ISO 5149-3:2026
(Main)Refrigerating systems and heat pumps — Safety and environmental requirements — Part 3: Installation site, classification and selection criteria
- Abstract
This document specifies: the classification and selection criteria applicable to refrigerating systems; safety requirements for the installation site of refrigerating systems and their ancillary components. These classification and selection criteria are used in ISO 5149-2 and ISO 5149-4. This document is applicable to: refrigerating systems, stationary or mobile, of all sizes, except vehicle air conditioning systems covered by a specific product standard, e.g. ISO 13043 and SAE J 639; secondary cooling or heating systems; the location of the refrigerating systems; parts replaced and components added after publication of this document if they are not identical in function and in capacity. This document is applicable: to new refrigerating systems, extensions or modifications of already existing systems; for used systems, being transferred to and operated on another site; in the case of the conversion of a system for another refrigerant. This document is only applicable to systems containing refrigerants which have a safety group classification and are listed in ISO 817.
- Status
- Published
- Publication Date
- 04-Nov-2026
- Current Stage
- 6060 - International Standard published - 60 Publication
- Start Date
- 05-Nov-2026
- Due Date
- 05-Nov-2026
- Completion Date
- 05-Nov-2026
ISO 5149-3:2026 is an ISO International Standard for refrigerating systems and heat pumps. It specifies classification and selection criteria for refrigerating systems, plus safety requirements for the installation site and ancillary components, for systems using refrigerants listed in ISO 817. The document supports site layout, charge-limit calculations, alarms, detection, and machinery-room design for designers, installers, owners, and maintenance personnel.
What does ISO 5149-3:2026 specify?
ISO 5149-3:2026 covers where refrigerating equipment may be located, how locations and access are classified, and how refrigerant quantity limits are determined for safety purposes. It also sets requirements for machinery rooms, ventilation, electrical installations, alarms, detection systems, site notices, inspections, heat sources, and heat-transfer fluids.
The standard applies to stationary or mobile refrigerating systems of all sizes, secondary cooling or heating systems, and to new systems, extensions, modifications, transferred used systems, and systems converted to another refrigerant. It is also used when parts are replaced or components are added after publication, if they are not identical in function and capacity.
The document is organized into clauses 1 to 15. Clauses 4 to 7 cover location, classification, room volume, and charge limits; clauses 8 to 12 cover machinery rooms, additional measures, electrical installations, alarms, and detection; clauses 13 to 15 cover instructions, inspections, heat sources, and heat-transfer fluid.
| Annex | What it covers |
|---|---|
| Annex A | Examples of system location and access category classification |
| Annex B | Safety classification and refrigerant information used in calculations |
| Annex C | Determination of the releasable charge |
| Annex D | Determination of the release height |
| Annex E | Determination of estimated height reached by airflow |
| Annex F | Charge limit determination using a surrounding concentration test |
What are the key requirements of ISO 5149-3:2026?
ISO 5149-3:2026 is built around risk-based classification and charge-limiting methods. The most important practical point is that the same refrigerating system can lead to different requirements depending on where it is installed, who can access the space, and which refrigerant is used.
Clause 5 classifies each system by location, access, and refrigerant type. There are four location classes, three access categories, and refrigerants are classified by toxicity and flammability. In practice, this determines which later charge-limit and site-protection rules apply.
Clause 6 defines the room volume and floor area used in charge calculations. The calculation space is the space into which refrigerant can leak, with deductions for significant equipment and inventory and special rules for false ceilings and connected spaces. This matters because a smaller effective volume usually drives a lower allowable charge.
Clause 7 gives two safety concepts: Path A and Path B. Path A limits the refrigerant charge directly through toxicity and flammability calculations, while Path B allows safety by other measures. If Path A is used, the releasable charge from Annex C may replace the total charge in the formulas, which is important when only part of the system can escape during a leak.
Clause 7 ties toxicity limits to the toxicity factor (TF) and flammability limits to the lower flammability limit (LFL). The document takes the greater of the relevant toxicity values for TF, then applies flammability cap factors for class 2L, 2, and 3 refrigerants. This means the permitted charge is controlled by the worst relevant hazard, not by a single generic limit.
Clauses 7.6 and 7.8 add ventilation and below-ground rules. Natural or mechanical ventilation can increase the allowable charge, but only under defined conditions. Below-ground spaces with heavier-than-air refrigerants need extra restrictions, such as independent ventilation and minimum air-exchange rates.
