IEC TR 61869-100:2017/COR1:2023 – 1 –
© IEC 2023
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
IEC 61869-100
Edition 1.0 2017-01
INSTRUMENT TRANSFORMERS –
Part 100: Guidance for application of current transformers in power system protection
CO RRI G E NDUM 1
6.1.3.3 Range 1: 0 ≤ t' ≤ t
al tf,max
Replace the following first and second formulae and the key:
"At this point in time, the following condition is fulfilled:
sin (ω t +γ− )=−1
tf,max
This equatio
...
This May Also Interest You
IEC 61869-1:2023 is applicable to newly manufactured instrument transformers intended for applications where the nominal voltage is higher than 1 kV AC or 1,5 kV DC, with an analogue or a digital secondary signal for measuring, protection and control purposes, with rated frequencies from 15 Hz to 400 Hz, or for DC applications.
The general requirements for instrument transformers for applications in LV systems (nominal voltage ≤ 1 kV AC or ≤ 1,5 kV DC) are covered by IEC 61869-201.
This part of IEC 61869 is a product family standard and covers general requirements only. For each type of instrument transformer, the product standard is composed of this document and the relevant specific product standard.
This part of IEC 61869 contains the requirements for the limits of the errors both for analogue and digital secondary signal. The other characteristics of a digital interface for instrument transformer are standardised in IEC 61869-9 as an application of the IEC 61850 horizontal standard series, covering communication networks and systems for power utility automation.
This part of IEC 61869 considers bandwidth requirements. The accuracy requirements on harmonics and requirements for the anti-aliasing filter are specified in 5.7.
IEC 61869-1:2023 cancels and replaces the first edition published in 2007 and IEC 61869-6:2016. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous edition:
a) merger with IEC 61869-6:2016;
b) new scope: equipment for HV applications with a nominal voltage > 1 kV AC or 1,5 kV DC;
c) new classification of some special tests as type tests or routine test;
d) additional type tests, additional special tests and new clause for commissioning tests;
e) new annexes E, F, G and I.
- Standard285 pagesEnglish and French languagesale 15% off
- Standard10 pagesEnglish and French languagesale 15% off
IEC 61869-99:2022 contains the glossary of specific terminology and definitions used in the field of instrument transformers within the various parts of the series. Unless it is otherwise specified, in this document all periodic electrical quantities are understood to be RMS values.
The contents of the corrigendum of January 2023 have been included in this copy.
- Standard109 pagesEnglish and French languagesale 15% off
- Standard3 pagesEnglish languagesale 15% off
IEC 61869-13:2021 is a product standard and covers only additional requirements for stand-alone merging units (SAMUs) used for AC applications having rated frequencies from 15 Hz to 100 Hz. The digital output format specification is not covered by this document; it is standardized in IEC 61869-9 as an application of IEC 61850, which specifies the power utility communication architecture.
This document covers SAMUs having standardized analogue inputs (for example: 1 A, 5 A, 3,25 V / √3 or 100 V / √3) provided by instrument transformers compliant with relevant product standards (e.g. IEC 61869-2 to IEC 61869-5, IEC 61869-7, IEC 61869-8, IEC 61869-10, IEC 61869-11, IEC 60044-1 to IEC 60044-6, IEC 60185, IEC 60186, IEEE C57.13), and aims to convert them to the digital output compliant with IEC 61869-9. Other input and output types are outside the scope of this document. Appropriate SAMU functionality can be combined with switchgear controller functionality defined in IEC 62271-3 or other IED functionality defined in IEC 60255 (all parts).
Cyber security requirements are outside the scope of this document and are covered by the IEC 62351 series.
IEC 61869-13:2021 is to be used in conjunction with IEC 61869-9:2016, Digital interface for instrument transformers, and IEC 618696:2016, Additional general requirements for low-power instrument transformers, which, in turn, are based on IEC 61869-1:2007, General requirements.
- Standard141 pagesEnglish and French languagesale 15% off
IEC 61869-14:2018 provides all requirements specific to current transformers to be used in DC applications (DCCTs), whatever the technology used. The output signal can be analogue or digital.
It is applicable to newly manufactured current transformers used for measuring, protection and/or control applications in DC power systems with a rated voltage above 1,5 kV.
The general configuration of a single-pole low-power instrument transformer is described in Figure 601 of IEC 61869-6:2016.
The DCCTs intended for current measurement in the transistor branch of the VSC valve (referred to as CT4a and CT4b in Figure 1403 and Table 1402) are not covered by this document, and will be considered in a future revision.
