This document specifies product characteristics, assessment methods, compliance criteria and a designation system for capillary fittings with short ends for brazing to copper tubes e.g. EN 1057, EN 13348, EN 13349, EN 12735-1, EN 12735-2, etc. These fitting ends exist in two forms: end feed fittings and integral brazing ring fittings. For the purposes of joining copper tubes, the fitting ends have a size range from 14,7 mm to 159 mm. The fittings are designed for a service lifetime up to fifty years.
The fittings are used up to the operating temperatures and maximum operating pressures as indicated in Annex A.
This document applies to copper alloy fittings. A non-exhaustive list of these copper alloys is given in CEN/TS 13388.
The capillary fittings with short ends for brazing to copper tubes are used with brazing alloys in accordance with alloys specified in EN ISO 17672.
Not all copper alloys that can be used to manufacture fittings can be brazed and those that can be brazed may require different brazing techniques (guidance is provided in in prEN1254-20:2019, Annex A).
Fittings with short ends for capillary brazing may also have threaded end connections. These threaded ends exist with metallic and with non-metallic sealing elements. For the purposes of joining with tubes, pipes, fittings or valves, the threaded ends have a size range from 1/8" to 4".
Adaptor fittings for use with copper tubes may combine short ends for capillary brazing with fitting ends defined in the other parts of EN 1254.
Capillary fittings with short ends for brazing may also have flanged end connections according to EN 1092-3.
Fittings can be produced by machining, metal forming, casting, or fabrication.
Products covered by this standard are intended to be used in:
a) liquid applications:
- hot, cold or combined hot and cold water systems according to EN 806;
- closed heating systems according to EN 12828 and cooling systems;
- drainage systems;
- sprinkler systems according to EN 12845;
- refrigeration systems.
b) gas applications:
- natural gas and liquefied petroleum gas systems with a maximum operating pressure less than or equal to 5 bar according to EN 1775;
- compressed air systems;
- medical gas systems according to EN ISO 7396;
- refrigeration systems.
Kupfer und Kupferlegierungen - Fittings - Teil 5: Kapillarlötfittings mit geringer Einstecktiefe zum Verbinden von Kupferrohren mittels Hartlöten
Dieses Dokument legt Produkteigenschaften, Bewertungsverfahren, Konformitätskriterien und ein Bezeichnungssystem für Kapillarfittings mit kurzen Enden zum Hartlöten von Kupferrohren fest, z. B. EN 1057, EN 13348, EN 13349, EN 12735-1, EN 12735-2 usw. Diese Fittingenden gibt es in zwei Formen: Lötfittings und Fittings mit integriertem Hartlötring. Zum Verbinden von Kupferrohren haben die Fittingenden einen Größenbereich von 14,7 mm bis 159 mm. Die Fittings sind für eine Lebensdauer von bis zu fünfzig Jahren ausgelegt.
Die Fittings werden bis zu den in Anhang A angegebenen Betriebstemperaturen und maximalen Betriebsdrücken eingesetzt.
Dieses Dokument gilt für Fittings aus Kupferlegierungen. Eine nicht vollständige Liste dieser Kupferlegierungen ist in CEN/TS 13388 enthalten.
Kapillarfittings mit kurzen Enden zum Hartlöten von Kupferrohren werden mit Hartloten nach den in EN ISO 17672 spezifizierten Legierungen verwendet.
Nicht alle Kupferlegierungen, die zur Herstellung von Fittings verwendet werden können, können hartgelötet werden, und diejenigen, die hartgelötet werden können, können andere Hartlöttechniken erfordern (Hinweise siehe prEN 1254-20:2019, Anhang A).
Kapillarfittings mit kurzen Enden zum Hartlöten von Kupferrohren dürfen auch Gewindeanschlüsse aufweisen. Diese Gewindeenden gibt es mit metallischen und mit nichtmetallischen Dichtelementen. Zum Verbinden von Rohren, Fittings oder Ventilen haben die Gewindeenden einen Größenbereich von 1/8" bis 4".
Übergangsfittings für Kupferrohre dürfen kurze Enden zum Kapillarhartlöten mit in den anderen Teilen der EN 1254 definierten Fittingenden kombinieren.
Kapillarfittings mit kurzen Enden zum Hartlöten dürfen auch Flanschendanschlüsse nach EN 1092-3 aufweisen.
Fittings können durch Bearbeiten, Metallumformen, Gießen oder Fertigen hergestellt werden.
Die unter diese Norm fallenden Produkte sind für den Einsatz bestimmt in:
a) Flüssigkeitsanwendungen:
- Warm-, Kalt- oder kombinierte Warm-/Kaltwassersysteme nach EN 806;
- geschlossene Heizsysteme nach EN 12828 und Kühlsysteme;
- Entwässerungssysteme;
- Sprinkleranlagen nach EN 12845;
- Kältetechnik.
b) Gasanwendungen:
- Erdgas- und Flüssiggasanlagen mit einem maximalen Betriebsdruck von weniger als oder gleich 5 bar nach EN 1775;
- Druckluftsysteme;
- Systeme für medizinische Gase nach EN ISO 7396;
- Kältetechnik.
Cuivre et alliages de cuivre - Raccords - Partie 5 : Raccords à emboîture courte pour brasure forte par capillarité pour tubes en cuivre
Le présent document spécifie les caractéristiques de produit, les méthodes d'évaluation, les critères de conformité et un système de désignation pour les raccords à emboîture courte pour brasure forte par capillarité pour tubes en cuivre conformes, par exemple, aux EN 1057, EN 13348, EN 13349, EN 12735-1, EN 12735-2, etc. Ces extrémités de raccords existent sous deux formes : raccords à extrémité d'alimentation et raccords à anneau de brasure forte incorporé. Pour l'assemblage de tubes en cuivre, les extrémités de raccords ont une gamme de dimensions comprise entre 14,7 mm et 159 mm. Les raccords sont conçus pour une durée de vie en service supérieure à 50 ans.
Les raccords sont utilisés jusqu'aux températures de service et aux pressions de service maximales indiquées à l'Annexe A.
Le présent document s'applique aux raccords en alliage de cuivre. Une liste non exhaustive de ces alliages de cuivre figure dans la CEN/TS 13388.
Les raccords à emboîture courte pour brasure forte par capillarité pour tubes en cuivre sont utilisés avec des alliages de brasage fort conformément aux alliages spécifiés dans l’EN ISO 17672.