Clause 8 sets machinery-room safeguards. These include restricted occupancy, outdoor venting of released refrigerant, limits on open flame and storage, remote emergency switching, lighting, accessibility, sealed penetrations, and ventilation. For flammable refrigerants and R-717, additional measures apply, so the room design must be matched to the refrigerant.
Clauses 10 to 12 require compatible electrical installations, alarms, and detection systems. The electrical arrangement must allow independent shutdown, electrical equipment in flammable-refrigerant rooms must suit the classified zones, and detection systems must be placed where refrigerant is likely to accumulate. In practice, these clauses link the refrigerant hazard to the control and warning systems on the site.
Clauses 13 to 15 cover operational readiness and site hazards. The site must have instructions, warning notices, visual checks before handover, routine maintenance checks, controls for heat sources, and requirements for heat-transfer fluids. This is the part that turns the installation design into something that can be operated and maintained safely.
What terms does ISO 5149-3:2026 define?
- Acute toxicity exposure limit (ATEL) - the toxicity limit value used with oxygen deprivation considerations to establish the toxicity factor for a refrigerant.
- Oxygen deprivation limit (ODL) - the oxygen-related limit value used with ATEL when determining the toxicity factor.
- Toxicity factor (TF) - the value used in charge-limit calculations, taken as the greater of ATEL/ODL or the practical limit.
- Lower flammability limit (LFL) - the flammability threshold used for cap factors, ventilation calculations, and acceptance criteria.
- Concentration limit (CL) - the concentration boundary used in the advanced charge-limit method in Clause 7.5.
- Concentration limit with additional measures (CLAM) - the higher concentration boundary used when additional measures are part of the safety concept.
- Releasable charge - the amount of refrigerant expected to be released during a leak, determined by test or calculation in Annex C.
- Safety data sheet (SDS) - the document used in Clause 15 to identify hazards and exposure controls for a heat-transfer fluid.
Who uses ISO 5149-3:2026?
ISO 5149-3:2026 is used by refrigeration and heat pump designers, equipment manufacturers, installers, commissioning teams, building owners, facility managers, and maintenance or repair personnel. It is also relevant to risk assessors, safety engineers, and inspectors who need to classify a site, set charge limits, and check machinery-room or alarm provisions.
The document is especially relevant in supermarkets, cold stores, food processing plants, hospitals, schools, offices, industrial facilities, and other buildings where refrigerating equipment may be in occupied spaces, machinery rooms, roofs, car parks, or fenced outdoor compounds.
What changed in ISO 5149-3:2026 from the previous edition?
ISO 5149-3:2026 cancels and replaces ISO 5149-3:2014 and incorporates Amendment ISO 5149-3:2014/Amd 1:2021. The foreword states four main changes:
- integration of Clause 5 to Clause 8 and Annex A of ISO 5149-1:2014 into this document
- introduction of Path A and Path B safety concepts and related safety provisions
- introduction of the releasable charge concept
- partial alignment with EN 378-3
Which standards are used with ISO 5149-3:2026?
| Reference | What it contributes |
|---|---|
| ISO 817:2024 | Refrigerant designation, safety classification, and refrigerant data used in Annex B |
| ISO 5149-1 | Vocabulary used throughout the series |
| ISO 5149-2:2026 | Design, construction, testing, marking, and documentation, including selected design features referenced here |
| ISO 5149-4 | Operation, maintenance, repair, and recovery, including emergency procedures and upkeep |
| ISO 12100 | Risk assessment and risk reduction principles |
| ISO 13850 | Emergency stop function principles |
| ISO 22712 | Competence of personnel |
| IEC 60079-10-1 | Area classification for explosive gas atmospheres |
| IEC 60204-1 | Electrical equipment of machines and main power connection requirements |
| IEC 60364-1 | Fundamental principles for low-voltage electrical installations |
| IEC 60364-5 | Selection and erection of electrical equipment in buildings |
| IEC 62990-3 | Gas detector performance requirements and test methods |
What does the ISO 5149-3:2026 document contain?
The document contains site-classification rules, charge-limit calculation methods, machinery-room requirements, electrical and alarm provisions, and requirements for detection systems. It also includes inspection and maintenance checks for the site, plus special rules for heat sources and heat-transfer fluids.
