Extended application of results from fire resistance tests for service installations - Part 5: Combined penetration seals

The purpose of this document is to provide the principles and guidance for the preparation of extended application documents for combined penetration seals where the systems were tested in accordance with EN 1366-1, EN 1366-2 and EN1366-3. The field of the extended application document is additional to the direct field of application given within EN 1366-1, EN 1366-2 and EN 1366-3 and may be applied on a number of tests from each standard, which provide the relevant information for the formulation of an extended application.
This EXAP is intended to allow the penetration sealing of more than one service including Ducts and Dampers in the same penetration.

Erweiterter Anwendungsbereich der Ergebnisse aus Feuerwiderstandsprüfungen für Installationen - Teil 5: Kombinierte Abschottungen

Zweck dieses Dokuments ist die Bereitstellung von Grundsätzen und Anleitungen für die Erstellung von Dokumenten zur erweiterten Anwendung von Kombi-Brandschotten, die nach EN 1366 1, EN 1366 2 und EN 1366 3 geprüft wurden. Das Dokument zum erweiterten Anwendungsbereich gilt zusätzlich zu dem in EN 1366 1, EN 1366 2 und EN 1366 3 angegebenen direkten Anwendungsbereich und kann für mehrere Prüfungen aus jeder Norm angewendet werden, die die relevanten Informationen für die Formulierung einer erweiterten Anwendung liefert.
Dieser EXAP (en: extended application) dient dazu, die Abschottung mehrerer Leitungen (z. B. Kabel, Rohrleitungen, Kanäle, feuerwiderstandsfähige Leitungen und Brandschutzklappen) in derselben Durchführung zu ermöglichen.

Application étendue des résultats des essais de résistance au feu des installations de service - Partie 5 : Calfeutrements de trémie combinés

Le présent document a pour objectif de fournir des principes et des recommandations pour l'élaboration de documents d'application étendue relatifs aux systèmes de calfeutrements de trémie combinés ayant été soumis à l'essai conformément à l'EN 1366-1, l'EN 1366-2 et l'EN 1366-3. Par rapport au domaine d'application direct décrit dans l'EN 1366-1, l'EN 1366-2 et l'EN 1366-3, le domaine d'application du document d'application étendue est complémentaire et peut s'appliquer à plusieurs essais de chacune de ces normes, lesquels fournissent les informations pertinentes permettant de formuler une application étendue.
Cet EXAP a pour objectif de permettre le calfeutrement de plusieurs traversants (par exemple : câbles, tuyaux,  gaines, conduits résistant au feu et clapets résistant au feu) dans la même traversée.

Razširjena uporaba rezultatov preskusov požarne odpornosti servisnih inštalacij - 5. del: Kombinirane tesnitve prebojev

General Information

Status
Not Published
Current Stage
5060 - Closure of Vote - Formal Approval
Due Date
24-Jun-2021
Completion Date
24-Jun-2021

Buy Standard

Draft
prEN 15882-5:2019
English language
33 pages
sale 10% off
Preview
sale 10% off
Preview

e-Library read for
1 day

Standards Content (sample)

SLOVENSKI STANDARD
oSIST prEN 15882-5:2019
01-november-2019

Razširjena uporaba rezultatov preskusov požarne odpornosti servisnih inštalacij -

5. del: Kombinirane tesnitve prebojev

Extended application of results from fire resistance tests for service installations - Part 5:

Combined penetration seals
Erweiterter Anwendungsbereich der Ergebnisse aus Feuerwiderstandsprüfungen für
Installationen - Teil 5: Kombinierte Abschottungen

Extension du champ d´application des résultats des essais de résistance au feu - Partie

5 : Calfeutrements a joints combines
Ta slovenski standard je istoveten z: prEN 15882-5
ICS:
13.220.50 Požarna odpornost Fire-resistance of building
gradbenih materialov in materials and elements
elementov
oSIST prEN 15882-5:2019 en,fr,de

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
oSIST prEN 15882-5:2019
---------------------- Page: 2 ----------------------
oSIST prEN 15882-5:2019
DRAFT
EUROPEAN STANDARD
prEN 15882-5
NORME EUROPÉENNE
EUROPÄISCHE NORM
September 2019
ICS 13.220.99
English Version
Extended application of results from fire resistance tests
for service installations - Part 5: Combined penetration
seals

Extension du champ d´application des résultats des Erweiterter Anwendungsbereich der Ergebnisse aus

essais de résistance au feu - Partie 5 : Calfeutrements a Feuerwiderstandsprüfungen für Installationen - Teil 5:

joints combines Kombinierte Abschottungen

This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee

CEN/TC 127.

