Surge arresters - Part 5: Selection and application recommendations

NEW!IEC 60099-5:2018 is available as IEC 60099-5:2018 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.IEC 60099-5:2018 provides information, guidance, and recommendations for the selection and application of surge arresters to be used in three-phase systems with nominal voltages above 1 kV. It applies to gapless metal-oxide surge arresters as defined in IEC 60099-4, to surge arresters containing both series and parallel gapped structure – rated 52 kV and less as defined in IEC 60099-6 and metal-oxide surge arresters with external series gap for overhead transmission and distribution lines (EGLA) as defined in IEC 60099-8. In Annex J, some aspects regarding the old type of SiC gapped arresters are discussed. Surge arrester residual voltage is a major parameter to which most users have paid a lot of attention to when selecting the type and rating. Typical maximum residual voltages are given in Annex F. It is likely, however, that for some systems, or in some countries, the requirements on system reliability and design are sufficiently uniform, so that the recommendations of the present standard may lead to the definition of narrow ranges of arresters. The user of surge arresters will, in that case, not be required to apply the whole process introduced here to any new installation and the selection of characteristics resulting from prior practice may be continued. Annexes H and I present comparisons and calculations between old line discharge classification and new charge classification. This third edition cancels and replaces the second edition published in 2013. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition regarding the new surge arrester classification introduced in IEC 60099-4:2014: a) Expanded discussion of comparison between the old and new classification and how to calculate or estimate the corresponding charge for different stresses. b) New annexes dealing with: - Comparison between line discharge classes and charge classification - Estimation of arrester cumulative charges and energies during line switching Keywords: selection and application of surge arrestors, nominal voltages above 1 kV

Überspannungsableiter - Teil 5: Anleitung für die Auswahl und die Anwendung

Parafoudres - Partie 5: Recommandations pour le choix et l'utilisation

NEW!IEC 60099-5:2018 est disponible sous forme de IEC 60099-5:2018 RLV qui contient la Norme internationale et sa version Redline, illustrant les modifications du contenu technique depuis l'édition précédente.

Prenapetostni odvodniki - 5. del: Izbira in priporočila za uporabo

Ta del standarda IEC 60099 vsebuje informacije, smernice in priporočila za izbiro in uporabo prenapetostnih odvodnikov, ki se uporabljajo v trifaznih sistemih z nazivnimi napetostmi nad 1 kV. Uporablja se za prenapetostne odvodnike iz kovinskega oksida brez iskrišč, kot je določeno v standardu IEC 60099-4, za prenapetostne odvodnike s tako skupinsko kot tudi z vzporedno strukturo z iskrišči, ki so ocenjeni na 52 kV in manj, kot je določeno v standardu IEC 60099-6, ter prenapetostne odvodnike iz kovinskega oksida z zunanjim iskriščem skupinske strukture za nadzemni prenos in razdelilna omrežja (EGLA), kot je določeno v standardu IEC 60099-8. V dodatku J so obravnavani nekateri vidiki v zvezi s starejšo vrsto prenapetostnih odvodnikov SiC z iskriščem. Preostala napetost prenapetostnega odvodnika je pomemben parameter, ki mu je večina uporabnikov posvetila veliko pozornosti pri izbiranju vrste in značilnosti. Tipične največje preostale napetosti so podane v dodatku F. Vendar je verjetno, da so pri nekaterih sistemih ali v nekaterih državah zahteve za zanesljivost sistema in zasnova dovolj enotne, da lahko priporočila sedanjega standarda vodijo k določitvi ozkih območij odvodnikov. Uporabnikom prenapetostnih odvodnikov v tem primeru ne bo treba uporabiti celotnega, tukaj predstavljenega postopka za vsako novo namestitev in lahko nadaljujejo z izbiro značilnosti, ki izhaja iz predhodne prakse.
V dodatkih H in I so predstavljene primerjave in izračuni med staro klasifikacijo razelektritve voda in novo klasifikacijo napajanja.