Its annexes provide practical support: examples of classification, refrigerant safety data, releasable-charge methods, release-height and airflow-height calculations, and a surrounding-concentration test for charge limits. The annexes are used for design review, installation planning, and test-based verification of safety limits.
Relations
- Effective Date
- 19-Nov-2022
- Effective Date
- 19-Nov-2022
Get Certified
Connect with accredited certification bodies for this standard

DNV
DNV is an independent assurance and risk management provider.

Lloyd's Register
Lloyd's Register is a global professional services organisation specialising in engineering and technology.

DNV Energy Systems
Energy and renewable energy certification.
Sponsored listings
Frequently Asked Questions
ISO 5149-3:2026 is a standard published by the International Organization for Standardization (ISO). Its full title is "Refrigerating systems and heat pumps — Safety and environmental requirements — Part 3: Installation site, classification and selection criteria". This standard covers: This document specifies: the classification and selection criteria applicable to refrigerating systems; safety requirements for the installation site of refrigerating systems and their ancillary components. These classification and selection criteria are used in ISO 5149-2 and ISO 5149-4. This document is applicable to: refrigerating systems, stationary or mobile, of all sizes, except vehicle air conditioning systems covered by a specific product standard, e.g. ISO 13043 and SAE J 639; secondary cooling or heating systems; the location of the refrigerating systems; parts replaced and components added after publication of this document if they are not identical in function and in capacity. This document is applicable: to new refrigerating systems, extensions or modifications of already existing systems; for used systems, being transferred to and operated on another site; in the case of the conversion of a system for another refrigerant. This document is only applicable to systems containing refrigerants which have a safety group classification and are listed in ISO 817.
This document specifies: the classification and selection criteria applicable to refrigerating systems; safety requirements for the installation site of refrigerating systems and their ancillary components. These classification and selection criteria are used in ISO 5149-2 and ISO 5149-4. This document is applicable to: refrigerating systems, stationary or mobile, of all sizes, except vehicle air conditioning systems covered by a specific product standard, e.g. ISO 13043 and SAE J 639; secondary cooling or heating systems; the location of the refrigerating systems; parts replaced and components added after publication of this document if they are not identical in function and in capacity. This document is applicable: to new refrigerating systems, extensions or modifications of already existing systems; for used systems, being transferred to and operated on another site; in the case of the conversion of a system for another refrigerant. This document is only applicable to systems containing refrigerants which have a safety group classification and are listed in ISO 817.
ISO 5149-3:2026 is classified under the following ICS (International Classification for Standards) categories: 27.080 - Heat pumps; 27.200 - Refrigerating technology. The ICS classification helps identify the subject area and facilitates finding related standards.
ISO 5149-3:2026 has the following relationships with other standards: It is inter standard links to ISO 5149-3:2014/Amd 1:2021, ISO 5149-3:2014. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
ISO 5149-3:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
Contents
- 1 Scope
- 2 Normative references
- 3 Terms and definitions
- 4 Location of refrigerating equipment
- 4.1 General
- 4.2 Refrigerating equipment located in the open air
- 4.3 Refrigerating equipment located in a machinery room
- 4.4 Refrigerating equipment located in the occupied space
- 4.5 Refrigerating equipment located in an area not designated as an occupied space or a
- 4.6 Refrigerating equipment located in a class IV ventilated enclosure within an occupied
- 4.7 Piping duct or shaft
- 5 Classification
- 5.1 General
- 5.2 Classification of system locations
- 5.3 Classification of access to occupied spaces, machinery rooms and open air
- 5.4 Classification of refrigerants
- 6 Determining the room volume and room area used in refrigerant quantity limit
- 6.1 General
- 6.2 Space volume and area calculations
- 7 Setting refrigerant quantity limits
- 7.1 General
- 7.2 Defining toxicity and flammability classes, toxicity factor, lower flammability limit and
- 7.3 Establishing the refrigerant quantity limit
- 7.4 Refrigerant charge limit calculation for Path A safety concept
- 7.5 Advanced methods for charge limit based on both flammability and toxicity
- 7.6 Refrigerant charge limit with ventilation
- 7.7 Charge limit determined by test
- 7.8 Additional requirements for spaces below ground
- 7.9 Ensuring safety by other methods – Path B safety concept
- 8 Machinery rooms
- 8.1 Occupancy of machinery rooms and separate refrigeration machinery rooms
