EN IEC 60255-187-1:2021
(Main)Measuring relays and protection equipment - Part 187-1: Functional requirements for differential protection - Restrained and unrestrained differential protection of motors, generators and transformers
Measuring relays and protection equipment - Part 187-1: Functional requirements for differential protection - Restrained and unrestrained differential protection of motors, generators and transformers
IEC 60255-187-1:2021 specifies the minimum requirements for functional and performance evaluation of (longitudinal) differential protection designed for the detection of faults in ac motors, generators and transformers. This document also defines how to document and publish performance test results. This document defines the influencing factors that affect the accuracy under steady state conditions and performance characteristics during dynamic conditions. The test methodologies for verifying performance characteristics and accuracy are also included in this document. This document, together with IEC 60255-187-2 and IEC 60255-187-3, cancels and replaces IEC 60255-13. This document includes the following significant technical changes with respect to IEC 60255-13: a) IEC 60255-13 has been significantly revised to follow the common structure of the functional standards for protection relays (IEC 60255-1xx series). IEC 60255-187-1 has been developed to address the restrained and unrestrained differential protection of motors, generators and transformers. The revisions include detailed description of the functions including the performance specification, testing and documentation requirements.
Messrelais und Schutzeinrichtungen - Teil 187-1: Funktionsanforderungen für den stabilisierten und nicht stabilisierten Differentialschutz von Motoren, Generatoren und Transformatoren
Relais de mesure et dispositifs de protection - Partie 187-1: Exigences fonctionnelles pour la protection différentielle - Protection différentielle avec et sans caractéristique de retenue des moteurs, générateurs et transformateurs
IEC 60255-187-1:2021 spécifie les exigences minimales relatives à l'évaluation fonctionnelle et à l’évaluation de la performance de la protection différentielle (longitudinale) conçue pour la détection des défauts dans les moteurs à courant alternatif, les générateurs et les transformateurs. Le présent document définit également comment documenter et publier les résultats des essais de performance.Le présent document définit les facteurs d'influence qui affectent la précision en état stable et les caractéristiques de performance dans des conditions dynamiques. Les méthodologies d’essai permettant de vérifier les caractéristiques de performance et la précision sont également incluses dans le présent document. Le présent document, ainsi que l’IEC 60255-187-2 et l’IEC 60255-187-3, annule et remplace l’IEC 60255-13. Le présent document inclut les modifications techniques majeures suivantes par rapport à l'IEC 60255‑13: a. L’IEC 60255-13 a été considérablement révisée pour suivre la structure commune des normes fonctionnelles pour les relais de protection (série IEC 60255-1xx). L’IEC 60255-187-1 a été développée pour traiter la protection différentielle avec et sans caractéristique de retenue des moteurs, générateurs et transformateurs. Les révisions comprennent une description détaillée des fonctions, y compris les spécifications de performance, les essais et les exigences en matière de documentation.
Merilni releji in zaščitna oprema - 187-1. del: Funkcijske zahteve za diferenčno zaščito - Omejena in neomejena diferenčna zaščita motorjev, generatorjev in transformatorjev
General Information
Relations
Overview
EN IEC 60255-187-1:2021 (IEC 60255-187-1:2021) specifies minimum functional and performance requirements for longitudinal (phase) differential protection used on AC motors, generators and transformers. The standard defines how to evaluate, test and document both restrained (biased) and unrestrained differential protection functions, describing the influencing factors that affect accuracy under steady-state and dynamic conditions and the test methods to verify performance. EN IEC 60255-187-1:2021 replaces IEC 60255-13 and aligns differential protection requirements with the IEC 60255-1xx functional standard structure.
Key topics and requirements
- Function specification
- Inputs: energizing quantities, CT connections and digital interfaces
- Binary inputs and functional logic for start (pick-up), operate (trip) and other signals
- Differential schemes
- Phase-biased (restrained) differential protection
- Unrestrained differential and biased restricted earth-fault protection
- Compensation: ratio (magnitude) compensation, phase (vector) compensation and zero-sequence compensation
- Performance and accuracy
- Effective and operating ranges; steady-state accuracy tests (basic characteristic, ratio/phase compensation, harmonic restraint)
- Dynamic performance: typical operate times for double-infeed and radial single-infeed network models (restrained/unrestrained)
- Stability requirements for CT saturation, magnetizing inrush, overexcitation, switch-on-to-fault, load harmonics and off‑nominal frequency
- Testing and documentation
- Detailed functional and dynamic test methods, reporting of typical operate times and type test reports
- Requirements for publishing performance test results and user documentation
Practical applications
EN IEC 60255-187-1:2021 is used to:
- Specify performance and test criteria in procurement and technical specifications for protection relays
- Guide factory and type testing of differential relays (manufacturers and testing laboratories)
- Support protection engineers during relay selection, commissioning and relay setting studies
- Ensure consistent testing and reporting for reliability on motors, generators and transformers in power plants, utilities and industrial installations
Who should use this standard
- Relay manufacturers and R&D teams developing differential protection functions
- Utility and industrial protection engineers and relay settings engineers
- Third‑party testing laboratories and certification bodies
- OEMs, consultants and procurement specialists responsible for protection system compliance
Related standards
- IEC 60255-187-2 and IEC 60255-187-3 (companion parts)
- IEC 60255-1 (common relay functional requirements)
- References to IEC 61850 series and IEC 61869 instrument transformer standards for digital/CT interfacing
Keywords: differential protection, restrained differential, unrestrained differential, motors generators transformers, EN IEC 60255-187-1:2021, protection relays, CT saturation, inrush, harmonic restraint, phase compensation, performance testing.
Frequently Asked Questions
EN IEC 60255-187-1:2021 is a standard published by CLC. Its full title is "Measuring relays and protection equipment - Part 187-1: Functional requirements for differential protection - Restrained and unrestrained differential protection of motors, generators and transformers". This standard covers: IEC 60255-187-1:2021 specifies the minimum requirements for functional and performance evaluation of (longitudinal) differential protection designed for the detection of faults in ac motors, generators and transformers. This document also defines how to document and publish performance test results. This document defines the influencing factors that affect the accuracy under steady state conditions and performance characteristics during dynamic conditions. The test methodologies for verifying performance characteristics and accuracy are also included in this document. This document, together with IEC 60255-187-2 and IEC 60255-187-3, cancels and replaces IEC 60255-13. This document includes the following significant technical changes with respect to IEC 60255-13: a) IEC 60255-13 has been significantly revised to follow the common structure of the functional standards for protection relays (IEC 60255-1xx series). IEC 60255-187-1 has been developed to address the restrained and unrestrained differential protection of motors, generators and transformers. The revisions include detailed description of the functions including the performance specification, testing and documentation requirements.
IEC 60255-187-1:2021 specifies the minimum requirements for functional and performance evaluation of (longitudinal) differential protection designed for the detection of faults in ac motors, generators and transformers. This document also defines how to document and publish performance test results. This document defines the influencing factors that affect the accuracy under steady state conditions and performance characteristics during dynamic conditions. The test methodologies for verifying performance characteristics and accuracy are also included in this document. This document, together with IEC 60255-187-2 and IEC 60255-187-3, cancels and replaces IEC 60255-13. This document includes the following significant technical changes with respect to IEC 60255-13: a) IEC 60255-13 has been significantly revised to follow the common structure of the functional standards for protection relays (IEC 60255-1xx series). IEC 60255-187-1 has been developed to address the restrained and unrestrained differential protection of motors, generators and transformers. The revisions include detailed description of the functions including the performance specification, testing and documentation requirements.
