Air conditioners, liquid chilling packages and heat pumps for space heating and cooling and process chillers, with electrically driven compressors - Part 2: Test conditions

1.1   The scope of FprEN 14511-1:2022 is applicable.
1.2   This document specifies the test conditions for the rating of air conditioners, liquid chilling packages and heat pumps, using either, air, water or brine as heat transfer media, with electrically driven compressors when used for space heating and/or cooling. The document also specifies the test conditions for the rating of air-cooled and water(brine)-cooled process chillers.
1.3   This document specifies the conditions for which performance data are to be declared for single duct and double duct units for compliance to the Ecodesign Regulation 206/2012 and Energy Labelling Regulation 626/2011.

Luftkonditionierer, Flüssigkeitskühlsätze und Wärmepumpen für die Raumbeheizung und -kühlung und Prozess-Kühler mit elektrisch angetriebenen Verdichtern - Teil 2: Prüfbedingungen

1.1   Es gilt der Anwendungsbereich von FprEN 14511-1:2022.
1.2   Dieses Dokument legt die Bedingungen für die Leistungsprüfung von Luftkonditionierern, Flüssigkeits-kühlsätzen und Wärmepumpen, die entweder Luft, Wasser oder Sole als Wärmeträger nutzen, mit elektrisch angetriebenen Verdichtern für die Raumbeheizung und/oder -kühlung fest. Das Dokument legt auch die Bedingungen für die Leistungsprüfung von luftgekühlten und von wasser(sole-)gekühlten Prozess-Kühlern fest.
1.3   Dieses Dokument legt die Bedingungen fest, für die die leistungsbezogenen Daten zu Einkanal- und Zweikanal-Geräten zum Zwecke der Übereinstimmung mit der Ökodesign-Verordnung 206/2012 und der Verordnung 626/2011 zur Energieverbrauchskennzeichnung angegeben werden müssen.

Climatiseurs, groupes refroidisseurs de liquide et pompes à chaleur pour le chauffage et le refroidissement des locaux et refroidisseurs industriels avec compresseur entraîné par moteur électrique - Partie 2 : Conditions d'essai

1.1   Le domaine d'application du FprEN 14511-1:2022 est applicable.
1.2   Le présent document spécifie les conditions d'essai pour la détermination des caractéristiques et des performances des climatiseurs, groupes refroidisseurs de liquide et pompes à chaleur utilisant l’air, l’eau ou l’eau glycolée comme fluide caloporteur avec compresseur entraîné par moteur électrique, lorsqu'ils sont utilisés pour le chauffage et/ou le refroidissement des locaux. Le présent document spécifie également les conditions d’essai pour la détermination des refroidisseurs industriels à condensation par eau(glycolée) ou par air.
1.3   Le présent document spécifie les conditions pour lesquelles les données de performance sont déclarées pour les appareils à simple ou double raccordement pour la conformité au Règlement Ecoconception 206/2012 et au Règlement Etiquetage énergétique 626/2011.

Klimatske naprave, enote za hlajenje kapljevine, toplotne črpalke za ogrevanje in hlajenje prostora ter procesne hladilne naprave z električnimi kompresorji - 2. del: Preskusni pogoji

General Information

Status
Not Published
Current Stage
5060 - Closure of Vote - Formal Approval
Due Date
18-Oct-2021

RELATIONS

Buy Standard

Draft
prEN 14511-2:2021
English language
21 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (sample)

SLOVENSKI STANDARD
oSIST prEN 14511-2:2021
01-april-2021

Klimatske naprave, enote za hlajenje kapljevine, toplotne črpalke za ogrevanje in

hlajenje prostora ter procesne hladilne naprave z električnimi kompresorji - 2. del:

Preskusni pogoji

Air conditioners, liquid chilling packages and heat pumps for space heating and cooling

and process chillers, with electrically driven compressors - Part 2: Test conditions

Luftkonditionierer, Flüssigkeitskühlsätze und Wärmepumpen für die Raumbeheizung und

-kühlung und Prozess-Kühler mit elektrisch angetriebenen Verdichtern - Teil 2:
Prüfbedingungen

Climatiseurs, groupes refroidisseurs de liquide et pompes à chaleur pour le chauffage et

le refroidissement des locaux et refroidisseurs industriels avec compresseur entraîné par

moteur électrique - Partie 2 : Conditions d'essai
Ta slovenski standard je istoveten z: prEN 14511-2
ICS:
23.120 Zračniki. Vetrniki. Klimatske Ventilators. Fans. Air-
naprave conditioners
27.080 Toplotne črpalke Heat pumps
91.140.30 Prezračevalni in klimatski Ventilation and air-
sistemi conditioning systems
oSIST prEN 14511-2:2021 en,fr,de