Les alliages de cuivre utilisés pour fabriquer des raccords ne peuvent pas tous être assemblés par brasage fort, et ceux qui peuvent être assemblés par brasage fort peuvent nécessiter de différentes techniques de brasage fort (des lignes directrices sont fournies dans le prEN1254-20:2019, Annexe A).
Les raccords à emboîture courte pour le brasage fort par capillarité peuvent également comporter des assemblages filetés. Ces extrémités filetées existent avec des éléments d'étanchéité métalliques et non métalliques. Pour l'assemblage avec des tubes, des tuyaux, des raccords ou des vannes, les extrémités filetées ont une gamme de dimensions comprise entre 1/8" et 4".
Les raccords adaptateurs utilisés avec des tubes en cuivre peuvent combiner des emboîtures courtes pour brasure forte par capillarité avec des extrémités définies dans les autres parties de l’EN 1254.
Les raccords à emboîture courte pour brasure forte par capillarité peuvent également comporter des raccordements à brides conformément à l’EN 1092-3.
Les raccords peuvent être fabriqués par usinage, formage des métaux, moulage ou mécanosoudage.
Les produits couverts par la présente norme sont destinés à être utilisés dans :
a) les applications liquides :
- les systèmes d'eau chaude, d'eau froide ou d'eau chaude et d'eau froide combinées conformes à l’EN 806 ;
- les systèmes de chauffage fermés conformes à l'EN 12828 et les systèmes de refroidissement ;
- les systèmes de purge ;
- les systèmes d'extinction de type sprinkleur conformes à l’EN 12845 ;
- les systèmes réfrigération.
b) les applications de gaz :
- les systèmes fonctionnant au gaz naturel et des systèmes fonctionnant au gaz de pétrole liquéfiés avec une pression maximale de service inférieure ou égale à 5 bar, conformément à l'EN 1775 ;
- les systèmes d’air comprimé ;
- les systèmes de distribution de gaz médicaux conformes à l’EN ISO 7396 ;
- les systèmes réfrigération.
Baker in bakrove zlitine - Fitingi - 5. del: Fitingi, ki imajo krajši konec prirejen za kapilarno trdo spajkanje na bakrene cevi
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
SIST EN 1254-5:2021
01-julij-2021
Nadomešča:
SIST EN 1254-5:2000
Baker in bakrove zlitine - Fitingi - 5. del: Fitingi, ki imajo krajši konec prirejen za
kapilarno trdo spajkanje na bakrene cevi
Copper and copper alloys - Plumbing fittings - Part 5: Capillary fittings with short ends for
brazing to copper tubes
Kupfer und Kupferlegierungen - Fittings - Teil 5: Kapillarlötfittings mit geringer
Einstecktiefe zum Verbinden von Kupferrohren mittels Hartlöten
Cuivre et alliages de cuivre - Raccords - Partie 5 : Raccords à emboîture courte pour
brasure forte par capillarité pour tubes en cuivre
Ta slovenski standard je istoveten z: EN 1254-5:2021
ICS:
23.040.40 Kovinski fitingi Metal fittings
77.150.30 Bakreni izdelki Copper products
SIST EN 1254-5:2021 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
SIST EN 1254-5:2021
---------------------- Page: 2 ----------------------
SIST EN 1254-5:2021
EN 1254-5
EUROPEAN STANDARD
NORME EUROPÉENNE
May 2021
EUROPÄISCHE NORM
ICS 23.040.40 Supersedes EN 1254-5:1998
English Version
Copper and copper alloys - Plumbing fittings - Part 5:
Capillary fittings with short ends for brazing to copper
tubes
Cuivre et alliages de cuivre - Raccords - Partie 5 : Kupfer und Kupferlegierungen - Fittings - Teil 5:
Raccords à emboîture courte pour brasure forte par Kapillarlötfittings mit geringer Einstecktiefe zum
capillarité pour tubes en cuivre Verbinden von Kupferrohren mittels Hartlöten
This European Standard was approved by CEN on 23 November 2020.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and
United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2021 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 1254-5:2021 E
worldwide for CEN national Members.
---------------------- Page: 3 ----------------------
SIST EN 1254-5:2021
EN 1254-5:2021 (E)
Contents Page
European foreword . 3
Introduction . 4
1 Scope . 5
2 Normative references . 6
3 Terms and definitions . 7
4 Product characteristics . 7
4.1 Internal pressure . 7
4.2 Tightness . 7
4.3 Release of dangerous substances . 7
4.4 Durability . 7
4.5 Dimensional tolerances of diameters . 8
4.6 Wall thickness for short ends for capillary brazing to copper tubes . 9
4.7 Wall thickness at threaded portions of adaptor fittings . 12
4.8 Dimensions of tail pipe ends for swivel fittings . 12
4.9 Dimensions of gas union connectors . 12
4.10 Threaded end dimensions . 12
4.11 Other adapter ends (not defined in EN 1254-20:2021) . 12
4.12 Length of engagement . 13
4.13 Bore dimensions . 14
4.14 Tube abutment . 15
4.15 Alignment of the fitting ends . 15
4.16 Shapes for tightening systems . 15
4.17 Surface condition . 15
4.18 Surface cleanliness for medical gases . 15
5 Testing, assessment and sampling methods . 16
5.1 General . 16
5.2 Internal pressure . 16
5.3 Tightness: Integrity of fabricated fitting bodies or having an 'as cast' microstructure . 16
5.4 Durability . 17
5.5 Dimensional tolerances of diameters . 17
5.6 Wall thickness for short ends for capillary brazing to copper tubes . 17
5.7 Wall thickness at threaded portions of adaptor fittings . 17
5.8 Dimensions of tail pipe ends for swivel fittings . 17
5.9 Dimensions of gas union connectors . 17
5.10 Threaded end dimensions . 18
5.11 Length of engagement . 18
5.12 Bore dimensions . 18
5.13 Alignment of the fitting ends . 18
6 Evaluation of conformity . 18
6.1 General . 18
6.2 Type testing . 18
6.3 Factory production control (FPC) . 21
7 Designation. 24
8 Marking, labelling and packaging . 24
Annex A (normative) Operating temperatures and corresponding maximum operating
pressures . 25
Bibliography . 26
2
---------------------- Page: 4 ----------------------
SIST EN 1254-5:2021
EN 1254-5:2021 (E)
European foreword
This document (EN 1254-5:2021) has been prepared by Technical Committee CEN/TC 133 “Copper and
copper alloys”, the secretariat of which is held by DIN.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by November 2021, and conflicting national standards
shall be withdrawn at the latest by November 2021.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
This document supersedes EN 1254-5:1998.