EN IEC 60255-187-1:2021 is classified under the following ICS (International Classification for Standards) categories: 29.120.70 - Relays. The ICS classification helps identify the subject area and facilitates finding related standards.
EN IEC 60255-187-1:2021 has the following relationships with other standards: It is inter standard links to EN IEC 60255-187-1:2021/AC:2023-04. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
You can purchase EN IEC 60255-187-1:2021 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of CLC standards.
Standards Content (Sample)
SLOVENSKI STANDARD
SIST EN 60255-187-1:2021
01-november-2021
Merilni releji in zaščitna oprema - 187-1. del: Funkcijske zahteve za diferenčno
zaščito - Omejena in neomejena diferenčna zaščita motorjev, generatorjev in
transformatorjev
Measuring relays and protection equipment - Part 187-1: Functional requirements for
differential protection - Restrained and unrestrained differential protection of motors,
generators and transformers
Ta slovenski standard je istoveten z: EN IEC 60255-187-1:2021
ICS:
29.120.70 Releji Relays
SIST EN 60255-187-1:2021 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
SIST EN 60255-187-1:2021
SIST EN 60255-187-1:2021
EUROPEAN STANDARD EN IEC 60255-187-1
NORME EUROPÉENNE
EUROPÄISCHE NORM
September 2021
ICS 29.120.70
English Version
Measuring relays and protection equipment - Part 187-1:
Functional requirements for differential protection - Restrained
and unrestrained differential protection of motors, generators
and transformers
(IEC 60255-187-1:2021)
Relais de mesure et dispositifs de protection - Partie 187-1: Messrelais und Schutzeinrichtungen - Teil 187-1:
Exigences fonctionnelles pour la protection différentielle - Funktionsanforderungen für den stabilisierten und nicht
Protection différentielle avec et sans caractéristique de stabilisierten Differentialschutz von Motoren, Generatoren
retenue des moteurs, générateurs et transformateurs und Transformatoren
(IEC 60255-187-1:2021) (IEC 60255-187-1:2021)
This European Standard was approved by CENELEC on 2021-09-01. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2021 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN IEC 60255-187-1:2021 E
SIST EN 60255-187-1:2021
European foreword
The text of document 95/465/FDIS, future edition 1 of IEC 60255-187-1, prepared by IEC/TC 95
“Measuring relays and protection equipment” was submitted to the IEC-CENELEC parallel vote and
approved by CENELEC as EN IEC 60255-187-1:2021.
The following dates are fixed:
• latest date by which the document has to be implemented at national (dop) 2022-06-01
level by publication of an identical national standard or by endorsement
• latest date by which the national standards conflicting with the (dow) 2024-09-01
document have to be withdrawn
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
Any feedback and questions on this document should be directed to the users’ national committee. A
complete listing of these bodies can be found on the CENELEC website.
Endorsement notice
The text of the International Standard IEC 60255-187-1:2021 was approved by CENELEC as a
European Standard without any modification.
In the official version, for Bibliography, the following notes have to be added for the standards
indicated:
IEC 61850 (series) NOTE Harmonized as EN 61850 (series)
IEC 61850-7-4:2010 NOTE Harmonized as EN 61850-7-4:2010 (not modified)
IEC 61850-9-2 NOTE Harmonized as EN 61850-9-2
SIST EN 60255-187-1:2021
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments)
applies.
NOTE 1 Where an International Publication has been modified by common modifications, indicated by (mod), the
relevant EN/HD applies.
NOTE 2 Up-to-date information on the latest versions of the European Standards listed in this annex is available
here: www.cenelec.eu.
Publication Year Title EN/HD Year
IEC 60255-1 - Measuring relays and protection equipment EN 60255-1 -
- Part 1: Common requirements
IEC 61850-8-1 - Communication networks and systems for EN 61850-8-1 -
power utility automation - Part 8–1:
Specific communication service mapping
(SCSM) - Mappings to MMS (ISO 9506-1
and ISO 9506-2) and to ISO/IEC 8802-3
IEC 61869-2 - Instrument transformers - Part 2: Additional EN 61869-2 -
requirements for current transformers
IEC 61869-9 - Instrument transformers - Part 9: Digital EN IEC 61869-9 -
interface for instrument transformers
SIST EN 60255-187-1:2021
SIST EN 60255-187-1:2021
IEC 60255-187-1 ®
Edition 1.0 2021-07
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
colour
inside
Measuring relays and protection equipment –
Part 187-1: Functional requirements for differential protection – Restrained and
unrestrained differential protection of motors, generators and transformers
Relais de mesure et dispositifs de protection –
Partie 187-1: Exigences fonctionnelles pour la protection différentielle –
Protection différentielle avec et sans caractéristique de retenue des moteurs,
générateurs et transformateurs
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 29.120.70 ISBN 978-2-8322-1003-9
SIST EN 60255-187-1:2021
– 2 – IEC 60255-187-1:2021 © IEC 2021
CONTENTS
FOREWORD . 11
1 Scope . 13
2 Normative references . 14
3 Terms and definitions . 14
4 Specification of the function . 18
4.1 General . 18
4.2 Input energizing quantities/energizing quantities . 19
4.2.1 General . 19
4.2.2 Connections . 19
4.3 Binary input signals. 19
4.4 Functional logic . 22
4.4.1 General . 22
4.4.2 Phase biased differential protection . 22
4.4.3 Biased restricted earth fault protection . 24
4.4.4 Compensation of energizing quantities . 25
4.4.5 Additional restraint or blocking methods . 26
4.5 Binary output signals . 27
4.5.1 General . 27
4.5.2 Start (pick-up) signals . 27
4.5.3 Operate (trip) signals . 27
4.5.4 Other output signals . 27
4.6 Additional influencing functions and conditions . 27
4.6.1 General . 27
4.6.2 Operation during CT saturation . 28
4.6.3 Switch onto fault . 28
4.6.4 Energizing quantity failure (CT supervision) . 28
4.6.5 Off-nominal frequency operation . 28
4.6.6 Geomagnetically induced currents (GIC) . 28
5 Performance specification . 29
5.1 General . 29
5.2 Effective and operating ranges. 29
5.3 Steady state accuracy tests in the effective range . 29
5.3.1 General . 29
5.3.2 Test related to the declared thermal withstand current . 30
5.3.3 Basic characteristic accuracy . 30
5.3.4 Ratio compensation accuracy . 30
5.3.5 Phase (vector) compensation validity . 31
5.3.6 Zero sequence compensation validity . 31
5.3.7 Harmonic restraint basic accuracy . 31
5.3.8 Basic accuracy of time delay settings . 31
5.3.9 Disengage time. 31
5.4 Dynamic performance in operating range . 32
5.4.1 General . 32
5.4.2 Typical operate time . 32
5.4.3 Relay stability for external faults . 32
5.4.4 Relay behaviour for internal fault preceded by an external fault . 33
5.5 Stability during magnetizing inrush conditions . 33
SIST EN 60255-187-1:2021
IEC 60255-187-1:2021 © IEC 2021 – 3 –
5.6 Stability during overexcitation conditions . 33
5.7 Presence of harmonics on load . 33
5.8 Performance during saturation of current transformers . 33
5.9 Behaviour of differential protection with digital interface for the energizing
quantities . 34
6 Functional tests . 34
6.1 General . 34
6.2 Test related to the declared thermal withstand current . 35
6.3 Steady state accuracy tests in effective range . 35
6.3.1 General . 35
6.3.2 Basic characteristic accuracy . 37