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
oSIST prEN 14511-2:2021
---------------------- Page: 2 ----------------------
oSIST prEN 14511-2:2021
DRAFT
EUROPEAN STANDARD
prEN 14511-2
NORME EUROPÉENNE
EUROPÄISCHE NORM
March 2021
ICS Will supersede EN 14511-2:2018
English Version
Air conditioners, liquid chilling packages and heat pumps
for space heating and cooling and process chillers, with
electrically driven compressors - Part 2: Test conditions

Climatiseurs, groupes refroidisseurs de liquide et Luftkonditionierer, Flüssigkeitskühlsätze und

pompes à chaleur pour le chauffage et le Wärmepumpen für die Raumbeheizung und -kühlung

refroidissement des locaux et refroidisseurs industriels und Prozess-Kühler mit elektrisch angetriebenen

avec compresseur entraîné par moteur électrique - Verdichtern - Teil 2: Prüfbedingungen

Partie 2 : Conditions d'essai

This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee

CEN/TC 113.

If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations

which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other

language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC

Management Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,

Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,

Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and

United Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are

aware and to provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without

notice and shall not be referred to as a European Standard.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels

© 2021 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 14511-2:2021 E

worldwide for CEN national Members.
---------------------- Page: 3 ----------------------
oSIST prEN 14511-2:2021
prEN 14511-2:2021 (E)
Contents

European foreword ....................................................................................................................................................... 3

1 Scope .................................................................................................................................................................... 4

2 Normative references .................................................................................................................................... 4

3 Terms and definitions ................................................................................................................................... 4

4 Test conditions ................................................................................................................................................. 4

4.1 Environmental conditions and electrical power supply requirements ...................................... 4

4.2 Rating conditions ............................................................................................................................................ 6

Annex ZA (informative) Relationship between this European Standard and the ecodesign

requirements of Commission Regulation (EU) No 2015/1095 aimed to be covered .......... 20

Bibliography ................................................................................................................................................................. 21

---------------------- Page: 4 ----------------------
oSIST prEN 14511-2:2021
prEN 14511-2:2021 (E)
European foreword

This document (prEN 14511-2:2021) has been prepared by Technical Committee CEN/TC 113 “Heat

pumps and air conditioning units”, the secretariat of which is held by UNE.
This document is currently submitted to the Enquiry.
This document will supersede EN 14511-2:2018.
This document has been prepared in the frame of:

— the Commission Regulation (EU) No 206/2012 implementing Directive 2009/125/EC with regard to

ecodesign requirements for air conditioners;

— the Commission Regulation (EU) n° 626/2011 supplementing Directive 2010/30/EU with regard to

energy labelling for air conditioners;

— the Commission Regulation (EU) No 813/2013 implementing Directive 2009/125/EC with regard to

ecodesign requirements for air-to-water and water-to-water heat pump space heaters;

— the Commission Regulation (EU) n° 811/2013 supplementing Directive 2010/30/EU with regard to

energy labelling for air-to-water and water-to-water heat pump space heaters;

— the Commission Regulation (EU) n° 2015/1095 implementing Directive 2009/125/EC of the

European Parliament and of the Council with regard to ecodesign requirements for process chillers;

— Commission Regulation (EU) 2016/2281 implementing Directive 2009/125/EC of the European

Parliament and of the Council with regard to ecodesign requirements for air heating products,

cooling products, high temperature process chillers and fan coil units.

EN 14511, Air conditioners, liquid chilling packages and heat pumps for space heating and cooling and

process chillers, with electrically driven compressors currently comprises the following parts:

— Part 1: Terms and definitions
— Part 2: Test conditions
— Part 3: Test methods
— Part 4: Requirements

This document has been prepared under a mandate given to CEN by the European Commission and the

European Free Trade Association, and supports essential requirements of EU Directive(s).

For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this

document.
---------------------- Page: 5 ----------------------
oSIST prEN 14511-2:2021
prEN 14511-2:2021 (E)
1 Scope
1.1 The scope of prEN 14511-1:2021 is applicable.

1.2 This document specifies the test conditions for the rating of air conditioners, liquid chilling

packages and heat pumps, using either, air, water or brine as heat transfer media, with electrically driven

compressors when used for space heating and/or cooling. The document also specifies the test conditions

for the rating of air-cooled and water(brine)-cooled process chillers.

1.3 This document specifies the conditions for which performance data are to be declared for single

duct and double duct units for compliance to the Ecodesign Regulation 206/2012 and Energy Labelling

Regulation 626/2011.
2 Normative references

The following documents are referred to in the text in such a way that some or all of their content

constitutes requirements of this document. For dated references, only the edition cited applies. For

undated references, the latest edition of the referenced document (including any amendments) applies.

prEN 14511-1:2021, Air conditioners, liquid chilling packages and heat pumps for space heating and

cooling and process chillers with electrically driven compressors — Part 1: Terms and definitions

prEN 14511-4:2021, Air conditioners, liquid chilling packages and heat pumps for space heating and

cooling and process chillers, with electrically driven compressors — Part 4: Requirements

EN 15218:2013, Air conditioners and liquid chilling packages with evaporatively cooled condenser and with

electrically driven compressors for space cooling - Terms, definitions, test conditions, test methods and

requirements
3 Terms and definitions

For the purposes of this document, the terms and definitions given in prEN 14511-1:2021 apply.

