Heat exchangers - Refrigerant cooled liquid coolers - Test pocedure for establishing the performance

UAP of 4 months (TC Res 146d/1998) (CC/001115)
2020-01-20: Originator of XML version: NEN (on behalf of NEN, ASI, DS, SFS, SIS, SN)

Wärmeaustauscher - Kältemittelgekühlte Flüssigkeitskühler - Prüfverfahren zur Leistungsfeststellung

Echangeurs thermiques - Refroidisseurs de liquides - Procédures d'essai pour la détermination de la performance

Prenosniki toplote – Hladilniki tekočin, hlajeni s hladivom – Postopki preskušanja za ugotavljanje tehničnih karakteristik - Dopolnilo A1

General Information

Status
Published
Publication Date
22-Oct-2002
Withdrawal Date
29-Apr-2003
Current Stage
6060 - Definitive text made available (DAV) - Publishing
Start Date
23-Oct-2002
Completion Date
23-Oct-2002

Relations

Buy Standard

Amendment
EN 1118:1999/A1:2004
English language
4 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 1118:1999/A1:2004
01-januar-2004
3UHQRVQLNLWRSORWH±+ODGLOQLNLWHNRþLQKODMHQLVKODGLYRP±3RVWRSNLSUHVNXãDQMD
]DXJRWDYOMDQMHWHKQLþQLKNDUDNWHULVWLN'RSROQLOR$
Heat exchangers - Refrigerant cooled liquid coolers - Test pocedure for establishing the
performance
Wärmeaustauscher - Kältemittelgekühlte Flüssigkeitskühler - Prüfverfahren zur
Leistungsfeststellung
Echangeurs thermiques - Refroidisseurs de liquides - Procédures d'essai pour la
détermination de la performance
Ta slovenski standard je istoveten z: EN 1118:1998/A1:2002
ICS:
27.060.30 Grelniki vode in prenosniki Boilers and heat exchangers
toplote
27.200 Hladilna tehnologija Refrigerating technology
SIST EN 1118:1999/A1:2004 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 1118:1999/A1:2004

---------------------- Page: 2 ----------------------

SIST EN 1118:1999/A1:2004
EUROPEAN STANDARD
EN 1118:1998/A1
NORME EUROPÉENNE
EUROPÄISCHE NORM
October 2002
ICS 27.060.30; 27.200
English version
Heat exchangers - Refrigerant cooled liquid coolers - Test
pocedure for establishing the performance
Echangeurs thermiques - Refroidisseurs de liquides - Wärmeaustauscher - Kältemittelgekühlte Flüssigkeitskühler
Procédures d'essai pour la détermination de la - Prüfverfahren zur Leistungsfeststellung
performance
This amendment A1 modifies the European Standard EN 1118:1998; it was approved by CEN on 14 September 2002.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for inclusion of this
amendment into the relevant national standard without any alteration. Up-to-date lists and bibliographical references concerning such
national standards may be obtained on application to the Management Centre or to any CEN member.
This amendment exists in three official versions (English, French, German). A version in any other language made by translation under the
responsibility of a CEN member into its own language and notified to the Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece,
Iceland, Ireland, Italy, Luxembourg, Malta, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36  B-1050 Brussels
© 2002 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 1118:1998/A1:2002 E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------

SIST EN 1118:1999/A1:2004
EN 1118:1998/A1:2002 (E)
Contents
page
Foreword.3
3 Definitions.3
7 Measurements.4
8 Testing methods and equipment.4
2

---------------------- Page: 4 ----------------------

SIST EN 1118:1999/A1:2004
EN 1118:1998/A1:2002 (E)
Foreword
This document (EN 1118:1998/A1:2002) has been prepared by Technical Committee CEN /TC 110 "Heat
exchangers", the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an identical text or
by endorsement, at the latest by April 2003, and conflicting national standards shall be withdrawn at the latest by
April 2003.
This amendment is introduced to accommodate newly available refrigerants such as R404A, R407C and R410A.
According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following
countries are bound to implement this European Standard: Austria, Belgium, Czech Republic, Denmark, Finland,
France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg, Malta, Netherlands, Norway, Portugal, Spain,
Sweden, Switzerland and the United Kingdom.
3 Definitions
Modify 3.7.4 to read as follows:
3.7.4 evaporating temperature: Dew point temperature of the refrigerant, corresponding to the evaporating
pressure.
Add definition after 3.7.6 as follows:
3.7.7 bubble point temperature: Temperature corresponding to the absolute pressure of the refrigerant at the inlet
connection of the expansion devices.
Modify 3.8.3 to read as follows:
3.8.3 subcooling: Difference between the bubble point temperature corre
...