SIST EN 13565-2:2018
(Main)Fixed firefighting systems - Foam systems - Part 2: Design, construction and maintenance
Fixed firefighting systems - Foam systems - Part 2: Design, construction and maintenance
This European Standard specifies the requirements and describes the methods for design, installation, testing and maintenance of low, medium, and high expansion foam fire extinguishing systems.
This European Standard provides guidance for the design of various foam systems available to persons with knowledge and experience in determining the selection of foam fire extinguishing systems which will be effective in protecting specific hazard configurations. The requirement for foam systems derives from risk assessment by those competent to carry out such assessments which are outside the scope of this European Standard.
This European Standard does not cover a risk analysis carried out by a competent person.
Nothing in this European Standard is intended to restrict new technologies or alternative arrangements, provided that the level of safety prescribed in this standard is not lowered, and supported by documented evidence/test reports.
All foam systems are generally unsuitable for the following:
- chemicals, such as cellulose nitrate, that release sufficient oxygen or other oxidising agents which can sustain combustion;
- energized unenclosed electrical equipment;
- metals such as sodium, potassium and sodium-potassium alloys which are reactive to water;
- hazardous, water–reactive materials such as triethyl-aluminium and phosphorous pentoxide;
- combustible metals such as aluminium and magnesium.
Ortsfeste Brandbekämpfungsanlagen - Schaumlöschanlagen - Teil 2: Planung, Einbau und Wartung
Diese Europäische Norm legt Anforderungen an die Planung, den Einbau, die Inbetriebnahme und den Betrieb von Schwer-, Mittel- oder Leichtschaumlöschanlagen fest.
Mit dieser Europäischen Norm wird Personen mit dem entsprechenden Kenntnisstand und Erfahrungen bei der Auswahl von Schaumlöschanlagen ein Leitfaden für die Planung verschiedener Schaumlöschanlagen zur Verfügung gestellt, mit denen ein effektiver Schutz bei speziellen Brandgefahren erzielt werden soll. Die Anforderung an Schaumlöschanlagen beruht auf den durch fachkundige Personen durchgeführten Risikobewertungen — die außerhalb des Anwendungsbereiches dieser Europäischen Norm liegen.
Diese Europäische Norm gilt nicht für Risikoanalysen, die von einer fachkundigen Person durchgeführt werden.
In dieser Europäischen Norm werden keinerlei Beschränkungen hinsichtlich neuer Technologien oder alternativer Lösungen vorgenommen, vorausgesetzt, das in dieser Norm beschriebene Sicherheitsniveau ist nicht niedriger und dies durch Prüfberichte nachgewiesen wird.
Alle Schaumlöschanlagen sind generell ungeeignet für:
- Chemikalien wie Cellulosenitrat, die genügend Sauerstoff oder andere Oxidationsmittel freisetzen, die die Verbrennung unterstützen;
- stromführende freiliegende elektrische Einrichtungen;
- Metalle wie Natrium, Kalium und Natrium-Kalium-Legierungen, die mit Wasser reagieren;
- gefährliche, mit Wasser reagierende Stoffe wie Triethylaluminium und Phosphorpentoxid;
- brennbare Metalle wie Aluminium und Magnesium.
Installations fixes de lutte contre l’incendie - Systèmes à émulseurs - Partie 2 : Calcul, installation et maintenance
La présente Norme européenne spécifie les exigences et décrit les méthodes relatives au calcul, à l’installation, aux essais et à la maintenance de systèmes d’extinction à mousse bas, moyen et haut foisonnement.
La présente Norme européenne fournit des lignes directrices pour le calcul des différents systèmes à mousse, destinées à des personnes ayant suffisamment de connaissances et d’expérience pour sélectionner les systèmes d’extinction à mousse qui seront efficaces dans certaines configurations de risques spécifiques. La nécessité d’un système à mousse est définie par l’évaluation des risques réalisée par des personnes compétentes en la matière, ce qui n’entre pas dans le domaine d’application de la présente Norme européenne.