The main changes to EN1254-5:1998 are:
— separation of test methods into part 20.
This part of the standard (EN 1254-5) should be read in conjunction with EN 1254-20:2021.
EN 1254 comprises the following parts under the general title “Copper and copper alloys — Plumbing
fittings”:
— Part 1: Capillary fittings for soldering or brazing to copper tubes
— Part 2: Compression fittings for use with copper tubes
— Part 3: Compression fittings for use with plastics and multilayer pipes
— Part 4: Threaded fittings
— Part 5: Capillary fittings with short ends for brazing to copper tubes
— Part 6: Push-fit fittings for use with metallic tubes, plastics and multilayer pipes
— Part 7: Press fittings for use with metallic tubes
— Part 8: Press fittings for use with plastics and multilayer pipes
— Part 20: Definitions, thread dimensions, test methods, reference data and supporting information
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria,
Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland,
Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Republic of
North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the
United Kingdom.
3
---------------------- Page: 5 ----------------------
SIST EN 1254-5:2021
EN 1254-5:2021 (E)
Introduction
Products complying with this document may be used for several fluids including the transport of water
intended for human consumption if they comply with the relevant national, regional or local regulatory
provisions applicable in the place of use.
4
---------------------- Page: 6 ----------------------
SIST EN 1254-5:2021
EN 1254-5:2021 (E)
1 Scope
This document specifies product characteristics, assessment methods, compliance criteria of the test
results and a designation system for capillary fittings with short ends for brazing to copper tubes e.g.
EN 1057, EN 13348, EN 13349, EN 12735-1, EN 12735-2, etc. These fitting ends exist in two forms: end
feed fittings and integral brazing ring fittings. For the purposes of joining copper tubes, the fitting ends
have a nominal diameter from 14,7 mm to 159 mm. The fittings are designed for a service lifetime up to
fifty years.
The fittings are used up to the operating temperatures and corresponding maximum operating
pressures as indicated in Annex A.
This document applies to copper alloy fittings. A non-exhaustive list of these copper alloys is given in
CEN/TS 13388.
The capillary fittings with short ends for brazing to copper tubes are used with brazing alloys in
accordance with alloys specified in EN ISO 17672.
Not all copper alloys that can be used to manufacture fittings can be brazed and those that can be
brazed may require different brazing techniques (guidance is provided in in EN 1254-20:2021,
Annex A).
Fittings with short ends for capillary brazing may also have threaded end connections. These threaded
ends exist with metallic and with non-metallic sealing elements. For the purposes of joining with tubes,
pipes, fittings or valves, the threaded ends have a size range from 1/8” to 4”.
Adaptor fittings for use with copper tubes may combine short ends for capillary brazing with fitting
ends defined in the other parts of EN 1254.
Capillary fittings with short ends for brazing may also have flanged end connections according to
EN 1092-3.
Fittings can be produced by machining, metal forming, casting, or fabrication.
Products covered by this document are intended to be used in:
a) liquid applications:
— hot, cold or combined hot and cold water, including systems according to EN 806;
— closed heating systems according to EN 12828;
— cooling systems;
— drainage systems;
— fire protection systems including sprinkler systems according to EN 12845;
— refrigeration systems;
— supply systems for points of consumption with liquid fuels according to EN 12514.
5
---------------------- Page: 7 ----------------------
SIST EN 1254-5:2021
EN 1254-5:2021 (E)
b) gas applications:
— natural gas and liquefied petroleum gas systems with a maximum operating pressure less than
or equal to 5 bar according to EN 1775;
— gas line systems with an operating pressure exceeding 0,5 bar for industrial installations and
exceeding 5 bar for industrial and non-industrial installations according to EN 15001-1;
— compressed air systems;
— medical gas systems according to EN ISO 7396;
— refrigeration systems.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN 723, Copper and copper alloys — Combustion method for determination of the carbon content on the
inner surface of copper tubes or fittings
EN 1057:2006+A1:2010, Copper and copper alloys — Seamless, round copper tubes for water and gas in
sanitary and heating applications
EN 1254-20:2021, Copper and copper alloys — Plumbing fittings — Part 20: Definitions, thread
dimensions, test methods, reference data and supporting information
EN 10226-3, Pipes threads where pressure tight joint are made on the threads — Part 3: Verification by
means of limit gauges
EN 12502-2, Protection of metallic materials against corrosion — Guidance on the assessment of
corrosion likelihood in water distribution and storage systems — Part 2: Influencing factors for copper
and copper alloys
EN ISO 6506-1, Metallic materials — Brinell hardness test — Part 1: Test method (ISO 6506-1)
EN ISO 6507-1, Metallic materials — Vickers hardness test — Part 1: Test method (ISO 6507-1)
ISO 7-2, Pipe threads where pressure-tight joints are made on the threads — Part 2: Verification by means
of limit gauges
ISO 228-2, Pipe threads where pressure-tight joints are not made on the threads — Part 2: Verification by
means of limit gauges
ISO 2859-1:1999, Sampling procedures for inspection by attributes — Part 1: Sampling schemes indexed
by acceptance quality limit (AQL) for lot-by-lot inspection
6
---------------------- Page: 8 ----------------------
SIST EN 1254-5:2021
EN 1254-5:2021 (E)
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 1254-20:2021 apply.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
— IEC Electropedia: available at http://www.electropedia.org/
— ISO Online browsing platform: available at https://www.iso.org/obp
4 Product characteristics
4.1 Internal pressure
When tested according to the method in 5.2 fittings shall show no signs of leakage or permanent
distortion.
4.2 Tightness
4.2.1 Leak tightness under internal hydrostatic pressure
Fittings assessed as indicated in 4.1 are considered to be leak tight under internal hydrostatic pressure.
4.2.2 Integrity of fabricated fitting bodies or having an 'as cast' microstructure
This requirement only applies to fitting bodies with an 'as cast' microstructure (excluding continuously
cast materials) or fabricated by welding or brazing.
When tested according to the method in 5.3 fitting bodies shall show no visual indication of leakage.
4.3 Release of dangerous substances
National regulations on dangerous substances may require verification and declaration on release, and
sometimes content, when construction products covered by this document are placed on those markets.
In the absence of European harmonized test methods, verification and declaration on release/content
should be done taking into account national provisions in the place of use.