6.3.3 Ratio (magnitude) compensation accuracy . 44
6.3.4 Phase (vector) compensation validity . 45
6.3.5 Zero sequence compensation validity . 47
6.3.6 Harmonic restraint basic accuracy test under steady state conditions at
nominal frequency . 50
6.3.7 Accuracy related to time delay setting . 52
6.3.8 Determination and reporting of the disengage time . 54
6.4 Dynamic performance tests . 55
6.4.1 General . 55
6.4.2 Operate time for double infeed network model (restrained operation) . 57
6.4.3 Operate time for double infeed network model (unrestrained operation) . 68
6.4.4 Operate time for radial single infeed network model (restrained
operation) . 73
6.4.5 Operate time for radial single infeed network model (unrestrained
operation) . 86
6.4.6 Reporting of typical operate time . 89
6.4.7 Stability for external faults . 95
6.5 Relay behaviour for internal fault preceded by an external fault . 112
6.5.1 General . 112
6.5.2 Application specific considerations: transformer differential . 112
6.5.3 Application specific considerations: biased restricted earth fault . 115
6.5.4 Application specific considerations: generator differential . 119
6.5.5 Reporting . 122
6.6 Stability during inrush conditions. 123
6.6.1 General . 123
6.6.2 Application specific considerations: transformer differential . 123
6.7 Stability during overexcitation conditions . 128
6.7.1 General . 128
6.7.2 Application specific considerations: transformer differential . 128
6.8 Performance with load harmonics . 133
6.8.1 General . 133
6.8.2 Application specific considerations: transformer differential . 133
6.8.3 Application specific considerations: generator or motor differential . 137
6.8.4 Application specific considerations: biased restricted earth fault . 140
6.8.5 Reporting . 142
7 Documentation requirements . 143
7.1 Type test report . 143
7.2 Other user documentation . 143
SIST EN 60255-187-1:2021
– 4 – IEC 60255-187-1:2021 © IEC 2021
Annex A (informative) Examples of phase (vector) compensation and zero sequence
compensation schemes . 144
A.1 General . 144
A.2 Y→d conversion . 145
A.2.1 Current conversion . 145
A.2.2 Three-phase fault at Y (star/wye) side . 146
A.2.3 Phase-phase fault at Y (star/wye) side . 147
A.2.4 Single-phase fault at Y (star/wye) side . 147
A.2.5 Three-phase fault at delta side . 148
A.2.6 Phase-phase fault at delta side . 149
A.2.7 Single-phase fault at delta side . 149
A.2.8 Ratio between start currents under different fault types . 152
A.3 d→Y conversion . 152
A.3.1 Current conversion . 152
A.3.2 Three-phase fault at Y (star/wye) side . 153
A.3.3 Phase-phase fault at Y (star/wye) side . 153
A.3.4 Single-phase fault at Y (star/wye) side . 153
A.3.5 Three-phase fault at delta side . 154
A.3.6 Phase-phase fault at delta side . 154
A.3.7 Single-phase fault at delta side . 155
A.3.8 Ratio between start currents under different fault types . 155
Annex B (normative) Calculation of mean, median and mode . 156
B.1 Mean . 156
B.2 Median . 156
B.3 Mode . 156
B.4 Example . 156
Annex C (normative) CT requirements . 157
C.1 General . 157
C.2 Transformer differential protection . 161
C.2.1 General . 161
C.2.2 Fault 1 . 161
C.2.3 Fault 2 . 162
C.2.4 Fault 3 . 162
C.3 Transformer restricted earth fault protection . 163
C.3.1 General . 163
C.3.2 Fault 1 . 163
C.3.3 Fault 2 . 164
C.3.4 Fault 3 . 164
C.4 Generator differential protection . 165
C.4.1 General . 165
C.4.2 Fault 2 . 165
C.4.3 Criteria and additional conditions . 166
C.5 Motor differential protection . 166
C.5.1 General . 166
C.5.2 Fault 1 . 166
C.5.3 Criteria and additional conditions . 166
C.5.4 Start of motor, security case . 167
C.5.5 Criteria and additional conditions . 167
C.6 Reporting . 167
SIST EN 60255-187-1:2021
IEC 60255-187-1:2021 © IEC 2021 – 5 –
Annex D (informative) CT saturation and influence on the performance of differential
relays . 168
Annex E (informative) Guidance on dimensioning of CTs for transformer differential
protection . 173
E.1 General . 173
E.2 Example 1 . 174
E.2.1 General . 174
E.2.2 Verification of CT1 – Internal fault . 175
E.2.3 Verification of CT1 – External fault . 175
E.2.4 Verification of CT2 . 176
E.3 Example 2 . 177
E.3.1 General . 177
E.3.2 Dimensioning of CT1 . 178
E.3.3 Dimensioning of CT2 . 179
Annex F (informative) Examples of test procedures to determine CT sizing
requirements for differential protection . 181
F.1 General . 181
F.2 Test data . 183
F.2.1 General . 183
F.2.2 Network model for CT requirement tests for the transformer differential
protection . 183
F.2.3 Network model for CT requirement tests for the transformer restricted
earth fault protection . 187
F.3 CT data and CT models . 189
F.4 Test summary . 197
Annex G (normative) Ramping methods for testing basic characteristic accuracy . 199
G.1 General . 199
G.2 Pre-fault condition . 199
G.3 Pseudo-continuous ramp . 199
G.4 Ramp of shots. 201
Annex H (informative) Example of COMTRADE file for an evolving fault test case . 203
Annex I (normative) Definition of fault inception angle. 204
Bibliography . 205
Figure 1 – Explanatory diagram for start time, operate time and disengage time . 17
Figure 2 – Simplified biased differential functional block diagram . 18
Figure 3 – Primary current reference direction . 21
Figure 4 – Typical restrained element (biased) characteristic . 23
Figure 5 – Typical unrestrained element characteristic . 23
Figure 6 – Example of combined characteristic using restrained and unrestrained
elements . 24
Figure 7 – Basic error of the operating characteristic . 30
Figure 8 – Example of an operating characteristic in the I /I plane with a
DIFF REST
tolerance band . 37
Figure 9 – Test cases for differential characteristic basic accuracy . 39
Figure 10 – Example of a differential characteristic with test lines "a" to "h" . 40
Figure 11 – Machine differential protection . 40
Figure 12 – Test sequence for basic characteristic accuracy . 42
SIST EN 60255-187-1:2021
– 6 – IEC 60255-187-1:2021 © IEC 2021
Figure 13 – Machine restricted earth fault protection . 44
Figure 14 – Example for documenting the test results for differential relay
characteristic . 45
Figure 15 – Ratio (magnitude) compensation accuracy test . 46
Figure 16 – Secondary three-phase and double-phase injection for Winding 1
(example) . 47
Figure 17 – Secondary single-phase and three-phase injections for Winding 1
(example) . 49
Figure 18 – Zero sequence current injection on the Y side of the transformer . 50
Figure 19 – Zero sequence current injection on the delta side of the transformer . 50
Figure 20 – Example of a rated frequency harmonic restraint characteristic with
visualization of test lines . 53
Figure 21 – Sequence of events for testing the disengage time . 55
Figure 22 – Double infeed network model for operate time tests . 58
Figure 23 – Test sequence for double infeed network model – Restrained operation
(transformer) . 62
Figure 24 – Double infeed network model for operate time tests . 63
Figure 25 – Test sequence for double infeed network model – Restrained operation
(REF) . 66
Figure 26 – Double infeed network model for operate time tests . 67
Figure 27 – Test sequence for double infeed network model – Restrained operation
(generator). 70
Figure 28 – Test sequence for double infeed network model – Unrestrained operation
(transformer) . 73
Figure 29 – Single infeed network model for operate time tests . 74
Figure 30 – Test sequence radial single infeed network model – Restrained operation . 78