If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations

which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other

language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC

Management Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,

Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,

Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and

United Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are

aware and to provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without

notice and shall not be referred to as a European Standard.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels

© 2019 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 15882-5:2019 E

worldwide for CEN national Members.
---------------------- Page: 3 ----------------------
oSIST prEN 15882-5:2019
prEN 15882-5:2019 (E)
Contents Page

European foreword ............................................................................................................................................ 4

1 Scope .......................................................................................................................................................... 5

2 Normative references .......................................................................................................................... 5

3 Terms and definitions ......................................................................................................................... 5

4 Extended application principles ..................................................................................................... 6

5 Pre-conditions for extended application ..................................................................................... 7

5.1 Basic tests required ............................................................................................................................. 7

5.2 Additional collaborative test requirements to be added to EN 1366-1 ............................ 7

5.2.1 General...................................................................................................................................................... 7

5.2.2 Additional test requirements table — fire resisting ducts .................................................... 8

5.2.3 Diagram indicating minimum and maximum edge distance position inside

penetration seal .................................................................................................................................. 10

5.2.4 Diagram indicating position of fire resisting duct reinforcements depending on the

system ..................................................................................................................................................... 11

5.2.5 Diagram indicating position critical service penetrations to be tested .......................... 12

5.2.6 Diagram position of penetrating service when additional insulation is applied ........ 12

6 Specific rules to be applied to combined penetration applications – Fire resisting

ducts ........................................................................................................................................................ 13

6.1 General.................................................................................................................................................... 13

6.2 Service penetration permitted variations ................................................................................. 14

6.2.1 Rules for supporting construction ................................................................................................ 14

6.2.2 Fire resisting duct dimension ......................................................................................................... 14

6.2.3 Rules for penetration seal ............................................................................................................... 15

6.2.4 Rules for penetration services ....................................................................................................... 15

7 Pre-conditions for extended application — Fire dampers .................................................. 16

7.1 Basic tests required ........................................................................................................................... 16

7.1.1 General.................................................................................................................................................... 16

7.1.2 Method of installation in the wall and/or floor ....................................................................... 17

7.1.3 Method of installation on to the wall and/or floor ................................................................. 17

7.1.4 Method of installation away (remote) from the wall and/or floor ................................... 17

7.2 Additional Collaborative Test Requirements to be added to EN 1366-2 ........................ 17

7.2.1 Additional test requirements table — fire dampers .............................................................. 17

7.2.2 Diagram indicating minimum and maximum edge distance position inside

penetration seal .................................................................................................................................. 21

7.2.3 Diagram indicating position critical service penetrations to be tested .......................... 22

7.2.4 Diagram position of penetrating service when additional insulation is applied ........ 22

8 Specific rules to be applied to combined penetration applications – Fire dampers .. 24

8.1 General.................................................................................................................................................... 24

8.2 Permitted variations.......................................................................................................................... 24

8.2.1 Rules for supporting construction ................................................................................................ 24

8.2.2 Fire damper dimension .................................................................................................................... 25

8.2.3 Rules for penetration seal ............................................................................................................... 25

8.2.4 Rules for penetration services ....................................................................................................... 26

9 Extended application report ........................................................................................................... 26

Annex A (informative) Explanatory notes .............................................................................................. 27

---------------------- Page: 4 ----------------------
oSIST prEN 15882-5:2019
prEN 15882-5:2019 (E)

A.1 Examples of the EXAP field of application ................................................................................. 27

A.1.1 Worked example table ...................................................................................................................... 27

A.1.2 EXAP field application flow chart ................................................................................................. 28

A.1.3 Template for worked example....................................................................................................... 29

Annex B (normative) Explanatory notes ................................................................................................. 31

B.1 Combined penetration seal EXAP test setup and requirements ....................................... 31

B.1.1 General ................................................................................................................................................... 31

B.1.2 Test Furnace ......................................................................................................................................... 31

B.1.3 Fire resisting duct and service combinations .......................................................................... 31

B.1.4 Fire Damper and service combinations...................................................................................... 31

B.1.5 Penetration Sealing System ............................................................................................................ 32

Bibliography ....................................................................................................................................................... 33

---------------------- Page: 5 ----------------------
oSIST prEN 15882-5:2019
prEN 15882-5:2019 (E)
European foreword

This document (prEN 15882-5:2019) has been prepared by Technical Committee CEN/TC 127 “Safety in

fire”, the secretariat of which is held by BSI.