IEC 61869-14:2018 applies to current transformers intended to be used in DC applications with at least one of the following functions:
• measure DC current (with significant harmonics);
• withstand DC voltage.
Depending on the position on the DC system, different kinds of application exist, which are briefly described below, together with the approximate voltage or current wave shape.
- Standard7 pagesEnglish languagesale 10% offe-Library read for×1 day
- Standard85 pagesEnglish and French languagesale 15% off
IEC 61869-15:2018 provides all requirements specific to voltage transformers to be used in DC applications (DCVTs), whatever the technology used. The output signal can be analogue or digital.
It is applicable to newly manufactured voltage transformers used for measuring, protection and/or control applications in DC power systems with a rated voltage above 1,5 kV.
This document covers passive voltage dividers as well as active voltage transformers, used for measurement, control and protection.
The general configuration of a single-pole low-power instrument transformer is described in Figure 601 of IEC 61869-6:2016.
IEC 61869-15:2018 applies to voltage transformers (VT) intended to be used in DC applications with the following functions:
• measure DC voltage (with significant harmonics);
• withstand DC voltage.
Two main technologies of DC converters exist today: LCC and VSC
• Line-commutated converters (LCC) are based on thyristor converters. They are characterized by a single direction of current flow, and a voltage polarity reversal possibility. Significant voltage and current harmonics exist up to frequencies of about 3 kHz to 4 kHz.
• Voltage source converters (VSC) are based on transistor converters. They are characterized by a bi-directional current flow and a single voltage polarity. Voltage and current harmonics exist up to frequencies of about 20 kHz.
- Standard71 pagesEnglish and French languagesale 15% off
IEC 61869-10:2017 is a product standard and covers only additional requirements for low-power passive current transformers. The product standard for low-power passive current transformers comprises IEC 61869-1, together with IEC 61869-6 and this document with specific requirements.
This document is applicable to newly manufactured low-power passive current transformers with analogue output for use with electrical measuring instruments or electrical protective devices having a rated frequency from 15 Hz to 100 Hz.
This document covers low-power passive current transformers used for measurement or protection and multi-purpose low-power passive current transformers used for both measurement and protection.
This first edition of IEC 61869-10, together with IEC 61869-1, IEC 61869-6, IEC 61869-8 and IEC 61869-9, cancels and replaces the first edition of IEC 60044-8, published in 2002. This edition constitutes a technical revision.
The technical changes concern IEC TC 38's decision to restructure the whole set of stand-alone standards in the IEC 60044 series and transform it into a new set of standards composed of general requirements documents and specific requirements documents.
- Standard87 pagesEnglish and French languagesale 15% off
IEC 61869-11:2017 is a product standard and covers only additional requirements for low-power passive voltage transformers (passive LPVT). The product standard for low-power passive voltage transformers is composed of IEC 61869-1, along with IEC 61869-6 and this document with specific requirements.
This document is applicable to newly manufactured low-power passive voltage transformers with analogue output having rated frequencies from 15 Hz to 100 Hz for use with electrical measuring instruments or electrical protective devices.
This document covers low-power passive voltage transformers used for measurement or protection and low-power passive voltage transformers used for both measurement and protection.
Low-power passive voltage transformers have analogue output only (for digital output or for technology using any kind of active electronic components refer to future IEC 61869-7). Such low-power passive voltage transformers can include the secondary signal cable (transmitting cable). The secondary voltage of the low-power passive voltage transformer is proportional to the primary voltage. Derivative output signals are not within the scope of this document.
This first edition of IEC 61869-11, together with IEC 61869-1 and IEC 61869-6, cancels and replaces the relevant clauses or subclauses of the first edition of IEC 60044-7, published in 1999 and the first edition of IEC 60044-8, published in 2002. This edition constitutes a technical revision.
The contents of the Interpretation Sheet 1 of September 2021 have been included in this copy.
- Standard67 pagesEnglish and French languagesale 15% off
IEC TR 61869-100:2017(E) is applicable to inductive protective current transformers meeting the requirements of the IEC 61869-2 standard.
It may help relay manufacturers, CT manufacturers and project engineers to understand how a CT responds to simplified or standardized short circuit signals. Therefore, it supplies advanced information to comprehend the definition of inductive current transformers as well as their requirements.
The document aims to provide information for the casual user as well as for the specialist. Where necessary, the level of abstraction is mentioned in the document. It also discusses the question about the responsibilities in the design process for current transformers.
The contents of the corrigendum of October 2023 have been included in this copy.
- Technical report135 pagesEnglish languagesale 15% off