Figure 31 – Single infeed network model for operate time tests . 79
Figure 32 – Test sequence for radial single infeed network – Restrained operation
(generator). 82
Figure 33 – Single infeed network model for operate time tests . 83
Figure 34 – Test sequence for radial single infeed network – Restrained operation
(motor) . 86
Figure 35 – Test sequence for radial single infeed network – Unrestrained operation . 89
Figure 36 – Example of distribution of the operate time for one application . 93
Figure 37 – Operate time as a function of the off-nominal frequency values (effective
range is the specified range of ±10 % of nominal frequency) . 95
Figure 38 – Operate time as a function of the off-nominal frequency values (accuracy
range beyond the specified range of ±10 % of nominal frequency . 96
Figure 39 – Double infeed network model for stability tests . 97
Figure 40 – Sequence of fault injection for stability due to external faults (transformer) . 100
Figure 41 – Double infeed network model for stability tests . 101
Figure 42 – Sequence of fault injection for stability due to external faults (REF) . 104
Figure 43 – Double infeed network model for stability tests . 105
Figure 44 – Sequence of fault injection for stability due to external faults (generator) . 108
Figure 45 – Double infeed network model for stability tests . 109
Figure 46 – Sequence of fault injection for stability due to external faults (motor) . 112
SIST EN 60255-187-1:2021
IEC 60255-187-1:2021 © IEC 2021 – 7 –
Figure 47 – Double infeed network model for internal fault preceded by an external fault . 112
Figure 48 – Double infeed network model for internal fault preceded by an external
fault test . 116
Figure 49 – Double infeed network model for internal fault preceded by an external
fault test . 119
Figure 50 – Power transformer inrush current waveform . 124
Figure 51 – Comparison of waveforms . 125
Figure 52 – Connection for the relay when current is injected from Y winding . 126
Figure 53 – Connection for the relay when current is injected from delta winding . 127
Figure 54 – Power transformer overexcitation current waveform injected from Y
winding . 129
Figure 55 – Overexcitation current waveform injected from delta winding . 129
Figure 56 – Comparison of the waveforms injected from Y winding . 130
Figure 57 – Comparison of the waveforms injected from delta winding . 131
Figure 58 – Three-phase overexcitation current waveform injected from Y winding . 132
Figure 59 – Three-phase overexcitation current waveform injected from delta winding . 133
Figure 60 – Test with superimposed harmonics on load – Transformer protection . 133
Figure 61 – Three-phase load current waveform on the Y side of the transformer with
superimposed harmonics . 137
Figure 62 – Three-phase load current waveforms on the delta side of the YNd1
transformer with superimposed harmonics . 137
Figure 63 – Test with superimposed harmonics on load . 138
Figure 64 – Test with superimposed harmonics on load – Restricted earth fault protection . 140
Figure A.1 – Example of a transformer . 144
Figure A.2 – Current vectors . 145
Figure A.3 – Three-phase injection at Y (star/wye) side . 147
Figure A.4 – Phase-phase injection at Y (star/wye) side . 147
Figure A.5 – Single-phase injection at Y (star/wye) side . 148
Figure A.6 – Three-phase injection at delta side . 149
Figure A.7 – Phase-phase injection at delta side . 149
Figure A.8 – Internal single-phase fault at delta side with neutral grounding transformer
in the system . 150
Figure A.9 – Single-phase injection at delta side . 150
Figure A.10 – External single-phase fault at delta side with neutral grounding
transformer inside protected zone . 151
Figure C.1 – Fault positions to be considered for specifying the CT requirements . 160
Figure C.2 – Fault positions to be considered for transformer differential protection. 161
Figure C.3 – Fault positions to be considered for the restricted earth fault protection . 163
Figure C.4 – External fault position to be considered for the generator differential
protection . 165
Figure C.5 – Internal fault position to be considered for the motor differential protection . 166
Figure D.1 – Fault positions to be considered for specifying the CT requirements . 170
Figure D.2 – Additional fault position to be considered in case of summation of currents . 170
Figure E.1 – Transformer differential relay example 1 . 174
Figure E.2 – Transformer differential relay example 2 . 177
Figure F.1 – Network models and fault positions for transformer differential protection . 184
SIST EN 60255-187-1:2021
– 8 – IEC 60255-187-1:2021 © IEC 2021
Figure F.2 – Network models and fault positions for transformer restricted earth fault
protection . 187
Figure F.3 – Excitation characteristic for the high-remanence basic CT . 191
Figure F.4 – Magnetization curve for the high-remanence type basic CT . 193
Figure F.5 – Secondary current at the limit of saturation caused by the AC component
with no remanent flux in the CT . 194
Figure F.6 – Secondary current in case of maximum DC offset . 194
Figure F.7 – Excitation characteristics for non-remanence and high-remanence type
basic CTs . 196
Figure F.8 – Magnetization curve for non-remanence type basic CTs. 197
Figure G.1 – Secondary injected currents for the simulation of a through load of 30 % . 200
Figure G.2 – Pseudo-continuous ramp in the restraining current – Differential current
plane in the time domain . 201
Figure G.3 – Ramp of shots showing differential step change and the time step . 202
Figure G.4 – Ramp of shots with binary search algorithm . 202
Figure I.1 – Graphical definition of fault inception angle . 204
Table 1 – Example of effective and operating ranges of differential protection . 29
Table 2 – Frequencies for steady state accuracy tests when the frequency effective
range is equal to ±5 % of nominal frequency . 36
Table 3 – Frequencies for steady state accuracy tests when the frequency effective
range is larger than ±5 % of nominal frequency . 36
Table 4 – Example frequencies for steady state accuracy tests when the frequency
effective range is narrower than ±5 % of nominal frequency . 36
Table 5 – Test points for differential characteristic basic accuracy . 38
Table 6 – Test lines on the differential characteristic (Figure 10) . 39
Table 7 – Basic characteristic accuracy . 43
Table 8 – Example of start ratios resulting from phase (vector) compensation . 47
Table 9 – Example of start ratios resulting from zero sequence compensation . 50
Table 10 – Test points for rated frequency harmonic restraint . 51
Table 11 – Reporting example of test results for harmonic restraint basic accuracy test . 52
Table 12 – Results of time delay tests . 53
Table 13 – Reported time delay . 53
Table 14 – Results of disengage time for all the tests . 55
Table 15 – Frequencies for dynamic performance tests when the frequency operating
range is equal to ±10 % of nominal frequency . 55
Table 16 – Frequencies for dynamic performance tests when the frequency operating
range is wider than ±10 % of nominal frequency . 55
Table 17 – Example frequencies for dynamic performance tests when the frequency
operating range is narrower than ±10 % of nominal frequency . 56
Table 18 – Double infeed network model . 58
Table 19 – Source impedances for double infeed network model – Restrained
operation (e.g. 50 Hz ± 10 % operating range) . 59
Table 20 – Double infeed network model .
...