La présente Norme européenne ne concerne pas l’analyse des risques réalisée par une personne compétente.
Dans la présente Norme européenne, rien n’est destiné à limiter les nouvelles technologies ou les modifications possibles des installations, à condition que le niveau de sécurité prescrit par la présente norme ne soit pas minimisé, et qu’il soit justifié par des rapports d’essais/des preuves documentés.
Les systèmes à mousse ne sont généralement pas appropriés dans les cas suivants :
- produits chimiques, tels que le nitrate de cellulose, qui libèrent de l’oxygène ou d’autres agents oxydants en quantité suffisante pour maintenir la combustion ;
- équipements électriques non fermés sous tension ;
- métaux tels que le sodium, le potassium et les alliages sodium-potassium qui sont réactifs à l’eau ;
- matériaux réactifs à l’eau et dangereux tels que le triéthyl-aluminium et l’anhydride phosphorique ;
- métaux combustibles tels que l’aluminium et le magnésium.
Vgrajeni gasilni sistemi - Sistemi za gašenje s peno - 2. del: Načrtovanje, izvedba in vzdrževanje
Ta evropski standard določa zahteve in opisuje metode za projektiranje, namestitev, preskušanje in vzdrževanje sistemov za gašenje požarov s peno z nizko, srednjo ali visoko ekspanzijo.
Ta evropski standard podaja smernice za projektiranje različnih sistemov s peno, ki so na voljo osebam z znanjem in izkušnjami s področja izbire sistemov za gašenje požarov s peno, ki bodo učinkoviti pri varovanju določenih nevarnih konfiguracij. Zahteva za sisteme s peno je izpeljana iz ocene tveganja, ki jo izvede oseba, kompetentna za pripravljanje takih ocen, kar je zunaj področja uporabe tega evropskega standarda.
Ta evropski standard ne zajema analize tveganja, ki jo izvede kompetentna oseba.
Nobena vsebina tega evropskega standarda ni namenjena omejevanju novih tehnologij ali alternativnih ureditev pod pogojem, da se raven varnosti, predpisana v tem standardu, ne zniža in da je to podprto z dokumentiranimi dokazili/poročili o preskušanju.
Vsi sistemi s peno so na splošno neprimerni za naslednje elemente:
– kemikalije, kot je celulozni nitrat, ki sproščajo zadostno mero kisika ali drugih oksidantov, ki lahko vzdržujejo gorenje;
– električna oprema brez ohišja, ki je pod napetostjo;
– kovine, kot so klorove, natrijeve in klorovo-natrijeve zlitine, ki reagirajo z vodo;
– nevarni materiali, ki reagirajo z vodo, kot je trietil-aluminij in fosforjev pentoksid;
– vnetljive kovine, kot sta aluminij in magnezij.
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
SIST EN 13565-2:2018
01-december-2018
1DGRPHãþD
SIST EN 13565-2:2009
SIST EN 13565-2:2009/AC:2009
SIST EN 13565-2:2009/AC:2010
9JUDMHQLJDVLOQLVLVWHPL6LVWHPL]DJDãHQMHVSHQRGHO1DþUWRYDQMHL]YHGED
LQY]GUåHYDQMH
Fixed firefighting systems - Foam systems - Part 2: Design, construction and
maintenance
Ortsfeste Brandbekämpfungsanlagen - Schaumlöschanlagen - Teil 2: Planung, Einbau
und Wartung
Installations fixes de lutte contre l’incendie - Systèmes à émulseurs - Partie 2 : Calcul,
installation et maintenance
Ta slovenski standard je istoveten z: EN 13565-2:2018
ICS:
13.220.10 Gašenje požara Fire-fighting
SIST EN 13565-2:2018 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
SIST EN 13565-2:2018
---------------------- Page: 2 ----------------------
SIST EN 13565-2:2018
EN 13565-2
EUROPEAN STANDARD
NORME EUROPÉENNE
October 2018
EUROPÄISCHE NORM
ICS 13.220.20 Supersedes EN 13565-2:2009
English Version
Fixed firefighting systems - Foam systems - Part 2: Design,
construction and maintenance
Installations fixes de lutte contre l'incendie - Systèmes Ortsfeste Brandbekämpfungsanlagen -
à émulseurs - Partie 2: Calcul, installation et Schaumlöschanlagen - Teil 2: Planung, Einbau und
maintenance Wartung
This European Standard was approved by CEN on 27 August 2018.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2018 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 13565-2:2018 E
worldwide for CEN national Members.