ISO and IEC maintain terminological databases for use in standardization at the following addresses:

— IEC Electropedia: available at http://www.electropedia.org/
— ISO Online browsing platform: available at http://www.iso.org/obp
4 Test conditions
4.1 Environmental conditions and electrical power supply requirements

The tests shall be carried out under the environmental conditions specified in Table 1 or Table 2

depending on the location of the unit.

For all units, electrical power voltage and frequency shall be given by the manufacturer.

---------------------- Page: 6 ----------------------
oSIST prEN 14511-2:2021
prEN 14511-2:2021 (E)
Table 1 — Environmental conditions for units designed for installation indoors
Type Measured quantities Rating test
Water(brine)-to-water(brine) units Dry bulb temperature 15 °C to 30 °C
Air-to-water(brine) units with duct
connection on the air inlet and outlet Dry bulb temperature 15 °C to 30 °C
side
Dry bulb temperature
Air-to-water(brine) units without duct
15 °C to 30 °C
connection on the air inlet side
Wet bulb temperature
Water(brine)-to-air units with duct
connection on the air inlet and outlet Dry bulb temperature 15 °C to 30 °C
side
Water(brine)-to-air units without duct
Dry bulb temperature
Inlet temperature (see
connection on the air inlet and outlet
Table 5 or Table 6)
Wet bulb temperature
side
Air-to-air units with duct connection
Dry bulb temperature 15 °C to 30 °C
on the outdoor air inlet and outlet side
Dry bulb temperature
Air-to-air units without duct connection As inlet temperature (see
on the outdoor air inlet and outlet side Table 3 or Table 4)
Wet bulb temperature
Air-cooled process chillers ducted on the
Dry bulb temperature 15 °C to 30 °C
air side
Water(brine)-cooled process chillers Dry bulb temperature 15 °C to 30 °C
Table 2 — Environmental conditions for units designed for installation outdoors
Type Measured quantities Rating test
Dry bulb temperature
Inlet temperature (see
Air-to-water(brine) units
Tables 12 to 16)
Wet bulb temperature
Dry bulb temperature
Water(brine)-to-air units without duct Inlet temperature (see
connection on the air inlet side Table 5 and Table 6)
Wet bulb temperature
Water(brine)-to-water(brine) units
Dry bulb temperature 15 °C to 30 °C
operating in cooling mode
Water(brine)-to-water(brine) units
Dry bulb temperature 0 °C to 7 °C
operating in heating mode
Dry bulb temperature
Air-to-air units with duct connection on Inlet temperature (see
the indoor air inlet and outlet side Table 3 and Table 4)
Wet bulb temperature
Dry bulb temperature
Air-cooled process chillers (non-ducted Inlet temperature (see
on the air side) Table 25)
Wet bulb temperature
Water(brine)-cooled process chillers Dry bulb temperature 15 °C to 30 °C
---------------------- Page: 7 ----------------------
oSIST prEN 14511-2:2021
prEN 14511-2:2021 (E)
4.2 Rating conditions

For the rating tests, the appropriate test conditions shall be applied in accordance with:

— Table 3 for air-to-air units in heating mode;
— Table 4 for air-to-air units in cooling mode;
— Table 5 for water(brine)-to-air units in heating mode;
— Table 6 for water(brine)-to-air units in cooling mode;

— Tables 7 to 10 for water(brine)-to-water(brine) units in heating mode, depending on the

temperature applications;
— Table 11 for water(brine)-to-water(brine) units in cooling mode;

— Tables 12 to 15 for air-to-water(brine) in heating mode, depending on the temperature applications;

— Table 16 for air-to-water(brine) units in cooling mode;
— Table 17 for liquid chilling packages with remote condenser;
— Table 18 for liquid chilling packages for heat recovery condenser;

— Table 19 for air-cooled multisplit systems and modular air-cooled multisplit systems in the heating

mode;

— Table 20 for air-cooled multisplit systems and modular air-cooled multisplit systems in the cooling

mode;
— Table 21 for modular heat recovery air-cooled multisplit systems;

— Table 22 for water-cooled multisplit systems and modular water-cooled multisplit systems in the

heating mode;

— Table 23 for water-cooled multisplit systems and modular water-cooled multisplit systems in the

cooling mode;
— Table 24 for modular heat recovery water-cooled multisplit systems.
— Table 25 for process chillers

For units with brine, the test shall be carried out with the brine specified by the manufacturer,

see prEN 14511-4:2021, 7.2.1.