This series has the general title Extended application of results from fire resistance tests for service

installations and consists of the following parts:
— Part 1: Fire resisting ducts
— Part 2: Fire dampers
— Part 3: Penetration seals
— Part 4: Linear joint seals
— Part 5: Combined Penetration Seals

This document has been prepared under a mandate given to CEN by the European Commission and the

European Free Trade Association.
---------------------- Page: 6 ----------------------
oSIST prEN 15882-5:2019
prEN 15882-5:2019 (E)
1 Scope

The purpose of this document is to provide the principles and guidance for the preparation of extended

application documents for combined penetration seals where the systems were tested in accordance with

EN 1366-1, EN 1366-2 and EN 1366-3. The field of the extended application document is additional to

the direct field of application given within EN 1366-1, EN 1366-2 and EN 1366-3 and can be applied on a

number of tests from each standard, which provide the relevant information for the formulation of an

extended application.

This EXAP is intended to allow the penetration sealing of more than one service (e.g. Cables, Pipes,

Conduits, Fire resisting ducts and Fire dampers) in the same penetration.
2 Normative references

The following documents are referred to in the text in such a way that some or all of their content

constitutes requirements of this document. For dated references, only the edition cited applies. For

undated references, the latest edition of the referenced document (including any amendments) applies.

EN 1363-1, Fire resistance tests — Part 1: General requirements
EN 1363-2, Fire resistance tests — Part 2: Alternative and additional procedures

EN 1366-1, Fire resistance tests for service installations — Part 1: Ventilation ducts

EN 1366-2, Fire resistance tests for service installations — Part 2: Fire dampers

EN 1366-3, Fire resistance tests for service installations — Part 3: Penetration seals

EN 15882-1, Extended application of results from fire resistance tests for service installations — Part 1:

Ducts

EN 15882-2, Extended application of results from fire resistance tests for service installations — Part 2: Fire

dampers

EN 15882-3, Extended applications of results from fire resistance tests for service installations — Part 3:

Penetration seals

EN 13501-1, Fire classification of construction products and building elements — Part 1: Classification

using data from reaction to fire tests

EN 13501-2, Fire classification of construction products and building elements — Part 2: Classification

using data from fire resistance tests, excluding ventilation services
EN ISO 13943, Fire safety — Vocabulary (ISO 13943)
3 Terms and definitions

For the purposes of this document, the definitions given in EN 1363-1, EN 1363-2, EN 1366-1, EN 1366-2,

EN 1366-3, EN 15882-1, EN 15882-3, EN 13501-1, EN 13501-2 and EN ISO 13943 and the following

apply:

ISO and IEC maintain terminological databases for use in standardization at the following addresses:

• IEC Electropedia: available at http://www.electropedia.org/
• ISO Online browsing platform: available at http://www.iso.org/obp
---------------------- Page: 7 ----------------------
oSIST prEN 15882-5:2019
prEN 15882-5:2019 (E)
3.1
combined penetration seal

system used to maintain the fire resistance of a separating element at the position where one or more

services, according to EN 1366-3,EN 1366-1 and EN 1366-2, pass through
3.2
duct reinforcement
assembly reinforcing the duct at the penetration sealing system
Note 1 to entry: as Figure 2, 5.2.3.
3.3
duct strip

assembly adjoining the duct at 90 degrees on each side of the penetration sealing system

Note 1 to entry: as Figure 2, 5.2.3.
Note 2 to entry: This is typically used with fully insulated ducts.
4 Extended application principles

Due to the diverse nature of materials and constructions used to seal openings in fire resistant separating

elements, it has been necessary to separate the extended application principles into generic seal types.

