Erection and operation of electrical test equipment

Text prepared by BTTF 85-1 disbanded by D101/122

Errichten und Betreiben elektrischer Prüfanlagen

Installation et exploitation des équipements électriques d'essais

Erection and operation of electrical test equipment

General Information

Status
Withdrawn
Publication Date
31-Aug-2001
Withdrawal Date
19-Nov-2013
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
20-Nov-2013
Due Date
13-Dec-2013
Completion Date
20-Nov-2013

Relations

Buy Standard

Standard
EN 50191:2001
English language
18 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 50191:2001
01-marec-2001
Erection and operation of electrical test equipment
Erection and operation of electrical test equipment
Errichten und Betreiben elektrischer Prüfanlagen
Installation et exploitation des équipements électriques d'essais
Ta slovenski standard je istoveten z: EN 50191:2000
ICS:
19.080 (OHNWULþQRLQHOHNWURQVNR Electrical and electronic
SUHVNXãDQMH testing
SIST EN 50191:2001 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 50191:2001

---------------------- Page: 2 ----------------------

SIST EN 50191:2001
EUROPEAN STANDARD EN 50191
NORME EUROPÉENNE
EUROPÄISCHE NORM September 2000

ICS 29.020; 19.080


English version


Erection and operation of electrical test equipment


Installation et exploitation des Errichten und Betreiben elektrischer
équipements électriques d'essais Prüfanlagen






This European Standard was approved by CENELEC on 1999-10-01. CENELEC members are bound to
comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and
notified to the Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Czech Republic,
Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg, Netherlands, Norway,
Portugal, Spain, Sweden, Switzerland and United Kingdom.


CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: rue de Stassart 35, B - 1050 Brussels


© 2000 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.

  Ref. No. EN 50191:2000 E

---------------------- Page: 3 ----------------------

SIST EN 50191:2001
Page 2
EN 50191:2000
Foreword

The text of this European Standard, prepared by CENELEC BTTF 85-1, Erection and operation of electrical test
equipment, was submitted to the formal vote and was approved by CENELEC as EN 50191 on 1999-10-01.

The following dates were fixed:

– latest date by which the EN has to be implemented
 at national level by publication of an identical
 national standard or by endorsement (dop) 2001-03-01

– latest date by which the national standards conflicting
 with the EN have to be withdrawn (dow) 2002-10-01

Annexes designated "normative" are part of the body of the standard.
Annexes designated "informative" are given for information only.
In this standard, annex A is normative and annex B is informative.

__________

---------------------- Page: 4 ----------------------

SIST EN 50191:2001
Page 3
EN 50191:2000
Contents Page
Introduction.4
1 Scope.4
2 Normative references.4
3 Definitions.5
4 Erection of test installations .7
4.1 General.7
4.2 Test stations with automatic protection against direct contact.8
4.3 Test stations without automatic protection against direct contact .9
4.4 Test laboratories and experimental stations .10
4.5 Temporary test station .11
4.6 Test station without test personnel in permanent attendance.11
5 Operation of test installations.11
5.1 General.11
5.2 Personnel.11
5.3 Preparation of tests, switching operations in test stations.12
5.4 Test procedure.12
Annex A (normative) Permissible body currents and contact voltages .14
Annex B (informative) Example of an application illustrating the prohibition zone and test area .17