- 8.2 Venting from or through the machinery room
- 8.3 Combustion equipment and air compressors
- 8.4 Open flame
- 8.5 Storage
- 8.6 Remote emergency switch
- 8.7 Exterior openings of the machinery room
- 8.8 Piping and ducting
- 8.9 Normal lighting
- 8.10 Emergency lighting
- 8.11 Dimensions and accessibility
- 8.12 Doors, walls and ducts
- 8.13 Ventilation
- 8.14 Additional measures for flammable refrigerants
- 9 Requirements for additional measures
- 9.1 General
- 9.2 Potential leak points in piping
- 9.3 Ventilation
- 9.4 Safety shut-off valves
- 10 Electrical installations
- 10.1 General requirements
- 10.2 Main power supply
- 10.3 Electrical equipment in machinery rooms in which a refrigerating system contains
- 11 Safety alarms
- 11.1 General
- 11.2 Alarm system power
- 11.3 Alarm system warning
- 11.4 Additional alarm system requirements for R-717 systems with charges above 4 500 kg
- 12 Detection systems
- 12.1 General
- 12.2 Location of detection systems
- 12.3 Function of the detection systems
- 12.4 Type and performance of a detection system
- 12.5 Installation
- 13 Instruction manuals, notices and inspections
- 13.1 Instruction manual
- 13.2 Warning notice
- 13.3 Visual inspection of site
- 13.4 Maintenance of the site
- 14 Heat sources and temporary high temperatures located at the site
- 15 Heat-transfer fluid
- 15.1 General
- 15.2 Ingestion
- 15.3 Water and soil contamination
- 15.4 Personal exposure (toxicity)
- 15.5 Pressure
- 15.6 Marking
- 15.7 Freezing point
- 15.8 Decomposition point
- 15.9 Flash point
1 Scope
This document specifies:
- the classification and selection criteria applicable to refrigerating systems;
- safety requirements for the installation site of refrigerating systems and their ancillary components. These classification and selection criteria are used in ISO 5149-2 and ISO 5149-4. This document is applicable to:
a) refrigerating systems, stationary or mobile, of all sizes, except vehicle air conditioning systems covered by a specific product standard, e.g. ISO 13043 and SAE J 639; b) secondary cooling or heating systems; c) the location of the refrigerating systems; d) parts replaced and components added after publication of this document if they are not identical in function and in capacity.
This document is applicable:
- to new refrigerating systems, extensions or modifications of already existing systems;
- for used systems, being transferred to and operated on another site;
- in the case of the conversion of a system for another refrigerant. This document is only applicable to systems containing refrigerants which have a safety group classification and are listed in ISO 817.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. ISO 817:2024, Refrigerants — Designation and safety classification ISO 5149-1, Refrigerating systems and heat pumps — Safety and environmental requirements — Part 1:
Vocabulary ISO 5149-2:2026, Refrigerating systems and heat pumps — Safety and environmental requirements — Part 2:
Design, construction, testing, marking and documentation
ISO 5149-3:2026(en) ISO 5149-4, Refrigerating systems and heat pumps — Safety and environmental requirements — Part 4:
Operation, maintenance, repair and recovery ISO 12100, Safety of machinery — General principles for design — Risk assessment and risk reduction ISO 13850, Safety of machinery — Emergency stop function — Principles for design ISO 22712, Refrigerating systems and heat pumps — Competence of personnel IEC 60079-10-1, Explosive atmospheres — Part 10-1: Classification of areas — Explosive gas atmospheres IEC 60204-1, Safety of machinery — Electrical equipment of machines — Part 1: General requirements IEC 60364-1, Low-voltage electrical installations — Part 1: Fundamental principles, assessment of general characteristics, definitions IEC 60364-5, Electrical installations of buildings — Part 5: Selection and erection of electrical equipment IEC 62990-3, Workplace atmospheres — Part 3. Gas detectors. Electrical apparatus for the detection and measurement of oxygen — Performance requirements and test methods
3 Terms and definitions
For the purposes of this document, the terms and definitions given in ISO 5149-1 apply. ISO and IEC maintain terminology databases for use in standardization at the following addresses:
- ISO Online browsing platform: available at https:// www .iso .org/ obp - IEC Electropedia: available at https:// www .electropedia .org/ For the user's convenience, the list of abbreviated terms used in this document is given in Table 1. Table 1 — Additional abbreviated terms Abbreviated term Description ATEL acute toxicity exposure limit CL concentration limit CLAM concentration limit with additional measures GWP global warming potential LFL lower flammability limit ODL oxygen deprivation limit ppm parts per million by volume RV room volume SDS safety data sheet TF toxicity factor
4 Location of refrigerating equipment
4.1 General
Refrigerating equipment can be sited outside the building in the open air, in a designated machinery room, in occupied areas or in areas not designated as occupied or as a machinery room. The refrigerating equipment can be contained in a class IV ventilated enclosure provided by the manufacturer.
