit temperature ................................................................................................................................. 77

B.1.2 Heating ............................................................................................................................................................. 77

B.2 Hours for active, thermostat-off, standby and off modes – Heating .......................................... 79

B.3 Hours used for crankcase heater mode – Heating............................................................................ 79

Annex C (normative) Applicable climate bins and hours for process chillers .................................... 80

C.1 Climate bins .................................................................................................................................................... 80

Annex D (normative) Applicable climate bins and hours for air-to-air units > 12 kW,

water(brine)-to-air units and comfort chillers ................................................................................. 84

D.1 Climate bins .................................................................................................................................................... 84

D.1.1 Bin limit temperature ................................................................................................................................. 84

D.1.2 Cooling.............................................................................................................................................................. 84

D.1.3 Heating ............................................................................................................................................................. 85

D.2 Hours for active, thermostat-off, standby and off modes .............................................................. 87

D.2.1 Cooling.............................................................................................................................................................. 87

---------------------- Page: 6 ----------------------
oSIST prEN 14825:2020
prEN 14825:2020 (E)

D.2.2 Heating ............................................................................................................................................................. 87

D.3 Hours used for crankcase heater mode ................................................................................................ 87

D.3.1 Cooling .............................................................................................................................................................. 87

D.3.2 Heating ............................................................................................................................................................. 87

Annex E (normative) Templates for technical documentation ................................................................. 88

E.1 General ............................................................................................................................................................. 88

E.2 Air-to-air units ≤ 12 kW .............................................................................................................................. 88

E.3 Space heaters: air-to-water(brine), water(brine)-to-water(brine) and DX-to-

water(brine) units ≤ 400 kW .................................................................................................................... 92

E.4 Hybrid units .................................................................................................................................................... 94

E.5 Process Chillers ............................................................................................................................................. 96

E.6 Comfort chillers, air-to-air (>12 kW) and water(brine)-to-air air conditioners not

exceeding 2 MW ............................................................................................................................................. 97

E.7 Air-to-air and water(brine)-to-air heat pumps not exceeding 1 MW ........................................ 98

Annex F (informative) Determination of water(brine) temperature for fixed capacity units

with variable outlet temperature ........................................................................................................ 100

F.1 General .......................................................................................................................................................... 100

F.2 Test procedure for an air-to-water unit with fixed water flow rate ....................................... 100

F.3 Test procedure for an air-to-water unit with variable water flow rate ................................. 101

Annex G (informative) Calculation example for SEER and SEER – Application to a

reversible air-to-air unit with variable capacity ............................................................................ 103

G.1 Calculation of SEER ................................................................................................................................. 103

G.2 Calculation of SEER .................................................................................................................................... 105

G.2.1 Calculation of reference annual cooling demand (Q ) according to Formula (3) .............. 105

G.2.2 Calculation of SEER according to Formula (6) ................................................................................. 105

Annex H (informative) Calculation example for SCOP and SCOP – Application to a fixed

on net

capacity air-to-water(brine) heat pump used for low temperature application ............... 106

Annex I (informative) Calculation example for SCOP and SCOP – Application to a fixed

on net
capacity brine-to-water(brine) heat pump used for medium temperature

application ................................................................................................................................................... 112

Annex J (informative) Calculation examples for SCOP for hybrid units ........................................... 119

J.1 Calculation example for SCOP for variable speed hybrid unit based on heat pump

and boiler separated tests ...................................................................................................................... 119

J.2 Calculation example for SCOP for hybrid unit using combined test method .................... 121

Annex K (informative) Calculation example for SEPR – Application to a process chiller with

staged capacity ........................................................................................................................................... 124

K.1 Rating performance .................................................................................................................................. 124

Annex L (informative) Compensation methods for air-to-water(brine) and water(brine)-to-

water(brine) units ..................................................................................................................................... 127

---------------------- Page: 7 ----------------------
oSIST prEN 14825:2020
prEN 14825:2020 (E)

L.1 General ........................................................................................................................................................... 127

L.2 Compensation system for reduced capacity test in cooling mode ........................................... 127

L.3 Compensation system for reduced capacity test in heating mode ........................................... 127

Annex M (normative) Rating of outdoor units of multi-split air conditioners and heat

pumps ............................................................................................................................................................. 129

M.1 General ......................................................................

...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.