NOTE An informative database covering European and national provisions on dangerous substances is
available at the Construction website on EUROPA accessed through: http://ec.europa.eu/growth/tools-
databases/cp-ds
4.4 Durability
4.4.1 Durability of internal pressure: Resistance to stress corrosion
Fittings manufactured from copper and copper-tin-zinc alloys (CuSnZnPb) shall be considered to be
resistant to stress corrosion according to EN 12502-2 and copper-zinc-silicon alloys containing ≥ 2 % Si
are also considered to be resistant.
Fittings manufactured from CuZn-alloys shall be considered to be resistant to stress corrosion when the
product has a hardness HBW 2,5/62,5 ≤ 110 measured according to EN ISO 6506-1 or a hardness
10
HV ≤ 134 measured according to EN ISO 6507-1.
5
Fittings manufactured from copper alloys with a zinc content of 10 % or greater not mentioned above
shall be tested and assessed according to 5.4.1, and shall show no evidence of cracking.
7
---------------------- Page: 9 ----------------------
SIST EN 1254-5:2021
EN 1254-5:2021 (E)
4.4.2 Durability of tightness: Residual carbon contamination in the bore
4.4.2.1 General
This requirement only applies for copper fittings. This requirement does not apply for copper alloy
fittings.
4.4.2.2 Carbon film
When tested according to 5.4.2.1 there shall not be any visible carbon film.
4.4.2.3 Total carbon
When tested according to 5.4.2.2 the maximum total carbon level on internal surfaces shall not exceed
2
1,0 mg/dm .
4.5 Dimensional tolerances of diameters
In order to achieve the capillary flow of a brazing alloy when making a connection, the dimensions of a
socket or male end shall be tightly controlled.
When assessed according to the method specified in 5.5, the diameter shall be within the tolerances
expressed in Table 1 for the relevant diameters.
8
---------------------- Page: 10 ----------------------
SIST EN 1254-5:2021
EN 1254-5:2021 (E)
Table 1 — Tolerances on the nominal diameter
Values in millimetres
a
Nominal Tolerances on the mean diameter Resulting diametrical
diameter with respect to the nominal diameter difference
D D
Outside diameter Inside diameter max. min.
of male end of socket
14,7
15 +0,04 +0,15
0,20 0,02
16 −0,05 +0,06
18
21
22
+0,05 +0,18
25 0,24 0,02
−0,06 +0,07
27,4
28
b
34
b
35
b
40
+0,06 +0,23
b
40,5 0,30 0,03
−0,07 +0,09
b
42
b
53,6
b
54
b
64
b
66,7
b
70
b
+0,07 +0,33
76,1
0,41 0,03
b
80 −0,08 +0,10
b
88,9
b
106
b
108
b
133
+0,20 +0,70
0,90 0,03
b
159
−0,20 +0,23
a
Arithmetical mean of two diameters at right angles in a cross-section taken anywhere on the length of the
socket or of the male end except under indented marking or in the solder or brazing alloy groove.
b
The brazing of tubes and fittings for these diameters requires more skilled techniques (further information is
available in in EN 1254-20:2021, Annex A).
4.6 Wall thickness for short ends for capillary brazing to copper tubes
When measured according to the method specified in 5.6, the minimum wall thickness shall be as
expressed in Table 2 for the relevant diameters and different forms of the material.
The minimum wall thickness requirements do not apply under embossed marking on the socket end.
9
---------------------- Page: 11 ----------------------
SIST EN 1254-5:2021
EN 1254-5:2021 (E)
In the case of integral brazing ring fittings where a groove is made within the brazing length, the
minimum wall thickness measured within or immediately adjacent to the brazing groove (see Figure 1)
shall be in accordance with dimension e' in Table 2.
end feed fitting integral brazing ring fitting integral brazing ring fitting
Key
D nominal diameter
e minimum wall thickness
e' minimum wall thickness within or immediately adjacent to the brazing ring groove
Figure 1 — Minimum wall thickness
10
---------------------- Page: 12 ----------------------
SIST EN 1254-5:2021
EN 1254-5:2021 (E)
Table 2 — Minimum wall thickness
Dimensions in millimetres
Nominal Minimum wall thickness
diameter
Wrought coppers Wrought copper alloys Cast coppers and copper
and continuous cast bar alloys
D e e' e e' e e'
14,7 0,7 0,63 1,2 0,66 1,2 0,78
15 0,7 0,63 1,2 0,66 1,2 0,78
16 0,7 0,63 1,2 0,66 1,2 0,78
18 0,8 0,72 1,4 0,77 1,4 0,91
21 0,9 0,81 1,4 0,77 1,4 0,91
22 0,9 0,81 1,4 0,77 1,5 0,97
25 0,9 0,81 1,4 0,77 1,6 1,04
27,4 0,9 0,81 1,5 0,82 1,6 1,04
28 0,9 0,81 1,5 0,82 1,8 1,17
34 1,0 0,90 1,6 0,88 1,8 1,17
35 1,0 0,90 1,6 0,88 1,8 1,17
40 1,1 0,99 1,8 0,99 2,0 1,30
40,5 1,1 0,99 1,8 0,99 2,0 1,30
42 1,1 0,99 1,8 0,99 2,0 1,30
53,6 1,2 1,08 1,9 1,04 2,3 1,49
54 1,2 1,08 1,9 1,04 2,3 1,49
64 1,4 1,26 2,0 1,10 2,4 1,56
66,7 1,4 1,26 2,0 1,10 2,4 1,56
70 1,4 1,26 2,3 1,26 2,6 1,69
76,1 1,6 1,44 2,6 1,43 2,8 1,82
80 1,8 1,62 2,8 1,54 2,9 1,88
11
---------------------- Page: 13 ----------------------
SIST EN 1254-5:2021
EN 1254-5:2021 (E)
Nominal Minimum wall thickness
diameter
Wrought coppers Wrought copper alloys Cast coppers and copper
and continuous cast bar alloys
D e e' e e' e e'
88,9 1,8 1,62 2,9 1,59 3,1 2,01
106 2,1 1,89 3,3 1,80 3,5 2,27
108 2,1 1,89 3,3 1,80 3,5 2,27
133 2,3 2,07 4,2 2,31 4,5 2,92
159 2,6 2,34 5,2 2,86 5,5 3,57
4.7 Wall thickness at threaded portions of adaptor fittings
This requirement only applies to fittings with an interface thread.
When assessed according to the method specified in 5.7 the minimum wall thickness at the interface
thread shall be as expressed in EN 1254-20:2021, 4.1 for the relevant diameters.