---------------------- Page: 3 ----------------------
SIST EN 13565-2:2018
EN 13565-2:2018 (E)
Contents Page
European foreword. 5
Introduction . 6
1 Scope . 7
2 Normative references . 7
3 Terms and definitions . 8
3.1 Definitions . 8
3.2 Abbreviations . 12
4 Foam extinguishing systems . 12
4.1 General . 12
4.1.1 General requirements . 12
4.1.2 Application rates . 13
4.1.3 Environmental considerations . 14
4.1.4 Planning . 14
4.1.5 Documentation. 15
4.1.6 Supplementary manual foam fire fighting provisions . 15
4.1.7 Equipment . 15
4.2 Water supply . 16
4.2.1 Water demand . 16
4.2.2 Operating time . 16
4.2.3 Quality of water . 16
4.2.4 Power supply for water pumps . 17
4.3 Foam concentrate . 17
4.3.1 General . 17
4.3.2 Foam concentrate supply – low and medium expansion foams . 17
4.3.3 Foam concentrate pumps . 18
4.3.4 Supplementary external connections . 18
4.4 Foam proportioners . 18
4.5 Pipework . 18
4.5.1 Water and foam solution pipework . 18
4.5.2 Foam concentrate piping . 19
4.5.3 Non Newtonian foam concentrate . 19
4.5.4 Piping of aspirated foam (including that for subsurface foam applications) . 19
4.5.5 Marking . 19
4.6 Foam discharge outlets and generators. 20
4.7 Operation and control systems . 20
4.7.1 Detection of fires . 20
4.7.2 Release of fixed foam extinguishing systems . 20
4.7.3 Alarms . 21
5 Flammable liquid storage tanks, bunds and process areas . 21
5.1 General . 21
5.2 Fixed cone roof tanks . 23
5.2.1 General . 23
5.2.2 Sub surface . 24
5.2.3 Restrictions for semi-subsurface-mode . 25
5.2.4 Restrictions for subsurface mode . 25
5.3 Floating roof tanks . 26
2
---------------------- Page: 4 ----------------------
SIST EN 13565-2:2018
EN 13565-2:2018 (E)
5.3.1 General . 26
5.3.2 Number of foam discharge outlets for floating roof tanks . 26
5.3.3 Rimseal protection . 26
5.4 Bunded/diked areas and process areas . 28
6 Foam sprinkler and deluge systems . 30
6.1 Deluge systems . 30
6.1.1 Deluge applications . 30
6.1.2 Deluge limitations . 30
6.1.3 Deluge design . 30
6.2 Foam enhanced sprinkler systems . 30
6.2.1 Foam enhanced sprinkler applications . 30
6.2.2 Foam enhanced sprinkler limitations . 30
6.2.3 Foam enhanced sprinkler design . 30
6.3 Foam concentrate . 31
6.3.1 Aspirated foams . 31
6.3.2 Non aspirated foams . 31
6.4 Foam proportioning . 31
6.5 Drain and flushing connections . 31
6.6 Supplementary hose streams . 33
7 High expansion foam systems . 33
7.1 General . 33
7.2 Foam concentrate . 34
7.3 Equipment . 34
7.4 System design . 34
7.5 Equipment location considerations . 34
7.6 Personnel safety . 34
7.7 Discharge rate . 35
7.8 Discharge time . 35
8 Marine loading and unloading docks . 35
8.1 Water supplies . 35
8.2 Foam concentrate . 36
8.3 Foam water monitors . 36
8.4 Below dock foam systems . 36
9 Aircraft hangars . 36
9.1 General . 36
9.2 Fire detection . 36
9.3 System design philosophy . 37
9.4 System duration . 39
9.5 Foam and water pumps . 39
9.6 Acceptable application methods . 39
9.7 Foam types . 39
9.8 Monitors . 39
9.9 Foam-water deluge systems . 39
9.10 Medium expansion systems (Type 3 hangars only) . 40
9.11 High expansion systems . 40
9.12 Handlines . 40
9.13 Commissioning tests . 40
10 Liquefied flammable gases (LNG/LPG) . 41
10.1 General . 41
10.1.1 Liquefied Natural Gas (LNG) . 41
10.1.2 Liquefied Petroleum Gas (LPG) . 41