Where more than one variation is to be incorporated the overall effect shall be considered. Principles

common to all generic seal types are given in EN 1366-3. Assembly adjoining the fire resisting duct at 90

degrees on each side of the penetration sealing system as Figure 2, 5.2.3. This is typically used with fully

insulated fire resisting ducts.

NOTE In any combined service penetration test according to this document, it is not the intention to re-test the

penetration sealing system but to identify if there are any interface effects between the fire resisting duct and other

services that can cause the whole system to fail, such as radiating heat from the fire resisting duct or any service

passing through the penetration seal.

Variables for each seal type, which require consideration, are included in this report. These are as follows:

a) Supporting construction;
b) Type of service;
c) Size of service;
d) Seal size ;
e) System changes (components) — comparison test approach, reduced test program;
f) Distance between services;
g) Distance between penetrations;
h) Configuration of penetration services;
i) Service support location;
j) Orientation of the services;

k) Classifications from tests results A to C in Figure 1 cannot be exceeded in the field of application (even

if a higher classification is achieved in test D);
l) Test results from this EXAP can only be used for combined penetration seals.

Each subclause gives the possible variation and the rule relating to the variation.

---------------------- Page: 8 ----------------------
oSIST prEN 15882-5:2019
prEN 15882-5:2019 (E)
5 Pre-conditions for extended application
5.1 Basic tests required

Basic tests shall have been conducted to allow the use of combined service penetrations in the same

penetration sealing system.

Figure 1 indicates the flow of basic test results to enable the use of the EXAP test. Test results from 1 of

each, A, B and C, shall have been previously achieved prior to moving on to the EXAP test. EXAP test

requirements according to Annex B.
Figure 1 — The Basic Tests

a) EN 1366-3, Maximum blank penetration size test for the required orientation(s) in the penetration

seal — Result A

b) EN 1366-3, Maximum penetration size test(s) with the penetrating services intended to be

incorporated in the combined penetration seal and required orientation in the penetration seal

system to be used in 6.2.1 or 6.2.2 — Result B
c) EN 1366-1, Duct A test(s) in the required orientation — Result C
d) EN 1366-1, Duct B test(s) in the required orientation — Result C
5.2 Additional collaborative test requirements to be added to EN 1366-1
5.2.1 General

The test can be conducted by multiple test sponsors, sharing each other’s initial type testing results, or as

a standalone approach if one test sponsor holds all the valid relevant test data required.

EN 1366-1 Maximum penetration size and edge distance required for the Type B duct according to

Table 2 if both fire resisting duct types are to be covered in the required orientation(s). Penetration

sealing system shall be the identical penetration seal and supporting construction as 2 and 3 with the

penetration services as defined in 5.2.1, Table 1;
and/or;

EN 1366-1 Maximum penetration size and edge distance required for the fire resisting duct type from 3

or 4 according to Table 2, if only one fire resisting duct type is required, in the required orientation(s).

Penetration sealing system shall be the identical penetration seal and supporting construction as 2 and 3