ISO 5149-3:2026(en)
4.2 Refrigerating equipment located in the open air
Refrigerating equipment sited in the open air shall be positioned to avoid refrigerant flowing from the equipment into the building or otherwise endangering people and property. NOTE Possible methods to achieve this include one or more of the following:
- location of the refrigerant-containing part of the refrigeration system (except piping) at least 6 m away from any opening to the building;
- for refrigerants heavier than air, use of barriers of at least 1 m height between the system location and the inlet ventilation opening to block the flow of leaked or vented refrigerant;
- for refrigerants heavier than air, location of the inlet ventilation opening at least 1 m above the level at which the system is installed.
The discharge opening from safety relief devices or associated discharge pipes shall be positioned according to the manufacturer's instructions and oriented to direct vented refrigerant away from inlet ventilation openings. Alternatively, for flammable refrigerants, the distance to the inlet ventilation opening may be determined in accordance with IEC 60079-10-1.
4.3 Refrigerating equipment located in a machinery room
When a machinery room is chosen as the location for refrigerating equipment, it shall meet the requirements specified in Clause 8.
A risk assessment based on the safety concept for the refrigerating system (as determined by the manufacturer and including the charge and safety classification of the refrigerant used) shall be conducted to determine whether it is necessary to place the refrigerating system in a separate refrigeration machinery room.
NOTE Where housing around refrigerating equipment is sufficiently large for people to enter, the housing is considered as a machinery room and requirements for such rooms apply.
4.4 Refrigerating equipment located in the occupied space
The requirements shall be as specified in Clause 5, Clause 6 and Clause 7.
4.5 Refrigerating equipment located in an area not designated as an occupied space or a
machinery room For any equipment located in a space that cannot be sealed from an occupied space, the location shall be treated as an occupied space in accordance with 4.4.
Where compressors or pressure vessels are located in an indoor space that is sealed from any occupied space, the location shall be treated as an occupied space in accordance with 4.4 or a machinery room in accordance with Clause 8.
Where equipment (not including compressors and pressure vessels) containing non-permanent joints is located in an unoccupied space that is sealed from any occupied space, the requirements of Clause 8 shall apply. If mechanical ventilation is required according to 8.13, ventilation shall be from an extractor hood
positioned adjacent to the equipment and the ventilation rate shall be more than 0,05 m /s per ventilator. In the case of equipment subject to adverse conditions, for example severe vibration or a corrosive
atmosphere, the ventilation rate shall be more than 0,5 m /s per extractor hood. If mechanical ventilation is required, refrigerant gas detectors shall activate the ventilation in accordance with the requirements given in Clause 12.
NOTE 1 Severe vibration can be caused by unbalanced dynamic loads or hydraulic shock during defrost operation.
NOTE 2 The ventilation rate is deemed sufficient to ventilate a volume of 18 m .
ISO 5149-3:2026(en)
4.6 Refrigerating equipment located in a class IV ventilated enclosure within an occupied
space The class IV ventilated enclosure containing the refrigerating equipment shall be installed in accordance with the design specified in ISO 5149-2:2026, 6.2.17. The class IV ventilated enclosure shall have a sufficient make up air source to replace any exhausted air. The ventilation from the enclosure shall be to the open air or to a room having a minimum volume as specified in 7.3 for an occupied space.
4.7 Piping duct or shaft
Where hand-operated shut-off devices are mounted in a piping duct or shaft designed for human entry, the duct or shaft shall have more than one escape exit. The duct shall have an internal height of at least 1,2 m.