10.2 Controlled burn-off . 41
3
---------------------- Page: 5 ----------------------
SIST EN 13565-2:2018
EN 13565-2:2018 (E)
10.3 Un-ignited spills . 41
10.4 Fire detection. 42
10.5 Foam properties . 42
10.6 Foam proportioning system . 42
10.7 Application techniques . 42
11 Commissioning, testing, and periodic inspections. 43
11.1 Instruction of operating personnel . 43
11.2 Commissioning . 43
11.2.1 General . 43
11.2.2 Visual inspection . 43
11.2.3 Pressure tests . 43
11.2.4 Tests . 43
11.2.5 Completion certificate . 43
11.3 The periodic inspection and testing of foam systems . 44
11.3.1 General . 44
11.3.2 Inspections . 44
11.4 Shut-down . 46
11.5 Maintenance . 46
11.6 Alterations . 46
Bibliography . 47
4
---------------------- Page: 6 ----------------------
SIST EN 13565-2:2018
EN 13565-2:2018 (E)
European foreword
This document (EN 13565-2:2018) has been prepared by Technical Committee CEN/TC 191 “Fixed firefighting
systems”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an identical text
or by endorsement, at the latest by April 2019, and conflicting national standards shall be withdrawn at the latest
by April 2019.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. CEN shall not be held responsible for identifying any or all such patent rights.
This document supersedes EN 13565-2:2009.
EN 13565, Fixed firefighting systems — Foam systems consists of the following parts:
— Part 1: Requirements and test methods for components
— Part 2: Design, construction and maintenance
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the following
countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech
Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece,
Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom.
5
---------------------- Page: 7 ----------------------
SIST EN 13565-2:2018
EN 13565-2:2018 (E)
Introduction
Foam systems are designed to provide a homogeneous layer of bubbles, of aerated fire fighting foam concentrate
and water, over the surface of flammable liquids (Class B) and/or combustible materials (Class A). The layer of
bubbles will suppress the release of flammable vapours, exclude air, and cool the fuel and hot surfaces.
Applications for foam systems can be diverse so no one type of foam system can be prescribed. In addition, High
Expansion Foam may be used to provide total flooding of enclosures with 3 dimensional hazards of either Class
A and/or Class B fuels. Examples of the various types of foam system are set out in Table 1 below:
Table 1 — Typical uses of the various types of foam system
Hazard Low expansion Medium High expansion
expansion (indoors)
Flammable liquid storage tanks Yes No No
Tank bunds/collecting areas Yes Yes Yes
+ LNG/LPG
Process areas Yes Yes Yes
2
Aircraft hangers Yes < 1 400 m only Yes
Fuel transfer areas Yes Yes Yes
Plastic packaging and storage Yes No Yes
Plastic recycling Yes No No
Refuse handling and storage Yes No No
Liquefied Natural Gas No No Yes (and outdoors)
Tyre storage Yes No Yes
Rolled paper No No Yes
Marine jetties Yes Yes No
Oil filled transformers and Yes No Yes
switchgear
Cable tunnels No No Yes
LPG (Liquefied Petroleum Gas) No Yes Yes (and outdoors)
Warehouses – Class A and B fuels Yes No Yes
NOTE These examples are not prescriptive and do not preclude other uses, providing there is a fire engineering basis.