with the penetration services as defined in 5.2.1, Table 1.
---------------------- Page: 9 ----------------------
oSIST prEN 15882-5:2019
prEN 15882-5:2019 (E)
5.2.2 Additional test requirements table — fire resisting ducts
Table 1 — To be read in conjunction with Figure 1, 2, 3 and 4
Combined penetration seal
E, ES, EI, EIS classified systems EXAP test setup and
requirements — see Annex A
Tested Tested
Tested Additional test requirements
according to according to
according to for combined penetration
EN 1366-1 EN 1366-1
EN 1366-3 seal system
Type A Type B
As required As required Maximum required seal size,
Maximum seal
by test by test not exceeding the blank seal as
size
sponsor sponsor tested according to EN 1366-3
Test duct B if both duct type are
Rectangle duct 1 000 mm x required. Should only one duct
size 500 mm type be required, that type shall
be tested
Circular duct
800 ± 10
size
500 mm ± 50 from the free 500 mm ± 50 mm from the free
Duct position
edge edge
As required As required
by test by test
Min. side space sponsor with sponsor with
Min. edge distance required
distance duct position duct position
according to according to
EN 1366-1 EN 1366-1
50 mm edge distance or collar
Bottom space
size ± 100 mm —whichever is
distance
greater
Max. top space
Max. edge distance required
distance
Max. side space
distance
Max. size
Max. seal size as tested
Blank seal size required by
according to EN 1366-3
test sponsor
Critical cables to be used:
1 x E type cable
Cable Full standard
F type cable bunches 100 mm
penetrating cable
2 x B type cable
services configuration
1 x C type cable
300 mm perforated cable tray
---------------------- Page: 10 ----------------------
oSIST prEN 15882-5:2019
prEN 15882-5:2019 (E)
Combined penetration seal
E, ES, EI, EIS classified systems EXAP test setup and
requirements — see Annex A
Tested Tested
Tested Additional test requirements
according to according to
according to for combined penetration
EN 1366-1 EN 1366-1
EN 1366-3 seal system
Type A Type B
Cable Non-standard Test those requires to be used
penetrating configuration from previous test according to
services cables EN 1366-3
Critical pipes
Metallic pipe Most critical pipes according to
as previously
penetrating EN 1366-3:2004, G.3 formed in
tested by test
services linear arrangement
sponsor
Critical
Plastic pipe services as Most critical pipes according to
penetrating previously EN 1366-3:2004, G.3 formed in
services tested by test linear arrangement
sponsor
Other types of
service e.g. As previously Most critical to be included as
conduit, MLC tested required by the test sponsor
pipes, etc.
Other types of
service e.g.
As required by the test sponsor
Waveguides,
Busbars
Penetrating
T/C position according to
service
EN 1366-3
thermocouples
Penetrating Critical services shall be tested
service position above the duct as per Figure 3
Penetrating
service As required by the test sponsor
distances
Cable and pipe service shall
extend 200 mm past any
Min. service additional
length insulation/penetration seal or
other materials for E classified
ducts as per Figure 4
• See worked example table in Annex A — Informative
• See Template table in Annex A — Informative
---------------------- Page: 11 ----------------------
oSIST prEN 15882-5:2019
prEN 15882-5:2019 (E)

5.2.3 Diagram indicating minimum and maximum edge distance position inside penetration seal

Key
A Minimum side edge distance

B 500mm Bottom edge distance or collar size +100mm — whichever is greater — see Figure 2

C Maximum top edge distance
D Maximum side edge distance
E Minimum edge distance of 500mm according to EN 1366-1

XX/YY Maximum penetration size as determined by previous tests according to EN 1366-3

Figure 2
---------------------- Page: 12 ----------------------
oSIST prEN 15882-5:2019
prEN 15882-5:2019 (E)

5.2.4 Diagram indicating position of fire resisting duct reinforcements depending on the system

Key
A Duct Strip and Position
B Fire resisting duct
C Penetration Sealing System
D Supporting Construction
Figure 3
---------------------- Page: 13 ----------------------
oSIST prEN 15882-5:2019
prEN 15882-5:2019 (E)
5.2.5 Diagram indicating position critical service penetrations to be tested

The distances between services in a combined penetration seal with reference to the particular

combination of service /service types and associated secondary part of the penetration seal types, shall

be minimum as tested according to EN 1366-3.
Key
A Penetrating service edge distance to supporting construction
B Penetrating service distance to top of fire resisting duct
B, C2, E, F Relevant cable types

XX/YY Maximum penetration size as determined by previous tests according to EN 1366-3

Figure 4 — Penetrating service distances

5.2.6 Diagram position of penetrating service when additional insulation is applied

If local insulation is added to an E Classified fire resisting duct or is part of the penetration sealing system,

combustible services shall extend for 200mm past the end of the insulation. If insulation is added for

more than 1 500mm the fire resisting duct should be EI Classified in the basic tests according to

EN 1366 1
---------------------- Page: 14 ----------------------
oSIST prEN 15882-5:2019
prEN 15882-5:2019 (E)
Key
A Penetrating Service
B Fire resisting duct
C Distance Past Insulation (200mm)
D Insulation Material
E Duct Strip
F Penetration Sealing System
G Supporting Construction
Figure 5
6 Specific rules to be applied to combined penetration applications – Fire
resisting ducts
6.1 General

• Subject to conducting the tests specified in Clause 5, services and fire resisting ducts may both be

included in a combined penetration seal subject to applying the variations in 6.2.