5 Classification
5.1 General
For the purpose of this document, refrigerating systems shall be classified according to:
- the location in which the system is installed;
- the type of people who have access to the place in which the system is installed;
- the toxicity and flammability characteristics of the refrigerant. There are four classes of location and three access categories for refrigerating systems or parts of refrigerating systems. Where a refrigerating system contains parts installed in several spaces, each space shall be considered individually. The charge limits shall be calculated for each of them, according to Clause 7. For installations with multiple refrigerating systems, each refrigerating system shall be evaluated independently.
Examples of classification of system locations, categorisation of access and classification of refrigerants are given in Annex A.
5.2 Classification of system locations
5.2.1 Class I – Mechanical equipment located within the occupied space
If the refrigerating system or any of its refrigerant-containing parts are located indoors in an occupied space or a non-occupied space which is not sealed from the occupied space or which can leak into the occupied space, then the system is considered to be of class I unless the system conforms to the requirements in 5.2.2 or 5.2.4.
EXAMPLE Integral display unit.
5.2.2 Class II – Compressors and pressure vessels outside the occupied space
If all compressors and pressure vessels are outside the occupied space and refrigerant leaks from compressors or pressure vessels cannot flow into the occupied space, then the requirements for a class II location shall apply to any refrigerant-containing part in the occupied space or that can leak refrigerant into the occupied space. Coil-type heat exchangers and pipework, including valves, may be located in an occupied space.
Refrigerant can leak into the occupied space through heat-transfer fluid if, for example:
- the heat-transfer fluid is ventilation air;
- the heat-transfer fluid is an open spray system;
ISO 5149-3:2026(en) - leakage of the refrigerant into the occupied space is caused by leakage of the refrigerant into the heat-transfer fluid; - there is a heat-transfer fluid relief valve or an automatic purge point that vents into the space. Leakage via the heat-transfer fluid is not considered for systems that conform to ISO 5149-2:2026, 6.2.9.5 on the protection of the secondary cooling and heating system.
EXAMPLE Cold store.
5.2.3 Class III – Machinery room or open air
If all of the refrigerant-containing parts are located in a machinery room or the open air, then the requirements for a class III location shall apply. The machinery room shall conform to the requirements of Clause 8.
EXAMPLE Water-cooled chiller.
5.2.4 Class IV – Ventilated enclosures
If, with the intent of preventing migration of leaked refrigerant to the surrounding area, refrigerant-containing parts are located in a ventilated enclosure that conforms to the requirements of 4.6 and ISO 5149-2:2026, 6.2.17, then the requirements for a class IV location shall apply. EXAMPLE Heat pump within a ventilated enclosure.
5.3 Classification of access to occupied spaces, machinery rooms and open air
For the purpose of this document, access classification shall be determined according to Table 2. The access category is defined according to Table 2 by consideration of the group of occupants who are least familiar with the safety precautions. For example, in a supermarket, department store or transport terminus, an unregulated number of customers who are not familiar with the location or its safety precautions can gather. In a general office, the number of people in the building is more easily regulated and occasional visitors are accompanied by a regular occupant who can advise on the safety precautions in the event of an emergency. In a manufacturing facility, all of the occupants are familiar with the safety requirements and access to the workplace is restricted.
NOTE 1 A complex building can contain several access categories. For example, the public areas and the plant rooms in a hospital can be classified as access category a and access category c respectively. Table 2 — Categories of access Categories General characteristics Parts of buildings:
- where sleeping facilities are the main purpose of the building General access
- where people are restricted in their movement a
- where an uncontrolled number of people are present (least restrictive access to the space)
- where students are present and are under instruction or supervision
- to which any person has access Parts of buildings where:
- only a limited number of people can be assembled, some being necessarily acquainted with the general safety precautions of the establishment Supervised access
- public access is not permitted but specific knowledge of refrigerating b systems is not required
- personnel access is strictly controlled but specific knowledge of refrigerating systems is not required
ISO 5149-3:2026(en) TTaabblle 2 e 2 ((ccoonnttiinnueuedd)) Categories General characteristics Parts of buildings where:
- only authorized persons have access, who are acquainted with general and special safety precautions of the establishment and where manufacturing, Authorised access processing or storage of material or products take place
- access to the space is restricted to personnel with specific knowledge of (most restrictive access to the space) refrigerating systems
- access to the space is restricted by the layout of the building and securely controlled Examples of access categories are given in Annex A.