---------------------- Page: 5 ----------------------

SIST EN 50191:2001
Page 4
EN 50191:2000
Introduction
With reference to clause 5, the user of this EN, prepared in the field of application of Article 118 A of the EC
Treaty, should be aware that standards have no formal legal relationship with Directives which may have been
made under Article 118 A of the Treaty. In addition, national legislation in the Member states may contain more
stringent requirements than the minimum requirements of a Directive based on Article 118 A. Information on the
relationship between the national legislation implementing Directives based on Article 118 A and this EN may be
given in a national foreword of the national standard implementing this EN.
1 Scope
1.1 This standard is applicable to the erection and operation of fixed and temporary electrical test
installations.
1.2 Compliance with this standard is not necessary, if contact with live parts presents no danger. This is
the case when one of the following conditions is satisfied at live exposed points:
a) The voltage at frequencies above 500 Hz does not exceed 25 V a.c. or 60 V d.c. and complies with the
requirements for SELV or for PELV in accordance with HD 384.4.41.
b) In case of voltages at frequencies up to 500 Hz exceeding 25 V a.c.or 60 V d.c., the resultant current
through a non-inductive resistance of 2 kΩ does not exceed 3 mA a.c. (r.m.s.). or 12 mA d.c.
c) At frequencies above 500 Hz no hazardous body currents or contact voltages occur. In these cases the
national determined current and voltage values should be applied. If there are no national requirements
determined reference values for permissible body currents and contact voltages can be taken from
Table A.1 in Annex A.
d) The discharge energy does not exceed 350 mJ.
Even though compliance with this standard is not necessary if one of the above-mentioned conditions is
satisfied, other potential risks shall be considered and appropriate measures put into place to obviate the
risks.
1.3 This standard does not apply to the power supply to the test installations. In this case, the standards
of the HD 384 series (for nominal voltages up to 1000 V) or HD 637 S1 (for nominal voltages exceeding 1
kV) are applicable to erection and EN 50110-1 is applicable to operation.
1.4 Where no requirements are given in this standard, the standards of the HD 384 series (for nominal
voltages up to 1000 V) or HD 637 S1 (for nominal voltages exceeding 1 kV) apply to the erection of electrical
test installations and EN 50110-1 applies to the operation of electrical test installations.
2 Normative references
This European Standard incorporates by dated or undated reference, provisions from other publications.
These normative references are cited at the appropriate places in the text and the publications are listed
hereafter. For dated references, subsequent amendments to or revisions of any of these publications apply
to this European Standard only when incorporated in it by amendment or revision. For undated references
the latest edition of the publication referred to applies.
EN 294 Safety of machinery - Safety distance to prevent danger zones being reached by the upper
limbs
EN 418 Safety of machinery - Emergency stop equipment, functional aspects - Principles for
design
EN 574 Safety of machinery - Two-hand control devices - Functional aspects - Principles for design
EN 50110-1 Operation of electrical installations
EN 60529 Degrees of protection provided by enclosures (IP Code) (IEC 60529)
EN 61219 Live working - Earthing or earthing and short-circuiting equipment using lances as short-
circuiting device - Lance earthing (IEC 61219)
EN 61310-1 Safety of machinery - Indication, marking and actuation -- Part 1: Requirements for visual,
auditory and tactile signals (IEC 61310-1)

---------------------- Page: 6 ----------------------

SIST EN 50191:2001
Page 5
EN 50191:2000
EN 61558 Safety of power transformers, power supply units and similar (IEC 61558 series)
HD 366 Classification of electrical and electronic equipment with regard to protection against
electric shock (IEC 60536)
HD 384 series Electrical installations of buildings (IEC 60364 series, modified)
HD 637 S1 Power installations exceeding 1 kV a.c.
IEC 60050-826 International Electrotechnical Vocabulary -- Chapter 826: Electrical installations of
buildings
3 Definitions
For the purpose of this standard, the following definitions apply:
3.1
electrical test installations
(referred to in the following as test installations)
the entirety of all the test appliances and devices combined for test purposes, by means of which electrical
tests are performed on test objects
Test installations may be designed and erected or installed as:
- test station;
- test laboratory or experimental station;
- temporary test installations.
3.2
test station
appropriately identified test installations within a defined area in which only one or two persons are generally
employed on test work, e.g. in the line of series production or in electric workshops, repair and service shops
In test stations a distinction is made between those with and those without automatic protection against
direct contact.
3.2.1
test station with automatic protection against direct contact
a test station in which the test object and all live parts of the test apparatus have automatically activated full
protection against direct contact in an energized condition
NOTE  Automatic protection means that voltages can only occur when the safety devices are effective, e.g. when the
cover or door of the test station is closed.
3.2.2
test station without automatic protection against direct contact
a test station in which parts of the test object or live parts of the test apparatus are not fully protected
against direct contact during testing. This includes, for instance, test areas in electric workshops,
laboratories, measurement and experimental areas
3.3
test laboratory
test installations in a securely enclosed space or within an area separated from adjacent work areas, in
which several persons are generally employed on test work on larger test objects remaining there for a
longer period of time
A test laboratory may be subdivided into test areas in which mutually independent tests are performed.
3.4
experimental station
test installations for performing experiments or tests within the scope of research and development work. In
general, no routine tests are performed in experimental stations. A variety of test assemblies as well as
different hazards shall therefore be anticipated
An experimental station may be subdivided into sections in which mutually independent experiments or tests
are carried out.