4.8 Dimensions of tail pipe ends for swivel fittings
This requirement only applies to tail pipe ends for swivel fittings.
When assessed according to the method specified in 5.8 the dimensions shall be as expressed in
EN 1254-20:2021, 4.2 for the thread size.
4.9 Dimensions of gas union connectors
This requirement only applies to fittings with gas union connectors.
When assessed according to the method specified in 5.9 the dimensions shall be as expressed in
EN 1254-20:2021, 4.3 for corresponding nominal size.
4.10 Threaded end dimensions
This requirement only applies to fitting bodies with threaded ends.
When assessed according to the method specified in 5.10 the thread shall be in accordance with
EN 1254-20:2021, 4.4.
4.11 Other adapter ends (not defined in EN 1254-20:2021)
Other adapter ends, when assembled in accordance with the manufacturer's instructions and pressure
tested according to the method in 5.2 shall show no signs of leakage or permanent distortion. When re-
tested in accordance with the test method in 5.2 after disconnection and reconnection, it shall again
show no signs of leakage or permanent distortion. If after disconnection the sealing element shows
signs of damage, it shall be replaced before the second test.
12
---------------------- Page: 14 ----------------------
SIST EN 1254-5:2021
EN 1254-5:2021 (E)
4.12 Length of engagement
When assessed according to the method specified in 5.11, the minimum length of engagement shall be
as expressed in Table 3 for the relevant diameters.
for integral brazing ring socket ends shall not include the width of the brazing alloy
The length L1
groove (see Figure 2b). The actual groove shape is unimportant providing that it contains sufficient
braze to produce a sound joint on assembly with the correct size of tube.
Male ends intended for use with integral ring sockets shall include an allowance for the width of the
brazing alloy groove.
When the male end diameter is less than the fitting diameter (see Figure 3), the length of the male end
shall be increased to L (see Table 3).
2
L = L + L
1 A Ā
end feed fitting integral brazing ring fitting
Key
D nominal diameter
L1 length of the socket end
L length from the groove to the inner end of the socket end
A
L length from the groove to the outer end of the socket end
Ā
Figure 2 — Socket
Key
D nominal diameter
L length of the male when the male end diameter is bigger than the fitting diameter
1
L length of the male when the male end diameter is less than the fitting diameter
2
Figure 3 — Male end
13
---------------------- Page: 15 ----------------------
SIST EN 1254-5:2021
EN 1254-5:2021 (E)
Table 3 — Minimum lengths of engagement exclusively for short ends for capillary brazing
Dimensions in millimetres
Length of engagement
Nominal diameter
D
L L
1 2
14,7
15
7 9
16
18
21
22 8 10
25
27,4
9 11
28
34
35
40 10 12
40,5
42
53,6
11 13
54
64
11 14
66,7
70
12 15
76,1
80 13 16
88,9 14 17
106
15 19
108
133 19 24
159 21 26
4.13 Bore dimensions
To minimize flow resistance, minimum bore dimensions are required.
When assessed according to the test method in 5.12, the minimum bore of the fitting shall be greater or
equal to the values expressed in EN 1254-20:2021, 4.5, Table 9, for the relevant nominal diameter.
For unequal-ended or adaptor fittings, the smallest diameter shall apply provided that this diameter
does not restrict other outlets.
Bores at threaded portions of fittings shall not restrict other outlets.
14
---------------------- Page: 16 ----------------------
SIST EN 1254-5:2021
EN 1254-5:2021 (E)
4.14 Tube abutment
This requirement does not apply to threaded ends.
Fitting ends are usually manufactured with an abutment to limit tube insertion (see Figure 4) and to
ensure that the minimum length of engagement between tube and fitting is satisfied.
Fittings may be produced for special purposes, particularly useful for repairs, where the fitting ends do
not incorporate abutments, allowing for the fitting to slide along a tube.
The dimensions of the abutment shall be such that it will stop the smallest possible tube according to
EN 1057:2006+A1:2010, Table 4. The abutment shall also satisfy the minimum bore requirement as
stated in 4.13.
Key
1 tube abutment
NOTE Figure 4 is diagrammatic only; the shape and number of abutments are at the manufacturer's
discretion.
Figure 4 — Tube abutment
4.15 Alignment of the fitting ends
When tested according to the method in 5.13, the alignment of the fitting ends with reference to the
specified axis shall be within ± 2 °.
4.16 Shapes for tightening systems
When visually inspected, fittings with threads shall have a shape or suitable features for the
transmission of tightening torques.
4.17 Surface condition
When visually inspected, fittings shall be free from sharp edges or burrs.
4.18 Surface cleanliness for medical gases
The inner and outer surfaces of the fittings shall be clean and smooth.
The surface of the fitting shall be capable of meeting the residual carbon contamination requirement
specified in 4.4.2.2.
To avoid contamination of the gas passing through the fitting,
...
SLOVENSKI STANDARD
oSIST prEN 1254-5:2019
01-september-2019
Baker in bakrove zlitine - Fitingi - 5. del: Fitingi, ki imajo krajši konec prirejen za
kapilarno trdo spajkanje na bakrene cevi
Copper and copper alloys - Plumbing fittings - Part 5: Capillary fittings with short ends for
brazing to copper tubes
Kupfer und Kupferlegierungen - Fittings - Teil 5: Hartkapillarlötfittings mit geringer
Einstecktiefe zum Verbinden mit Kupferrohren
Cuivre et alliages de cuivre - Raccords - Partie 5 : Raccords à emboîture courte pour
brasure forte par capillarité pour tubes en cuivre
Ta slovenski standard je istoveten z: prEN 1254-5
ICS:
23.040.40 Kovinski fitingi Metal fittings
77.150.30 Bakreni izdelki Copper products
oSIST prEN 1254-5:2019 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
oSIST prEN 1254-5:2019
---------------------- Page: 2 ----------------------
oSIST prEN 1254-5:2019
DRAFT
EUROPEAN STANDARD
prEN 1254-5
NORME EUROPÉENNE
EUROPÄISCHE NORM
June 2019
ICS 23.040.40 Will supersede EN 1254-5:1998
English Version
Copper and copper alloys - Plumbing fittings - Part 5:
Capillary fittings with short ends for brazing to copper
tubes
Cuivre et alliages de cuivre - Raccords - Partie 5 : Kupfer und Kupferlegierungen - Fittings - Teil 5:
Raccords à emboîture courte pour brasure forte par Hartkapillarlötfittings mit geringer Einstecktiefe zum
capillarité pour tubes en cuivre Verbinden mit Kupferrohren
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee
CEN/TC 133.