For air-to-water(brine), and water(brine)-to-water(brine) heat pumps, the manufacturer may declare

the water(brine) temperatures levels (low, intermediate, medium, and high) applicable to the heating

mode.

NOTE For comparison purposes between reverse cycle and non-reverse cycle units, the conditions on the

water(brine) side are given by the inlet and outlet water(brine) temperatures, possibly leading to different

water(brine) flow rates in heating and cooling modes.
---------------------- Page: 8 ----------------------
oSIST prEN 14511-2:2021
prEN 14511-2:2021 (E)

The rating tests in heating mode also apply for units having evaporatively cooled condenser, which

performance in cooling mode is determined in accordance with EN 15218:2013, and which can operate

in heating mode.

The standard rating conditions, extracted from Table 3 for heating mode, shall be used to determine the

rated capacity (P ), the rated power input (P ), the rated coefficient of performance (COP ) and the

rated COP rated
electricity consumption (Q , Q ) in heating mode.
DD SD
Table 3 — Air-to-air units - Heating mode
Outdoor heat exchanger Indoor heat exchanger
Inlet dry Inlet wet Inlet dry Inlet wet
bulb bulb bulb bulb
temperature temperature temperature temperature
°C °C °C °C
Outdoor air / recycled
7 6 20 15 max
air
Standard rating Exhaust air / recycled
20 12 20 12
conditions air
Exhaust air / outdoor
20 12 7 6
air
Outdoor air / recycled
2 1 20 15 max.
air
Outdoor air / recycled
- 7 - 8 20 15 max.
air
Outdoor air / recycled
- 15 — 20 15 max.
Application a
air
rating
Outdoor air / recycled
conditions
12 11 20 15 max.
air
Exhaust air / outdoor
20 12 2 1
air
Exhaust air / outdoor
20 12 - 7 - 8
air
For example, window, double duct, split units
For example, single duct units
---------------------- Page: 9 ----------------------
oSIST prEN 14511-2:2021
prEN 14511-2:2021 (E)
Table 4 — Air-to-air units - Cooling mode
Outdoor heat exchanger Indoor heat exchanger
Inlet dry Inlet wet Inlet dry Inlet wet
bulb bulb bulb bulb
temperature temperature temperature temperature
°C °C °C °C
Outdoor air / recycled
35 24 27 19
air
Exhaust air / recycled
27 19 27 19
air
Standard rating
Exhaust air / outdoor
27 19 35 24
conditions
air
c, d
Single duct 35 24 35 24
Control cabinet 35 24 35 24
Close control 35 24 24 17
Outdoor air / recycled
27 19 21 15
air
c, d
Single duct 27 19 27 19
Application
rating Outdoor air / recycled
46 24 29 19
conditions air
Control cabinet 50 30 35 24
Close control 27 19 21 15
For example, window, double duct, split units

The wet bulb temperature condition is not required when testing units which do not evaporate condensate.

When using the calorimeter room method, pressure equilibrium between indoor and outdoor compartments

shall be obtained by introducing into indoor compartment, air at the same rating temperature conditions.

The pressure difference between the two compartments of the calorimeter room shall not be greater than

1,25 Pa. This pressure equilibrium can be achieved by using an equalizing device or by creating an open space

area in the separation partition wall, which dimensions shall be calculated for the maximum airflow of the unit

to be tested. If an open space is created in the partition wall, an air sampling device or several temperature

sensors shall be used to measure the temperature of the air from the outdoor compartment to the indoor

compartment.
---------------------- Page: 10 ----------------------
oSIST prEN 14511-2:2021
prEN 14511-2:2021 (E)
Table 5 — Water(brine)-to-air units - Heating mode
Outdoor heat exchanger Inlet heat exchanger
Inlet Outlet Inlet dry Inlet wet
temperature temperature bulb bulb
temperature temperature
°C °C °C °C
Water 10 7 20 15 max.
Standard rating
Brine 0 −3 20 15 max.
conditions
Water loop 20 17 20 15 max.
b c
Water(brine) 15 35
b c
Brine 10 35
Application
rating conditions
b c
Water(brine) 5 35
b c
Brine −5 35

The term “water” includes indifferently water from a river or a lake, ground water.

The test is performed with the fixed flow rate or with the ΔT obtained during the test at the corresponding

standard rating conditions for units with variable flow rate. If the resulting flow rate is below the minimum flow

rate then this minimum is used with the inlet temperature.
Table 6 — Water(brine)-to-air units - Cooling mode
Outdoor heat exchanger Indoor heat exchanger
Inlet Outlet Inlet dry Inlet wet
temperature temperature bulb bulb
temperature temperature
°C °C °C °C
Cooling tower or wate
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.