General Information

Status
Published
Publication Date
22-Mar-2018
Withdrawal Date
22-Feb-2021
Technical Committee
Drafting Committee
Current Stage
6060 - Document made available - Publishing
Start Date
23-Mar-2018
Completion Date
23-Mar-2018

Relations

Buy Standard

Standard
EN IEC 60099-5:2018 - BARVE
English language
193 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-maj-2018
1DGRPHãþD
SIST EN 60099-5:2013
3UHQDSHWRVWQLRGYRGQLNLGHO,]ELUDLQSULSRURþLOD]DXSRUDER
Surge arresters - Part 5: Selection and application recommendations
Überspannungsableiter - Teil 5: Anleitung für die Auswahl und die Anwendung
Parafoudres - Partie 5: Recommandations pour le choix et l'utilisation
Ta slovenski standard je istoveten z: EN IEC 60099-5:2018
ICS:
29.240.10 Transformatorske postaje. Substations. Surge arresters
Prenapetostni odvodniki
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD EN IEC 60099-5

NORME EUROPÉENNE
EUROPÄISCHE NORM
March 2018
ICS 29.120.50; 29.240.10 Supersedes EN 60099-5:2013
English Version
Surge arresters - Part 5: Selection and application
recommendations
(IEC 60099-5:2018)
Parafoudres - Partie 5: Recommandations pour le choix et Überspannungsableiter - Teil 5: Anleitung für die Auswahl
l'utilisation und die Anwendung
(IEC 60099-5:2018) (IEC 60099-5:2018)
This European Standard was approved by CENELEC on 2018-02-23. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden,
Switzerland, Turkey and the United Kingdom.

European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2018 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN IEC 60099-5:2018 E

European foreword
The text of document 37/437/FDIS, future edition 3 of IEC 60099-5, prepared by IEC/TC 37 "Surge
arresters" was submitted to the IEC-CENELEC parallel vote and approved by CENELEC as
The following dates are fixed:
• latest date by which the document has to be (dop) 2018-11-23
implemented at national level by
publication of an identical national
standard or by endorsement
(dow) 2021-02-23
• latest date by which the national
standards conflicting with the
document have to be withdrawn
This document supersedes EN 60099-5:2013.

Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.

Endorsement notice
The text of the International Standard IEC 60099-5:2018 was approved by CENELEC as a European
Standard without any modification.
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications

The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments)
applies.
NOTE 1  Where an International Publication has been modified by common modifications, indicated by (mod), the relevant
EN/HD applies.
NOTE 2  Up-to-date information on the latest versions of the European Standards listed in this annex is available here:
www.cenelec.eu.
Publication Year Title EN/HD Year
IEC 60071-1 2006 Insulation co-ordination -- Part 1: EN 60071-1 2006
Definitions, principles and rules
+ A1 2010  + A1 2010
IEC 60071-2 1996 Insulation co-ordination -- Part 2: EN 60071-2 1997
Application guide
IEC 60099-4 2004  Surge arresters -- Part 4: Metal-oxide EN 60099-4 2004
surge arresters without gaps for a.c.
systems
+ A1 2006  + A1 2006
+ A2 2009  + A2 2009
IEC 60099-4 2014 Surge arresters - Part 4: Metal-oxide surge EN 60099-4 2014
arresters without gaps for a.c. systems
IEC 60099-6 2002 Surge arresters -- Part 6: Surge arresters - -
containing both series and parallel gapped
structures - Rated 52 kV and less
IEC 60099-8 2011 Surge arresters -- Part 8: Metal-oxide EN 60099-8 2011
surge arresters with external series gap
(EGLA) for overhead transmission and
distribution lines of a.c. systems above 1
kV
IEC 60507 -  Artificial pollution tests on high-voltage EN 60507 -
ceramic and glass insulators to be used on
a.c. systems
IEC 62271-200 -  High-voltage switchgear and controlgear -- EN 62271-200 -
Part 200: AC metal-enclosed switchgear
and controlgear for rated voltages above 1
kV and up to and including 52 kV
IEC 62271-203 -  High-voltage switchgear and controlgear -- EN 62271-203 -
Part 203: Gas-insulated metal-enclosed
switchgear for rated voltages above 52 kV
IEC/TR 60071-4 -  Insulation co-ordination -- Part 4: - -
Computational guide to insulation co-
ordination and modelling of electrical
networks
IEC/TS 60815-1 2008 Selection and dimensioning of high-voltage - -
insulators intended for use in polluted
conditions - Part 1: Definitions, information
and general principles
IEC 60099-5 ®
Edition 3.0 2018-01
INTERNATIONAL
STANDARD
colour
inside
Surge arresters –
Part 5: Selection and application recommendations