If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations
which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC
Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and United Kingdom.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are
aware and to provide supporting documentation.
Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without
notice and shall not be referred to as a European Standard.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2019 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 1254-5:2019 E
worldwide for CEN national Members.
---------------------- Page: 3 ----------------------
oSIST prEN 1254-5:2019
prEN 1254-5:2019 (E)
Contents Page
European foreword . 4
Introduction . 5
1 Scope . 6
2 Normative references . 7
3 Terms and definitions . 8
4 Product characteristics . 8
4.1 Internal pressure . 8
4.2 Tightness . 8
4.2.1 Leak tightness under internal hydrostatic pressure . 8
4.2.2 Integrity of fabricated fitting bodies or having an 'as cast' microstructure . 8
4.3 Release of dangerous substances . 8
4.4 Durability . 8
4.4.1 Durability of internal pressure . 8
4.4.2 Durability of tightness . 9
4.5 Dimensional tolerances of diameters . 9
4.6 Wall thickness for short ends for capillary brazing to copper tubes . 10
4.7 Wall thickness at threaded portions of adaptor fittings . 13
4.8 Dimensions of tail pipe ends for swivel fittings . 13
4.9 Dimensions of gas union connectors . 13
4.10 Threaded end dimensions . 13
4.11 Other adapter ends (not defined in prEN 1254-20:2019) . 13
4.12 Length of engagement . 13
4.13 Bore dimensions . 15
4.14 Tube abutment . 17
4.15 Alignment of the fitting ends . 17
4.16 Shapes for tightening systems . 18
4.17 Surface condition . 18
4.18 Surface cleanliness for medical gases . 18
5 Testing, assessment and sampling methods . 18
5.1 General . 18
5.1.1 Preparation of fittings for testing. 18
5.1.2 Test temperature . 18
5.2 Internal pressure . 18
5.3 Tightness . 19
5.3.1 Integrity of fabricated fitting bodies or having an 'as cast' microstructure . 19
5.4 Durability . 19
5.4.1 Durability of internal pressure . 19
5.4.2 Durability of tightness . 19
5.5 Dimensional tolerances of diameters . 19
5.6 Wall thickness for short ends for capillary brazing to copper tubes . 19
5.7 Wall thickness at threaded portions of adaptor fittings . 20
5.7.1 Type testing . 20
5.7.2 FPC testing . 20
5.8 Dimensions of tail pipe ends for swivel fittings . 20
5.9 Dimensions of gas union connectors . 20
2
---------------------- Page: 4 ----------------------
oSIST prEN 1254-5:2019
prEN 1254-5:2019 (E)
5.9.1 Type testing . 20
5.9.2 FPC testing . 20
5.10 Threaded end dimensions . 20
5.11 Length of engagement . 20
5.12 Bore dimensions . 20
5.13 Alignment of the fitting ends . 20
6 Assessment and verification of constancy of performance - AVCP . 21
6.1 General . 21
6.2 Type testing . 21
6.2.1 General . 21
6.2.2 Test samples, testing and compliance criteria . 22
6.2.3 Test reports . 23
6.3 Factory production control (FPC) . 23
6.3.1 General . 23
6.3.2 Requirements . 23
6.3.3 Product specific requirements . 27
6.3.4 Procedure for modifications . 27
6.3.5 One-off products, pre-production products (e.g. prototypes) and products produced
in very low quantity . 27
7 Classification and designation . 28
8 Marking, labelling and packaging . 29
8.1 General . 29
Annex A (normative) Intended maximum operating temperatures and maximum operating
pressures . 30
Bibliography . 31
3
---------------------- Page: 5 ----------------------
oSIST prEN 1254-5:2019
prEN 1254-5:2019 (E)
European foreword
This document (prEN 1254-5:2019) has been prepared by Technical Committee CEN/TC 133 “Copper
and copper alloys”, the secretariat of which is held by DIN.
This document is currently submitted to the CEN Enquiry.
This document will supersede EN 1254-5:1998.
This part of the standard (EN 1254-5) should be read in conjunction with prEN 1254-20:2019.
EN 1254 comprises the following parts under the general title “Copper and copper alloys — Plumbing
fittings”:
— Part 1: Capillary fittings for soldering or brazing to copper tubes
— Part 2: Compression fittings for use with copper tubes
— Part 3: Compression fittings for use with plastics and multilayer pipes
— Part 4: Threaded fittings
— Part 5: Capillary fittings with short ends for brazing to copper tubes
— Part 6: Push-fit fittings for use with metallic tubes, plastics and multilayer pipes
— Part 7: Press fittings for use with metallic tubes
— Part 8: Press fittings for use with plastics and multilayer pipes
— Part 20: Definitions, thread dimensions, test methods, reference data and supporting information
The main changes to EN1254-5:1998 are:
— separation of test methods into part 20.
4
---------------------- Page: 6 ----------------------
oSIST prEN 1254-5:2019
prEN 1254-5:2019 (E)
Introduction
Products complying with this European standard may be used for the transport of water intended for
human consumption if they comply with the relevant national, regional or local regulatory provisions
applicable in place of use.
5
---------------------- Page: 7 ----------------------
oSIST prEN 1254-5:2019
prEN 1254-5:2019 (E)
1 Scope
This document specifies product characteristics, assessment methods, compliance criteria and a
designation system for capillary fittings with short ends for brazing to copper tubes e.g. EN 1057,
EN 13348, EN 13349, EN 12735-1, EN 12735-2, etc. These fitting ends exist in two forms: end feed
fittings and integral brazing ring fittings. For the purposes of joining copper tubes, the fitting ends have
a size range from 14,7 mm to 159 mm. The fittings are designed for a service lifetime up to fifty years.
The fittings are used up to the operating temperatures and maximum operating pressures as indicated
in Annex A.
This document applies to copper alloy fittings. A non-exhaustive list of these copper alloys is given in
CEN/TS 13388.
The capillary fittings with short ends for brazing to copper tubes are used with brazing alloys in
accordance with alloys specified in EN ISO 17672.
Not all copper alloys that can be used to manufacture fittings can be brazed and those that can be
brazed may require different brazing techniques (guidance is provided in in prEN1254–20:2019,
Annex A).