SLOVENSKI STANDARD
01-november-2021
Merilni releji in zaščitna oprema - 187-1. del: Funkcijske zahteve za diferenčno
zaščito - Omejena in neomejena diferenčna zaščita motorjev, generatorjev in
transformatorjev
Measuring relays and protection equipment - Part 187-1: Functional requirements for
differential protection - Restrained and unrestrained differential protection of motors,
generators and transformers
Messrelais und Schutzeinrichtungen - Teil 187-1: Funktionsanforderungen für den
stabilisierten und nicht stabilisierten Differentialschutz von Motoren, Generatoren und
Transformatoren
Relais de mesure et dispositifs de protection - Partie 187-1: Exigences fonctionnelles
pour la protection différentielle - Protection différentielle avec et sans caractéristique de
retenue des moteurs, générateurs et transformateurs
Ta slovenski standard je istoveten z: EN IEC 60255-187-1:2021
ICS:
29.120.70 Releji Relays
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD EN IEC 60255-187-1
NORME EUROPÉENNE
EUROPÄISCHE NORM
September 2021
ICS 29.120.70
English Version
Measuring relays and protection equipment - Part 187-1:
Functional requirements for differential protection - Restrained
and unrestrained differential protection of motors, generators
and transformers
(IEC 60255-187-1:2021)
Relais de mesure et dispositifs de protection - Partie 187-1: Messrelais und Schutzeinrichtungen - Teil 187-1:
Exigences fonctionnelles pour la protection différentielle - Funktionsanforderungen für den stabilisierten und nicht
Protection différentielle avec et sans caractéristique de stabilisierten Differentialschutz von Motoren, Generatoren
retenue des moteurs, générateurs et transformateurs und Transformatoren
(IEC 60255-187-1:2021) (IEC 60255-187-1:2021)
This European Standard was approved by CENELEC on 2021-09-01. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2021 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN IEC 60255-187-1:2021 E
European foreword
The text of document 95/465/FDIS, future edition 1 of IEC 60255-187-1, prepared by IEC/TC 95
“Measuring relays and protection equipment” was submitted to the IEC-CENELEC parallel vote and
approved by CENELEC as EN IEC 60255-187-1:2021.
The following dates are fixed:
• latest date by which the document has to be implemented at national (dop) 2022-06-01
level by publication of an identical national standard or by endorsement
• latest date by which the national standards conflicting with the (dow) 2024-09-01
document have to be withdrawn
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
Any feedback and questions on this document should be directed to the users’ national committee. A
complete listing of these bodies can be found on the CENELEC website.
Endorsement notice
The text of the International Standard IEC 60255-187-1:2021 was approved by CENELEC as a
European Standard without any modification.
In the official version, for Bibliography, the following notes have to be added for the standards
indicated:
IEC 61850 (series) NOTE Harmonized as EN 61850 (series)
IEC 61850-7-4:2010 NOTE Harmonized as EN 61850-7-4:2010 (not modified)
IEC 61850-9-2 NOTE Harmonized as EN 61850-9-2
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments)
applies.
NOTE 1 Where an International Publication has been modified by common modifications, indicated by (mod), the
relevant EN/HD applies.
NOTE 2 Up-to-date information on the latest versions of the European Standards listed in this annex is available
here: www.cenelec.eu.
Publication Year Title EN/HD Year
IEC 60255-1 - Measuring relays and protection equipment EN 60255-1 -
- Part 1: Common requirements
IEC 61850-8-1 - Communication networks and systems for EN 61850-8-1 -
power utility automation - Part 8–1:
Specific communication service mapping
(SCSM) - Mappings to MMS (ISO 9506-1
and ISO 9506-2) and to ISO/IEC 8802-3
IEC 61869-2 - Instrument transformers - Part 2: Additional EN 61869-2 -
requirements for current transformers
IEC 61869-9 - Instrument transformers - Part 9: Digital EN IEC 61869-9 -
interface for instrument transformers
IEC 60255-187-1 ®
Edition 1.0 2021-07
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
colour
inside
Measuring relays and protection equipment –
Part 187-1: Functional requirements for differential protection – Restrained and
unrestrained differential protection of motors, generators and transformers
Relais de mesure et dispositifs de protection –
Partie 187-1: Exigences fonctionnelles pour la protection différentielle –
Protection différentielle avec et sans caractéristique de retenue des moteurs,
générateurs et transformateurs
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 29.120.70 ISBN 978-2-8322-1003-9
– 2 – IEC 60255-187-1:2021 © IEC 2021
CONTENTS
FOREWORD . 11
1 Scope . 13
2 Normative references . 14
3 Terms and definitions . 14
4 Specification of the function . 18
4.1 General . 18
4.2 Input energizing quantities/energizing quantities . 19
4.2.1 General . 19
4.2.2 Connections . 19
4.3 Binary input signals. 19
4.4 Functional logic . 22
4.4.1 General . 22
4.4.2 Phase biased differential protection . 22
4.4.3 Biased restricted earth fault protection . 24
4.4.4 Compensation of energizing quantities . 25
4.4.5 Additional restraint or blocking methods . 26
4.5 Binary output signals . 27
4.5.1 General . 27
4.5.2 Start (pick-up) signals . 27
4.5.3 Operate (trip) signals . 27
4.5.4 Other output signals . 27
4.6 Additional influencing functions and conditions . 27
4.6.1 General . 27
4.6.2 Operation during CT saturation . 28
4.6.3 Switch onto fault . 28
4.6.4 Energizing quantity failure (CT supervision) . 28
4.6.5 Off-nominal frequency operation . 28
4.6.6 Geomagnetically induced currents (GIC) . 28
5 Performance specification . 29
5.1 General . 29
5.2 Effective and operating ranges. 29
5.3 Steady state accuracy tests in the effective range . 29
5.3.1 General . 29
5.3.2 Test related to the declared thermal withstand current . 30
5.3.3 Basic characteristic accuracy . 30
5.3.4 Ratio compensation accuracy . 30
5.3.5 Phase (vector) compensation validity . 31
5.3.6 Zero sequence compensation validity . 31
5.3.7 Harmonic restraint basic accuracy . 31
5.3.8 Basic accuracy of time delay settings . 31
5.3.9 Disengage time. 31
5.4 Dynamic performance in operating range . 32
5.4.1 General . 32
5.4.2 Typical operate time . 32
5.4.3 Relay stability for external faults . 32
5.4.4 Relay behaviour for internal fault preceded by an external fault . 33
5.5 Stability during magnetizing inrush conditions . 33
IEC 60255-187-1:2021 © IEC 2021 – 3 –
5.6 Stability during overexcitation conditions . 33
5.7 Presence of harmonics on load . 33
5.8 Performance during saturation of current transformers . 33
5.9 Behaviour of differential protection with digital interface for the energizing
quantities . 34
6 Functional tests . 34
6.1 General . 34
6.2 Test related to the declared thermal withstand current . 35
6.3 Steady state accuracy tests in effective range . 35
6.3.1 General . 35
6.3.2 Basic characteristic accuracy . 37
6.3.3 Ratio (magnitude) compensation accuracy . 44
6.3.4 Phase (vector) compensation validity . 45
6.3.5 Zero sequence compensation validity . 47