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
ICS 29.120.50; 29.240.10 ISBN 978-2-8322-5075-4

– 2 – IEC 60099-5:2018 © IEC 2018
CONTENTS
FOREWORD . 9
1 Scope . 11
2 Normative references . 11
3 Terms and definitions . 12
4 General principles for the application of surge arresters . 21
5 Surge arrester fundamentals and applications issues . 22
5.1 Evolution of surge protection equipment . 22
5.2 Different types and designs and their electrical and mechanical
characteristics . 23
5.2.1 General . 23
5.2.2 Metal-oxide arresters without gaps according to IEC 60099-4 . 24
5.2.3 Metal-oxide surge arresters with internal series gaps according to
IEC 60099-6 . 34
5.2.4 Externally gapped line arresters (EGLA) according to IEC 60099-8. 36
5.2.5 Application considerations . 39
6 Insulation coordination and surge arrester applications. 52
6.1 General . 52
6.2 Insulation coordination overview . 52
6.2.1 General . 52
6.2.2 IEC insulation coordination procedure . 53
6.2.3 Overvoltages . 53
6.2.4 Line insulation coordination: Arrester Application Practices . 59
6.2.5 Substation insulation coordination: Arrester application practices . 64
6.2.6 Insulation coordination studies. 68
6.3 Selection of arresters . 70
6.3.1 General . 70
6.3.2 General procedure for the selection of surge arresters . 70
6.3.3 Selection of line surge arresters, LSA . 84
6.3.4 Selection of arresters for cable protection . 93
6.3.5 Selection of arresters for distribution systems – special attention . 95
6.3.6 Application and coordination of disconnectors . 96
6.3.7 Selection of UHV arresters . 98
6.4 Standard and special service conditions . 99
6.4.1 Standard service conditions . 99
6.4.2 Special service conditions . 99
7 Surge arresters for special applications . 103
7.1 Surge arresters for transformer neutrals . 103
7.1.1 General . 103
7.1.2 Surge arresters for fully insulated transformer neutrals . 103
7.1.3 Surge arresters for neutrals of transformers with non-uniform insulation . 103
7.2 Surge arresters between phases . 104
7.2.1 General . 104
7.2.2 6-arrester arrangement . 104
7.2.3 4-arrester (Neptune) arrangement . 104
7.3 Surge arresters for rotating machines . 105
7.4 Surge arresters in parallel . 106

IEC 60099-5:2018 © IEC 2018 – 3 –
7.4.1 General . 106
7.4.2 Combining different designs of arresters . 107
7.5 Surge arresters for capacitor switching . 107
7.6 Surge arresters for series capacitor banks . 109
8 Asset management of surge arresters . 110
8.1 General . 110
8.2 Managing surge arresters in a power grid . 110
8.2.1 Asset database . 110
8.2.2 Technical specifications . 110
8.2.3 Strategic spares . 110
8.2.4 Transportation and storage . 111
8.2.5 Commissioning . 111
8.3 Maintenance . 111
8.3.1 General . 111
8.3.2 Polluted arrester housing . 112
8.3.3 Coating of arrester housings . 112
8.3.4 Inspection of disconnectors on surge arresters . 112
8.3.5 Line surge arresters . 112
8.4 Performance and diagnostic tools . 112
8.5 End of life . 113
8.5.1 General .
...