Fittings with short ends for capillary brazing may also have threaded end connections. These threaded
ends exist with metallic and with non-metallic sealing elements. For the purposes of joining with tubes,
pipes, fittings or valves, the threaded ends have a size range from 1/8” to 4”.
Adaptor fittings for use with copper tubes may combine short ends for capillary brazing with fitting
ends defined in the other parts of EN 1254.
Capillary fittings with short ends for brazing may also have flanged end connections according to
EN 1092-3.
Fittings can be produced by machining, metal forming, casting, or fabrication.
Products covered by this standard are intended to be used in:
a) liquid applications:
— hot, cold or combined hot and cold water systems according to EN 806;
— closed heating systems according to EN 12828 and cooling systems;
— drainage systems;
— sprinkler systems according to EN 12845;
— refrigeration systems.
b) gas applications:
— natural gas and liquefied petroleum gas systems with a maximum operating pressure less than
or equal to 5 bar according to EN 1775;
— compressed air systems;
— medical gas systems according to EN ISO 7396;
— refrigeration systems.
6
---------------------- Page: 8 ----------------------
oSIST prEN 1254-5:2019
prEN 1254-5:2019 (E)
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN 723, Copper and copper alloys — Combustion method for determination of the carbon content on the
inner surface of copper tubes or fittings
EN 806 (series), Specifications for installations inside buildings conveying water for human consumption
EN 1057:2006+A1:2010, Copper and copper alloys — Seamless, round copper tubes for water and gas in
sanitary and heating applications
EN 1092-3, Flanges and their joints — Circular flanges for pipes, valves, fittings and accessories, PN
designated — Part 3: Copper alloy flanges
prEN 1254-20:2019, Copper and copper alloys — Plumbing fittings — Part 20: Definitions, thread
dimensions, test methods, reference data and supporting information
EN 1775, Gas supply — Gas pipework for buildings — Maximum operating pressure less than or equal to 5
bar — Functional recommendations
EN 10226-3, Pipes threads where pressure tight joint are made on the threads — Part 3: Verification by
means of limit gauges
EN 12502-2, Protection of metallic materials against corrosion — Guidance on the assessment of
corrosion likelihood in water distribution and storage systems — Part 2: Influencing factors for copper
and copper alloys
EN 12735-1, Copper and copper alloys — Seamless, round tubes for air conditioning and refrigeration —
Part 1: Tubes for piping systems
EN 12735-2, Copper and copper alloys — Seamless, round tubes for air conditioning and refrigeration —
Part 2: Tubes for equipment
EN 12828, Heating systems in buildings — Design for water-based heating systems
EN 12845, Fixed firefighting systems — Automatic sprinkler systems — Design, installation and
maintenance
EN 13348, Copper and copper alloys — Seamless, round copper tubes for medical gases or vacuum
EN 13349, Copper and copper alloys — Pre-insulated copper tubes with solid covering
EN ISO 6506-1, Metallic materials — Brinell hardness test — Part 1: Test method (ISO 6506-1)
EN ISO 6507-1, Metallic materials — Vickers hardness test — Part 1: Test method (ISO 6507-1)
EN ISO 7396, Medical gas pipeline systems
EN ISO 17672, Brazing — Filler metals (ISO 17672:2016)
ISO 7-2, Pipe threads where pressure-tight joints are made on the threads — Part 2: Verification by means
of limit gauges
7
---------------------- Page: 9 ----------------------
oSIST prEN 1254-5:2019
prEN 1254-5:2019 (E)
ISO 228-2, Pipe threads where pressure-tight joints are not made on the threads — Part 2: Verification by
means of limit gauges
ISO 2859-1:1999, Sampling procedures for inspection by attributes — Part 1: Sampling schemes indexed
by acceptance quality limit (AQL) for lot-by-lot inspection
ISO 6957:1988, Copper alloys — Ammonia test for stress corrosion resistance
3 Terms and definitions
For the purposes of this document, the terms and definitions given in prEN 1254-20:2019 apply.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
— IEC Electropedia: available at http://www.electropedia.org/
— ISO Online browsing platform: available at http://www.iso.org/obp
4 Product characteristics
4.1 Internal pressure
When tested according to the method in 5.2 fittings shall show no signs of leakage or permanent
distortion.
4.2 Tightness
4.2.1 Leak tightness under internal hydrostatic pressure
Fittings assessed as indicated in 4.1 are considered to be leak tight under internal hydrostatic pressure.
4.2.2 Integrity of fabricated fitting bodies or having an 'as cast' microstructure
This requirement only applies to fitting bodies with an 'as cast' microstructure (excluding continuously
cast materials) or fabricated by welding or brazing.
When tested according to the method in 5.3.1 fitting bodies shall show no visual indication of leakage.
4.3 Release of dangerous substances
National regulations on dangerous substances may require verification and declaration on release, and
sometimes content, when construction products covered by this standard are placed on those markets.
In the absence of European harmonized test methods, verification and declaration on release/content
should be done taking into account national provisions in the place of use.
4.4 Durability
4.4.1 Durability of internal pressure
4.4.1.1 Resistance to stress corrosion
Fittings manufactured from copper and copper-tin-zinc alloys (CuSnZnPb) shall be considered to be
resistant to stress corrosion according to EN 12502-2 and copper-zinc-silicon alloys containing ≥ 2 % Si
are also considered to be resistant.
Fittings manufactured from CuZn-alloys shall be considered to be resistant to stress corrosion when the
product has a hardness HBW 2,5/62,5 ≤ 110 measured according to EN ISO 6506-1 or a hardness
10
HV ≤ 134 measured according to EN ISO 6507-1.
5
8
---------------------- Page: 10 ----------------------
oSIST prEN 1254-5:2019
prEN 1254-5:2019 (E)
Fittings manufactured from copper alloys with a zinc content of 10 % or greater not mentioned above
shall be tested and assessed according to 5.4.1.1, and shall show no evidence of cracking.
4.4.2 Durability of tightness
4.4.2.1 Residual carbon contamination in the bore
This requirement only applies for copper fittings. This requirement does not apply for copper alloy
fittings.
4.4.2.1.1 Carbon film
When tested according to 5.4.2.1 there shall not be any visible carbon film.
4.4.2.1.2 Total carbon
When tested according to 5.4.2.2 the maximum total carbon level on internal surfaces shall not exceed
2
1,0 mg/dm .
4.5 Dimensional tolerances of diameters
In order to achieve the capillary flow of a solder or brazing alloy when making a connection, the
dimensions of a socket or male end shall be tightly controlled.