6.3.6 Harmonic restraint basic accuracy test under steady state conditions at
nominal frequency . 50
6.3.7 Accuracy related to time delay setting . 52
6.3.8 Determination and reporting of the disengage time . 54
6.4 Dynamic performance tests . 55
6.4.1 General . 55
6.4.2 Operate time for double infeed network model (restrained operation) . 57
6.4.3 Operate time for double infeed network model (unrestrained operation) . 68
6.4.4 Operate time for radial single infeed network model (restrained
operation) . 73
6.4.5 Operate time for radial single infeed network model (unrestrained
operation) . 86
6.4.6 Reporting of typical operate time . 89
6.4.7 Stability for external faults . 95
6.5 Relay behaviour for internal fault preceded by an external fault . 112
6.5.1 General . 112
6.5.2 Application specific considerations: transformer differential . 112
6.5.3 Application specific considerations: biased restricted earth fault . 115
6.5.4 Application specific considerations: generator differential . 119
6.5.5 Reporting . 122
6.6 Stability during inrush conditions. 123
6.6.1 General . 123
6.6.2 Application specific considerations: transformer differential . 123
6.7 Stability during overexcitation conditions . 128
6.7.1 General . 128
6.7.2 Application specific considerations: transformer differential . 128
6.8 Performance with load harmonics . 133
6.8.1 General . 133
6.8.2 Application specific considerations: transformer differential . 133
6.8.3 Application specific considerations: generator or motor differential . 137
6.8.4 Application specific considerations: biased restricted earth fault . 140
6.8.5 Reporting . 142
7 Documentation requirements . 143
7.1 Type test report . 143
7.2 Other user documentation . 143
– 4 – IEC 60255-187-1:2021 © IEC 2021
Annex A (informative) Examples of phase (vector) compensation and zero sequence
compensation schemes . 144
A.1 General . 144
A.2 Y→d conversion . 145
A.2.1 Current conversion . 145
A.2.2 Three-phase fault at Y (star/wye) side . 146
A.2.3 Phase-phase fault at Y (star/wye) side . 147
A.2.4 Single-phase fault at Y (star/wye) side . 147
A.2.5 Three-phase fault at delta side . 148
A.2.6 Phase-phase fault at delta side . 149
A.2.7 Single-phase fault at delta side . 149
A.2.8 Ratio between start currents under different fault types . 152
A.3 d→Y conversion . 152
A.3.1 Current conversion . 152
A.3.2 Three-phase fault at Y (star/wye) side . 153
A.3.3 Phase-phase fault at Y (star/wye) side . 153
A.3.4 Single-phase fault at Y (star/wye) side . 153
A.3.5 Three-phase fault at delta side . 154
A.3.6 Phase-phase fault at delta side . 154
A.3.7 Single-phase fault at delta side . 155
A.3.8 Ratio between start currents under different fault types . 155
Annex B (normative) Calculation of mean, median and mode . 156
B.1 Mean . 156
B.2 Median . 156
B.3 Mode . 156
B.4 Example . 156
Annex C (normative) CT requirements . 157
C.1 General . 157
C.2 Transformer differential protection . 161
C.2.1 General . 161
C.2.2 Fault 1 . 161
C.2.3 Fault 2 . 162
C.2.4 Fault 3 . 162
C.3 Transformer restricted earth fault protection . 163
C.3.1 General . 163
C.3.2 Fault 1 . 163
C.3.3 Fault 2 . 164
C.3.4 Fault 3 . 164
C.4 Generator differential protection . 165
C.4.1 General . 165
C.4.2 Fault 2 . 165
C.4.3 Criteria and additional conditions . 166
C.5 Motor differential protection . 166
C.5.1 General . 166
C.5.2 Fault 1 . 166
C.5.3 Criteria and additional conditions . 166
C.5.4 Start of motor, security case . 167
C.5.5 Criteria and additional conditions . 167
C.6 Reporting . 167
IEC 60255-187-1:2021 © IEC 2021 – 5 –
Annex D (informative) CT saturation and influence on the performance of differential
relays . 168
Annex E (informative) Guidance on dimensioning of CTs for transformer differential
protection . 173
E.1 General . 173
E.2 Example 1 . 174
E.2.1 General . 174
E.2.2 Verification of CT1 – Internal fault . 175
E.2.3 Verification of CT1 – External fault . 175
E.2.4 Verification of CT2 . 176
E.3 Example 2 . 177
E.3.1 General . 177
E.3.2 Dimensioning of CT1 . 178
E.3.3 Dimensioning of CT2 . 179
Annex F (informative) Examples of test procedures to determine CT sizing
requirements for differential protection . 181
F.1 General . 181
F.2 Test data . 183
F.2.1 General . 183
F.2.2 Network model for CT requirement tests for the transformer differential
protection . 183
F.2.3 Network model for CT requirement tests for the transformer restricted
earth fault protection . 187
F.3 CT data and CT models . 189
F.4 Test summary . 197
Annex G (normative) Ramping methods for testing basic characteristic accuracy . 199
G.1 General . 199
G.2 Pre-fault condition . 199
G.3 Pseudo-continuous ramp . 199
G.4 Ramp of shots. 201
Annex H (informative) Example of COMTRADE file for an evolving fault test case . 203
Annex I (normative) Definition of fault inception angle. 204
Bibliography . 205
Figure 1 – Explanatory diagram for start time, operate time and disengage time . 17
Figure 2 – Simplified biased differential functional block diagram . 18
Figure 3 – Primary current reference direction . 21
Figure 4 – Typical restrained element (biased) characteristic . 23
Figure 5 – Typical unrestrained element characteristic . 23
Figure 6 – Example of combined characteristic using restrained and unrestrained
elements . 24
Figure 7 – Basic error of the operating characteristic . 30
Figure 8 – Example of an operating characteristic in the I /I plane with a
DIFF REST
tolerance band . 37
Figure 9 – Test cases for differential characteristic basic accuracy . 39
Figure 10 – Example of a differential characteristic with test lines "a" to "h" . 40
Figure 11 – Machine differential protection . 40
Figure 12 – Test sequence for basic characteristic accuracy . 42
– 6 – IEC 60255-187-1:2021 © IEC 2021
Figure 13 – Machine restricted earth fault protection . 44
Figure 14 – Example for documenting the test results for differential relay
characteristic . 45
Figure 15 – Ratio (magnitude) compensation accuracy test . 46
Figure 16 – Secondary three-phase and double-phase injection for Winding 1
(example) . 47
Figure 17 – Secondary single-phase and three-phase injections for Winding 1
(example) . 49
Figure 18 – Zero sequence current injection on the Y side of the transformer . 50
Figure 19 – Zero sequence current injection on the delta side of the transformer . 50
Figure 20 – Example of a rated frequency harmonic restraint characteristic with
visualization of test lines . 53
Figure 21 – Sequence of events for testing the disengage time . 55
Figure 22 – Double infeed network model for operate time tests . 58
Figure 23 – Test sequence for double infeed network model – Restrained operation
(transformer) . 62
Figure 24 – Double infeed network model for operate time tests . 63
Figure 25 – Test sequence for double infeed network model – Restrained operation
(REF) . 66
Figure 26 – Double infeed network model for operate time tests . 67
Figure 27 – Test sequence for double infeed network model – Restrained operation
(generator). 70
Figure 28 – Test sequence for double infeed network model – Unrestrained operation
(transformer) . 73
Figure 29 – Single infeed network model for operate time tests . 74