NOTE 2 Open air locations including roofs, car parks and outdoor equipment compounds are considered to be parts of the building.
Machinery rooms shall not be considered as an occupied space except as defined in 8.1.
5.4 Classification of refrigerants
Refrigerant shall be classified according to toxicity and flammability as specified in ISO 817 (see Annex B). The toxicity class of the refrigerant is designated by A or B. The flammability class of the refrigerant is designated by 1, 2L, 2 or 3.
6 Determining the room volume and room area used in refrigerant quantity limit
calculations
6.1 General
Where IEC or ISO product standards exist for particular types of systems, and where these product standards provide a method to determine refrigerant quantity limits or room volume limits or floor area limits, those methods shall be used in place of the requirements of this document. The space considered shall be any occupied space that contains refrigerant-containing parts. The refrigerant quantity limit for any system or part of a system shall be based on the quantity of refrigerant that can leak into the occupied space, the room volume or floor area of that space and the effect that the leak can have on the space or on the occupants of the space.
Any significant volume taken up by equipment or inventory and similar shall be deducted from the space volume calculation. Spaces above false ceilings shall not be included in the volume calculation unless the false ceiling has openings greater than 50 % of the ceiling area (e.g. grille construction) or is used as part of a ventilation system, allowing free air movement with the space below. NOTE The volume of equipment or inventory is considered significant if it is more than 20 % of the gross room volume.
6.2 Space volume and area calculations
The space for a refrigerant quantity limit calculation shall be a space into which refrigerant can leak. When considering systems located in (or serving) multiple spaces, the refrigerant quantity limit shall be based on the most stringent combination of space volume or area, access category and refrigerant characteristic. For a system using a heat-transfer fluid where the system is subject to the requirements for a Class III location, the space to be considered for the refrigerant quantity limit calculation shall be the machinery room or open-air location in which the system is located.
ISO 5149-3:2026(en) Spaces that are not occupied and are not machinery rooms but that contain components of the refrigerating system shall conform to 4.5.
Multiple spaces that have appropriate openings, that cannot be closed between the individual spaces or are connected with a common ventilation supply, return or exhaust system not containing the evaporator or the condenser shall be treated as a single space. Where the evaporator or condenser is located in an air supply duct system serving multiple spaces, the volume of the smallest single space shall be used. If the airflow to a space cannot be reduced to less than 10 % of the maximum airflow by the use of an airflow reducer, then that space shall be included in the volume of the smallest occupied space.
7 Setting refrigerant quantity limits
7.1 General
This document provides two alternative methods to ensure that the risk of hazards arising from the leakage of refrigerant from refrigeration systems is tolerable. The first method, Path A safety concept, applies a limit to the amount of refrigerant that is contained within the system and can leak. This limit is established in accordance with 7.2 to 7.8. The limitation of refrigerant charge ensures that the quantity of refrigerant in the atmosphere does not present unacceptable risk to building occupants or property. The second method, Path B safety concept, does not necessarily rely on a limitation of charge to ensure safety of the building occupants or property. Both methods, Path A safety concept and Path B safety concept, consider the hazards associated with toxicity and flammability.
The refrigerant charge for a system shall not be higher than the maximum refrigerant charge. The releasable charge for a system shall not be higher than the refrigerant quantity limit as calculated according to Clause 7. If no maximum refrigerant charge is specified, then the maximum refrigerant charge shall be the maximum amount of refrigerant that can be contained in that part of the system without adversely affecting its capacity, efficiency, reliability, operability or maintainability. NOTE In some systems, it can be possible to charge the system with more refrigerant than the minimum required for normal operation. The normal operating charge in this case can be lower than the maximum refrigerant charge. If the releasable charge, m , is used, it shall be determined according to Annex C. If a releasable charge is rl not determined by testing according to Clause C.2 or calculation according to Clause C.3, then the releasable charge for a system shall be the refrigerant charge. If Path A safety concept is applied, the refrigerant charge may be replaced by the releasable charge in the formulae in Clause 7.
7.2 Defining toxicity and flammability classes, toxicity factor, lower flammability limit and
cap factors The toxicity and flammability classes shall be as indicated in Annex B.
The toxicity factor (TF), expressed in kg/m , for the refrigerant shall be the acute toxicity exposure limit/ oxygen deprivation limit (ATEL/ODL) value or the practical limit (see Annex B), whichever is greater.
...