When assessed according to the method specified in 5.5, the diameter shall be within the tolerances
expressed in Table 1 for the relevant diameters.
Table 1 — Tolerances on the nominal diameter
Values in millimetres
a
Nominal Tolerances on the mean diameter Resulting diametrical
diameter with respect to the nominal diameter difference
D D
Outside diameter Inside diameter max. min.
of male end of socket
6
8
10
12
+0,04 +0,15
0,20 0,02
14
−0,05 +0,06
14,7
15
16
18
21
22
+0,05 +0,18
25 0,24 0,02
−0,06 +0,07
27,4
28
9
---------------------- Page: 11 ----------------------
oSIST prEN 1254-5:2019
prEN 1254-5:2019 (E)
a
Nominal Tolerances on the mean diameter Resulting diametrical
diameter with respect to the nominal diameter difference
D D
Outside diameter Inside diameter max. min.
of male end of socket
b
34 +0,06 +0,23 0,03
−0,07 +0,09
b
35
b
40
b
40,5 0,30
b
42
b
53,6
b
54
b
64
b
66,7
b
70
b
76,1
+0,07 +0,33
0,41 0,03
b
−0,08 +0,10
80
b
88,9
b
106
b
108
b
133
+0,20 +0,70
0,90 0,03
b −0,20 +0,23
159
a
Arithmetical mean of two diameters at right angles in a cross-section taken anywhere on the length of
the socket or of the male end except under indented marking or in the solder or brazing alloy groove.
b
The soldering or brazing of tubes and fittings for these diameters requires more skilled techniques
(further information is available in in prEN 1254-20:2019, Annex A).
4.6 Wall thickness for short ends for capillary brazing to copper tubes
When measured according to the method specified in 5.6, the minimum wall thickness shall be as
expressed in Table 2 for the relevant diameters and different forms of the material.
The minimum wall thickness requirements do not apply under embossed marking on the socket end.
In the case of integral solder or brazing ring fittings where a groove is made within the soldering or
brazing length, the minimum wall thickness measured within or immediately adjacent the solder
groove (see Figure 1) shall be in accordance with dimension e' in Table 2.
10
---------------------- Page: 12 ----------------------
oSIST prEN 1254-5:2019
prEN 1254-5:2019 (E)
end feed fitting integral solder or brazing ring integral solder or brazing ring
fitting fitting
Key
D nominal diameter
e minimum wall thickness
e' minimum wall thickness within or immediately adjacent the solder or brazing ring groove
Figure 1 — Minimum wall thickness
Table 2 — Minimum wall thickness
Dimensions in millimetres
Nominal Minimum wall thickness
diameter
Wrought coppers Wrought copper alloys Cast coppers and copper
and continuous cast bar alloys
D e e' e e' e e'
6 0,6 0,54 1,0 0,55 1,0 0,65
8 0,6 0,54 1,0 0,55 1,0 0,65
10 0,6 0,54 1,0 0,55 1,0 0,65
12 0,6 0,54 1,1 0,60 1,1 0,71
14 0,6 0,54 1,1 0,60 1,1 0,71
14,7 0,7 0,63 1,2 0,66 1,2 0,78
15 0,7 0,63 1,2 0,66 1,2 0,78
16 0,7 0,63 1,2 0,66 1,2 0,78
11
---------------------- Page: 13 ----------------------
oSIST prEN 1254-5:2019
prEN 1254-5:2019 (E)
Nominal Minimum wall thickness
diameter
Wrought coppers Wrought copper alloys Cast coppers and copper
and continuous cast bar alloys
D e e' e e' e e'
18 0,8 0,72 1,4 0,77 1,4 0,91
21 0,9 0,81 1,4 0,77 1,4 0,91
22 0,9 0,81 1,4 0,77 1,5 0,97
25 0,9 0,81 1,4 0,77 1,6 1,04
27,4 0,9 0,81 1,5 0,82 1,6 1,04
28 0,9 0,81 1,5 0,82 1,8 1,17
34 1,0 0,90 1,6 0,88 1,8 1,17
35 1,0 0,90 1,6 0,88 1,8 1,17
40 1,1 0,99 1,8 0,99 2,0 1,30
40,5 1,1 0,99 1,8 0,99 2,0 1,30
42 1,1 0,99 1,8 0,99 2,0 1,30
53,6 1,2 1,08 1,9 1,04 2,3 1,49
54 1,2 1,08 1,9 1,04 2,3 1,49
64 1,4 1,26 2,0 1,10 2,4 1,56
66,7 1,4 1,26 2,0 1,10 2,4 1,56
70 1,4 1,26 2,3 1,26 2,6 1,69
76,1 1,6 1,44 2,6 1,43 2,8 1,82
80 1,8 1,62 2,8 1,54 2,9 1,88
88,9 1,8 1,62 2,9 1,59 3,1 2,01
106 2,1 1,89 3,3 1,80 3,5 2,27
108 2,1 1,89 3,3 1,80 3,5 2,27
133 2,3 2,07 4,2 2,31 4,5 2,92
159 2,6 2,34 5,2 2,86 5,5 3,57
12
---------------------- Page: 14 ----------------------
oSIST prEN 1254-5:2019
prEN 1254-5:2019 (E)
4.7 Wall thickness at threaded portions of adaptor fittings
This requirement only applies to fittings with an interface thread.
When assessed according to the method specified in 5.7 the minimum wall thickness at the interface
thread shall be as expressed in prEN 1254-20:2019, 4.1 for the relevant diameters.
4.8 Dimensions of tail pipe ends for swivel fittings
This requirement only applies to tail pipe ends for swivel fittings.
When assessed according to the method specified in 5.8 the dimensions shall be as expressed in
prEN 1254-20:2019, 4.2 for the thread size.
4.9 Dimensions of gas union connectors
This requirement only applies to fittings with gas union connectors.
When assessed according to the method specified in 5.9 the dimensions shall be as expressed in
prEN 1254-20:2019, 4.3 for corresponding nominal size.
4.10 Threaded end dimensions
This requirement only applies to fitting bodies with threaded ends.
When assessed according to the method specified in 5.10 the thread shall be in accordance with
prEN 1254-20:2019, 4.4.
4.11 Other adapter ends (not defined in prEN 1254-20:2019)
Other adapter ends, when assembled in accordance with the manufacturer's instructions and pressure
tested according to the method in 5.2 shall show no signs of leakage or permanent distortion
...