Figure 30 – Test sequence radial single infeed network model – Restrained operation . 78
Figure 31 – Single infeed network model for operate time tests . 79
Figure 32 – Test sequence for radial single infeed network – Restrained operation
(generator). 82
Figure 33 – Single infeed network model for operate time tests . 83
Figure 34 – Test sequence for radial single infeed network – Restrained operation
(motor) . 86
Figure 35 – Test sequence for radial single infeed network – Unrestrained operation . 89
Figure 36 – Example of distribution of the operate time for one application . 93
Figure 37 – Operate time as a function of the off-nominal frequency values (effective
range is the specified range of ±10 % of nominal frequency) . 95
Figure 38 – Operate time as a function of the off-nominal frequency values (accuracy
range beyond the specified range of ±10 % of nominal frequency . 96
Figure 39 – Double infeed network model for stability tests . 97
Figure 40 – Sequence of fault injection for stability due to external faults (transformer) . 100
Figure 41 – Double infeed network model for stability tests . 101
Figure 42 – Sequence of fault injection for stability due to external faults (REF) . 104
Figure 43 – Double infeed network model for stability tests . 105
Figure 44 – Sequence of fault injection for stability due to external faults (generator) . 108
Figure 45 – Double infeed network model for stability tests . 109
Figure 46 – Sequence of fault injection for stability due to external faults (motor) . 112
IEC 60255-187-1:2021 © IEC 2021 – 7 –
Figure 47 – Double infeed network model for internal fault preceded by an external fault . 112
Figure 48 – Double infeed network model for internal fault preceded by an external
fault test . 116
Figure 49 – Double infeed network model for internal fault preceded by an external
fault test . 119
Figure 50 – Power transformer inrush current waveform . 124
Figure 51 – Comparison of waveforms . 125
Figure 52 – Connection for the relay when current is injected from Y winding . 126
Figure 53 – Connection for the relay when current is injected from delta winding . 127
Figure 54 – Power transformer overexcitation current waveform injected from Y
winding . 129
Figure 55 – Overexcitation current waveform injected from delta winding . 129
Figure 56 – Comparison of the waveforms injected from Y winding . 130
Figure 57 – Comparison of the waveforms injected from delta winding . 131
Figure 58 – Three-phase overexcitation current waveform injected from Y winding . 132
Figure 59 – Three-phase overexcitation current waveform injected from delta winding . 133
Figure 60 – Test with superimposed harmonics on load – Transformer protection . 133
Figure 61 – Three-phase load current waveform on the Y side of the transformer with
superimposed harmonics . 137
Figure 62 – Three-phase load current waveforms on the delta side of the YNd1
transformer with superimposed harmonics . 137
Figure 63 – Test with superimposed harmonics on load . 138
Figure 64 – Test with superimposed harmonics on load – Restricted earth fault protection . 140
Figure A.1 – Example of a transformer . 144
Figure A.2 – Current vectors . 145
Figure A.3 – Three-phase injection at Y (star/wye) side . 147
Figure A.4 – Phase-phase injection at Y (star/wye) side . 147
Figure A.5 – Single-phase injection at Y (star/wye) side . 148
Figure A.6 – Three-phase injection at delta side . 149
Figure A.7 – Phase-phase injection at delta side . 149
Figure A.8 – Internal single-phase fault at delta side with neutral grounding transformer
in the system . 150
Figure A.9 – Single-phase injection at delta side . 150
Figure A.10 – External single-phase fault at delta side with neutral grounding
transformer inside protected zone . 151
Figure C.1 – Fault positions to be considered for specifying the CT requirements . 160
Figure C.2 – Fault positions to be considered for transformer differential protection. 161
Figure C.3 – Fault positions to be considered for the restricted earth fault protection . 163
Figure C.4 – External fault position to be considered for the generator differential
protection . 165
Figure C.5 – Internal fault position to be considered for the motor differential protection . 166
Figure D.1 – Fault positions to be considered for specifying the CT requirements . 170
Figure D.2 – Additional fault position to be considered in case of summation of currents . 170
Figure E.1 – Transformer differential relay example 1 . 174
Figure E.2 – Transformer differential relay example 2 . 177
Figure F.1 – Network models and fault positions for transformer differential protection . 184
– 8 – IEC 60255-187-1:2021 © IEC 2021
Figure F.2 – Network models and fault positions for transformer restricted earth fault
protection . 187
Figure F.3 – Excitation characteristic for the high-remanence basic CT . 191
Figure F.4 – Magnetization curve for the high-remanence type basic CT . 193
Figure F.5 – Secondary current at the limit of saturation caused by the AC component
with no remanent flux in the CT . 194
Figure F.6 – Secondary current in case of maximum DC offset . 194
Figure F.7 – Excitation characteristics for non-remanence and high-remanence type
basic CTs . 196
Figure F.8 – Magnetization curve for non-remanence type basic CTs. 197
Figure G.1 – Secondary injected currents for the simulation of a through load of 30 % . 200
Figure G.2 – Pseudo-continuous ramp in the restraining current – Differential current
plane in the time domain . 201
Figure G.3 – Ramp of shots showing differential step change and the time step . 202
Figure G.4 – Ramp of shots with binary search algorithm . 202
Figure I.1 – Graphical definition of fault inception angle . 204
Table 1 – Example of effective and operating ranges of differential protection . 29
Table 2 – Frequencies for steady state accuracy tests when the frequency effective
range is equal to ±5 % of nominal frequency . 36
Table 3 – Frequencies for steady state accuracy tests when the frequency effective
range is larger than ±5 % of nominal frequency . 36
Table 4 – Example frequencies for steady state accuracy tests when the frequency
effective range is narrower than ±5 % of nominal frequency . 36
Table 5 – Test points for differential characteristic basic accuracy . 38
Table 6 – Test lines on the differential characteristic (Figure 10) . 39
Table 7 – Basic characteristic accuracy . 43
Table 8 – Example of start ratios resulting from phase (vector) compensation . 47
Table 9 – Example of start ratios resulting from zero sequence compensation . 50
Table 10 – Test points for rated frequency harmonic restraint . 51
Table 11 – Reporting example of test results for harmonic restraint basic accuracy test . 52
Table 12 – Results of time delay tests . 53
Table 13 – Reported time delay . 53
Table 14 – Results of disengage time for all the tests . 55
Table 15 – Frequencies for dynamic performance tests when the frequency operating
range is equal to ±10 % of nominal frequency . 55
Table 16 – Frequencies for dynamic performance tests when the frequency operating
range is wider than ±10 % of nominal frequency . 55
Table 17 – Example frequencies for dynamic performance tests when the frequency
operating range is narrower t
...