• Supporting Construction;
• Fire resisting duct Dimension;
• Penetration Seal Type ;
• Seal Construction.
---------------------- Page: 15 ----------------------
oSIST prEN 15882-5:2019
prEN 15882-5:2019 (E)
6.2 Service penetration permitted variations
6.2.1 Rules for supporting construction
Permitted changes to the supporting construction:
Table 2
Rules
• Permitted same as in item 1 to 4, Clause 5
• Wall thickness being equal to or greater than that tested.

• Test results obtained with flexible vertical (wall) supporting constructions as in item 1 to 4,

Clause 5, may be applied to rigid horizontal (floor) supporting constructions of a thickness equal

to or greater than that of the element used in the tests, provided that the classified fire resistance

of the rigid supporting construction is greater than or equal to the one used for the test.

• The floor depth being equal to or greater than that tested.

• Test results obtained with the flexible wall constructions may be applied to rigid constructions of

an overall thickness equal to or greater than that of the element used in the tests and a minimum

density of 450 kg/m . In case of hollow brick walls, the same rules regarding aperture framing

apply as for flexible walls.

Test results obtained with rigid supporting constructions may be applied to high-density, rigid

constructions made of block work, masonry or homogenous concrete with an overall

density ≥ 850 kg/m with a thickness appropriate for the expected fire resistance period, and low

density rigid construction shall be made of aerated concrete block wall with an overall density of

(500 ± 250) kg/m with a thickness appropriate for the expected fire resistance period and separating

elements of a thickness and density equal to or greater than that of the supporting construction used

in the test
6.2.2 Fire resisting duct dimension

Maximum increased nominal internal dimensions of fire resisting ducts are permitted, according to

EN 1366-1.
---------------------- Page: 16 ----------------------
oSIST prEN 15882-5:2019
prEN 15882-5:2019 (E)
6.2.3 Rules for penetration seal
Table 3
Rules
• Identical seal system as previously tested in EN 1366-3.

• Identical secondary seal system, such as closure devices, as previously tested in EN 1366-3.

• Maximum seal size as tested according to EN 1366-3.
• Position of combined services once EXAP test has been completed as Figure 4.

• Duct position can be anywhere in the penetration as long as the maximum edge distance is not

exceeded as defined by Figure 2 (distance D).

• Duct position can be anywhere in the penetration as long as the overall penetration height is not

exceeded (distance YY) Figure 2.

• Duct position can be anywhere in the penetration as long as the minimum side edge distance is not

decreased as defined by Figure 2 (distance A).

• Cable and Pipe service position can be anywhere in the penetration subject to the minimum

separation as tested according to EN 1366-3.
• Penetration service minimum edge distances as defined in EN 1366-3.
• Penetration Service supports according to EN 1366-3.
• Fire resisting duct Service supports according to EN 1366-1.
• Direct field of application according to EN 1366-3 and EN 1366-1.
6.2.4 Rules for penetration services
Table 4
Rules

• Fire resisting duct to be identical to the size previously tested according to EN 1366-1.

• Mixed Pipes as previously tested according to EN 1366-3.

• Standard Cable Configuration as previously tested according to EN 1366-3 covers all cables.

• Non-standard cables as previously tested according to EN 1366-3.
• Metallic Pipes as previously tested according to EN 1366-3.
• Plastic Pipes as previously tested according to EN 1366-3.
• Other pipes as previously tested according to EN 1366-3.
• Conduits as previously tested according to EN 1366-3.
• Waveguides as previously tested according to EN 1366-3.
• Busbars as previously tested according to EN 1366-3.
---------------------- Page: 17 ----------------------
oSIST prEN 15882-5:2019
prEN 15882-5:2019 (E)
7 Pre-conditions for extended application — Fire dampers
7.1 Basic tests required
7.1.1 General

Basic tests to have been conducted to allow use of combined service penetrations in the same penetration

sealing system.

Figure 6 indicates the flow of basic test results to enable the use of the EXAP test. Test results from 1 of

each A,B and C, shall have been previously achieved prior to moving on to the EXAP test. EXAP test

requirements according to Annex B.
Figure 6
The basic tests
a) The same penetration sealing system intended to be incorporated in the
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.