Foam systems reduce the environmental impact of fire by reducing fire effluent both into the atmosphere and
onto the ground. This is achieved through a more efficient application of fire extinguishing agent onto the seat of
fire. Compared to other extinguishing systems, the necessary application rate is significantly reduced by using
foam systems. Lower fire water damages and a reduced application of contaminated fire water in the
environment are also important advantages. Foam extinguishing systems give increased safety for the fire
fighting personnel and neighbouring communities.
6
---------------------- Page: 8 ----------------------
SIST EN 13565-2:2018
EN 13565-2:2018 (E)
1 Scope
This document specifies the requirements and describes the methods for design, installation, testing and
maintenance of low, medium, and high expansion foam fire extinguishing systems.
Foam systems may be used to suppress the release of toxic vapours but this application is outside the scope of
this document.
This document provides guidance for the design of various foam systems available to persons with knowledge
and experience in determining the selection of foam fire extinguishing systems which will be effective in
protecting specific hazard configurations. For the application of this standard, a risk assessment by a qualified
and experienced person should be performed for both new and existing systems, however the risk assessment
is outside the scope of this document.
This document does not cover a risk analysis carried out by a competent person.
Nothing in this document is intended to restrict new technologies or alternative arrangements, provided that the
level of foam system performance prescribed in this standard is not lowered, and supported by documented
evidence/test reports.
All foam systems are generally unsuitable for the following:
— chemicals, such as cellulose nitrate, that release sufficient oxygen or other oxidizing agents which can sustain
combustion;
— energized unenclosed electrical equipment;
— metals such as sodium, potassium and sodium-potassium alloys which are reactive to water;
— hazardous, water–reactive materials such as triethyl-aluminium and phosphorous pentoxide;
— combustible metals such as aluminium and magnesium.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes
requirements of this document. For dated references, only the edition cited applies. For undated references, the
latest edition of the referenced document (including any amendments) applies.
EN 54 (all parts), Fire detection and fire alarm systems
EN 1568 (all parts), Fire extinguishing media — Foam concentrates
EN 12094-1, Fixed firefighting systems — Components for gas extinguishing systems — Part 1: Requirements and
test methods for electrical automatic control and delay devices
EN 12259-1, Fixed firefighting systems — Components for sprinkler and water spray systems — Part 1: Sprinklers
EN 12845:2015, Fixed firefighting systems — Automatic sprinkler systems — Design, installation and maintenance
prEN 13565-1:2016, Fixed firefighting systems — Foam systems — Part 1: Requirements and test methods for
components
7
---------------------- Page: 9 ----------------------
SIST EN 13565-2:2018
EN 13565-2:2018 (E)
3 Terms and definitions
For the purposes of this document, the terms and definitions given in prEN 13565-1:2016 and the following
apply.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
• IEC Electropedia: available at http://www.electropedia.org/
• ISO Online browsing platform: available at http://www.iso.org/obp
3.1 Definitions
3.1.1
mode of application
method for the transportation of the foam onto the surface to be protected
Note 1 to entry: 3.1.2, 3.1.3 and 3.1.4 are subdivisions of the mode of application.
3.1.2
semi-subsurface
system where foam is delivered under the surface of the fuel and directed by a floating hose onto the surface to
be protected
3.1.3
subsurface
system where foam is delivered under the surface of the liquid
3.1.4
top pouring
system where foam is delivered onto the surface to be protected
3.1.5
application rate
calculated amount of foam solution in litres per square metre per minute
3.1.6
type of foam extinguishing systems
a fixed, semi-fixed or mobile foam extinguishing system
3.1.7
semi-fixed foam extinguishing system
system where extinguishing foam is delivered through a fixed installed pipework and stationery foam making
components whilst the foam concentrate only, or both the foam concentrate and water, are supplied from mobile
appliances
3.1.8
fixed foam extinguishing system
system w
...