Die EN IEC 60255-187-1:2021 ist ein umfassendes Dokument, das die funktionalen Anforderungen für differenzielle Schutzgeräte festlegt, die für die Fehlererkennung in Wechselstrommotoren, Generatoren und Transformatoren konzipiert sind. Der Umfang dieser Norm umfasst die Mindestanforderungen für die funktionale und leistungsbezogene Bewertung von longitudinalen differenziellen Schutzsystemen. Diese Anforderungen sind entscheidend für die Gewährleistung der Sicherheit und Zuverlässigkeit in elektrischen Anlagen. Ein herausragendes Merkmal der EN IEC 60255-187-1:2021 ist die präzise Definition der Einflussfaktoren, die die Genauigkeit unter stationären Bedingungen sowie die Leistungsmerkmale unter dynamischen Bedingungen beeinflussen. Dies ermöglicht eine detaillierte Analyse der Funktionsweise differenzieller Schutzgeräte und führt zu einer verbesserten Fehlersicherheit in der Anwendung. Die Norm bietet auch eine klare Anleitung zur Dokumentation und Veröffentlichung von Leistungstest-Ergebnissen. Dies ist besonders wichtig für Fachleute, die in der Industrie tätig sind, da eine konsistente und transparente Testdokumentation das Vertrauen in das getestete Equipment erhöht und die Implementierung standardisierter Prüfmethoden fördert. Ein weiterer wesentlicher Vorteil der Norm ist ihre Übereinstimmung mit den allgemeinen Strukturen der funktionalen Standards für Schutzrelais (siehe IEC 60255-1xx-Serie). Diese Harmonisierung erleichtert die Integration der EN IEC 60255-187-1:2021 in bestehende Systeme und fördert die konsistente Anwendung in verschiedenen Schutzszenarien. Die signifikanten technischen Änderungen im Vergleich zu IEC 60255-13, wie die detaillierte Beschreibung der Funktionen, der Leistungsanforderungen und der Test- sowie Dokumentationsanforderungen, sorgen für eine moderne und anwendungsorientierte Gestaltung der Norm. Zusammenfassend lässt sich sagen, dass die EN IEC 60255-187-1:2021 nicht nur die Relevanz der differenziellen Schutztechnologie unterstreicht, sondern auch einen wichtigen Beitrag zur Verbesserung der Sicherheitsstandards in der Elektrotechnik leistet. Die Norm ist ein entscheidendes Hilfsmittel für Ingenieure und Techniker, die mit der Entwicklung, Implementierung und Wartung von Schutzsystemen betraut sind.
EN IEC 60255-187-1:2021は、交流モーター、発電機、変圧器における故障を検出するために設計された(縦型)差動保護の機能要件を規定する重要な標準です。この文書は、機能評価および性能評価のための最低限の要件を示しており、保護機器における信頼性を確保するための基盤を提供しています。 この標準の強みは、精度に影響を与える要因を定義している点です。静的条件下における精度や動的条件下での性能特性に関する情報が詳細に示されているため、ユーザーは実際の運用環境における保護器具の動作をより正確に評価することができます。また、性能特性と精度を検証するためのテスト方法論が含まれており、これによりユーザーは実際の性能をしっかりと確認できます。 さらに、IEC 60255-187-1は、IEC 60255-187-2およびIEC 60255-187-3との関連において、IEC 60255-13を廃止・置換する重要な役割を果たしています。その再編成により、保護リレーの機能標準(IEC 60255-1xxシリーズ)に沿った共通の構造に基づく改訂が行われており、ユーザーにとっても使いやすくなっています。 この標準は、モーター、発電機、変圧器の制約された差動保護および非制約型差動保護を扱っており、詳細な機能の説明、性能仕様、テスト及び文書化に関する要件を明確にしているため、幅広い産業分野において重要なリファレンスとなります。全体として、EN IEC 60255-187-1は、保護機器の設計者及びエンジニアにとって必須の標準であり、信頼性と性能に対する厳格な要求を満たすための指針を提供しています。
SIST EN 60255-187-1:2021 표준은 AC 모터, 발전기 및 변압기의 결함 탐지를 위한 (종방향) 차동 보호 기능의 최소 요구 사항을 규정하고 있습니다. 이 표준은 기능과 성능 평가를 위한 기준을 명확히 하며, 성능 테스트 결과를 문서화하고 발표하는 방법을 정의합니다. 이 문서에서는 정상 상태에서의 정확도에 영향을 미치는 요인과 동적 조건에서의 성능 특성을 다룹니다. SIST EN 60255-187-1:2021은 IEC 60255-1xx 시리즈의 기능 표준의 공통 구조에 따라 IEC 60255-13을 크게 개정한 것으로, 모터, 발전기, 변압기의 억제형 및 비억제형 차동 보호에 대한 내용을 포함하고 있습니다. 이와 같은 기술적 변화는 성능 사양, 테스트 및 문서화 요구 사항에 대한 상세한 설명을 포함하여, 보호 릴레이의 기능적 요구 사항을 명확하게 전달합니다. 또한, 이 표준은 성능 특성과 정확성을 검증하기 위한 테스트 방법론을 포함하고 있어, 사용자는 다양한 운영 상태에서 요구되는 신뢰성과 안정성을 확보할 수 있습니다. 전체적으로 SIST EN 60255-187-1:2021은 차동 보호 장치의 기능적 요구 사항을 갖춘 성능 평가 기준으로서 그 중요성이 크며, 정확하고 신뢰할 수 있는 전기 기기의 보호를 위한 중요한 역할을 수행합니다.
The standard EN IEC 60255-187-1:2021 provides a comprehensive framework for the functional requirements essential for the differential protection of motors, generators, and transformers. Its scope is meticulously crafted to define the minimum requirements for functional and performance evaluation of longitudinal differential protection systems, ensuring they are adequately equipped to detect faults in alternating current (AC) machines. One of the key strengths of this standard lies in its rigor in establishing clear methodologies for performance testing. It details the influencing factors that affect accuracy under steady-state conditions, as well as the performance characteristics during dynamic conditions, which is crucial for the reliability of protection systems. This aspect enhances the safety and operational efficiency of electrical equipment, ultimately minimizing downtime and risk of failure. Furthermore, the document addresses the integration of restrained and unrestrained differential protection, which is vital for offering versatility in application. The updates from its predecessor, IEC 60255-13, are significant, as the standard has evolved to align with the common structure of functional standards within the IEC 60255-1xx series. This ensures consistency and clarity in documentation and testing protocols, which are essential for practitioners in the field. The inclusion of performance specifications, testing methodologies, and documentation requirements enriches the standard’s relevance and utility for professionals involved in the design and deployment of protective relay systems. This structured approach not only facilitates compliance with safety regulations but also supports engineers in achieving more precise and reliable outcomes. In summary, EN IEC 60255-187-1:2021 stands out for its detailed directives on the functional requirements for differential protection systems, underscoring its importance in the ongoing advancement of protection equipment for motors, generators, and transformers. The standard embodies a robust resource for industry professionals seeking to enhance their understanding and application of differential protection technologies.
La norme SIST EN IEC 60255-187-1:2021 fournit un cadre essentiel pour l'évaluation fonctionnelle et les performances des équipements de protection différentielle. En se concentrant sur la protection des moteurs, générateurs et transformateurs, elle définit les exigences minimales indispensables pour une détection efficace des défauts dans ces dispositifs à courant alternatif. L'un des points forts de cette norme réside dans sa structure, qui s'aligne avec celle des normes fonctionnelles pour les relais de protection de la série IEC 60255-1xx, assurant ainsi une cohérence dans l'application des méthodes de test et des exigences. Le document précise également les facteurs influençant la précision des mesures dans des conditions stationnaires, ainsi que les caractéristiques de performance en conditions dynamiques. Cela garantit que les utilisateurs puissent non seulement investiguer les performances des équipements, mais aussi que ces derniers répondent aux exigences de sécurité et d'efficacité en toutes circonstances. De plus, l'intégration de méthodologies de test robustes et de critères de documentation favorise une transparence et une reproductibilité qui sont essentielles dans le domaine industriel. Les modifications techniques significatives par rapport à l'ancienne norme IEC 60255-13 témoignent d'un effort de modernisation et d'amélioration continue, dirigeant l'attention vers des exigences plus strictes en matière de spécifications de performance et de documentation de tests. En somme, la norme SIST EN IEC 60255-187-1:2021 s'affirme comme un document de référence incontournable pour tous les professionnels cherchant à garantir des performances optimales des protections différentielles dans les systèmes électriques.










Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...