---------------------- Page: 7 ----------------------

SIST EN 50191:2001
Page 6
EN 50191:2000
3.5
temporary test installations
test installations erected for a short time in order to perform tests on individual test objects
3.6
prohibition zone
a volume around live parts which should not be breached if full protection against direct contact with these
parts is not provided
3.7
test area
the area around the test assembly which is separated from the surrounding area
3.8
signal lights
lights which are clearly visible from outside the boundaries of the test area giving red or green signals to
indicate the operational status inside the test area
3.9
indicator lights
serve to indicate the switching status on the control panels. They are not an alternative to required signal
lights
3.10
risk
a combination of the probability and the degree of the possible injury or damage to health of a person
exposed to a hazard or to hazards
3.11
electrical hazard
a source of possible injury or damage to health in presence of electrical energy from an electrical installation
3.12
skilled person
a person with relevant education and experience to enable him or her to avoid dangers which electricity may
create. (IEV 826-09-01, modified)
3.13
instructed person
a person adequately advised by skilled persons to enable him or her to avoid dangers which electricity may
create (IEV 826-09-02, modified)
3.14
nominated person in control of a work activity
that person who has been nominated to be the person with direct management responsibility for the work
activity. parts of this responsibility may be delegated to others as required
3.15 Operational status
3.15.1
out of operation
status when
a) all power supplies, signalling and control circuits are switched off and secured against unauthorized
switching-on,
b) all safety precautions necessary before entering the test area (for voltages exceeding 1 kV, e.g.
earthing, short-circuiting) have been taken
3.15.2
ready for operation
status when
a) the power supplies for the switchgear signalling and control circuits of the test installations are switched
on,
b) the green signal lights, where these are required in accordance with the provisions in clause 4, are on,
c) all power supplies for the test voltage are switched off and secured against unintentional switching,
d) the safety precautions specified in 3.16.1 b ("out of operation") are in force

---------------------- Page: 8 ----------------------

SIST EN 50191:2001
Page 7
EN 50191:2000
3.15.3
ready to switch on
status when
a) all power supplies for the test voltage are switched off,
b) all entries to the test area are closed,
c) the red signal lights are switched on,
d) the safety precautions specified in 3.16.1 b ("Out of operation") are no longer in force
3.15.4
in operation
status when
a) all entries to the test area are closed,
b) the red signal lights are switched on,
c) one or more power supplies for the test voltage are switched on
NOTE  In clauses 4 and 5, the technical devices for setting up the operational status ready for operation and ready
to switch on are only required for certain test installations with voltages exceeding 1 kV.
4 Erection of test installations
4.1 General
4.1.1 Protection against electric shock
4.1.1.1 Test assembly
The test assembly shall be so arranged and designed that the protection against direct contact is secured
by insulation of live parts, covers, enclosures, obstacles or safe distances. A safe distance is ensured, when
the person carrying out the tests cannot reach the prohibition zone with parts of his / her body or tools.
Safety can also be satisfied by means of a two-hand control device or the use of two safety test probes to
apply the test voltage. Test leads with full protection against direct contact shall be used. Two-hand control
devices shall comply with EN 574, Type II or IIIB. Where several persons are involved in a test, a two-hand
control device shall be provided for each person of the test personnel and which are so connected that all
the two hand controls are required to be operated before the test supplies can be energised.
Safety test probes shall have the adequate insulation level for the applied test voltage. No clamping devices
shall be permitted for this purpose.
In case of measuring instruments and auxiliary appliances of protection Class I HD 366 (e.g. cathode ray
oscilloscope, sine wave generator), where the protective conductor is interrupted to facilitate testing, e.g.
because the enclosure has to be isolated from earth potential, the appliance shall be supplied from an
isolating transformer in accordance with EN 61558.
If a circuit and/or the enclosure of a measuring instrument or an auxiliary appliance designed for mains
connection is connected to live parts of the test assembly which can carry voltage to earth, then the internal
insulation of the supplying isolating transformer shall be rated at least for this voltage.
An effective protective measure for protection in case of a fault (protection against indirect contact) shall be
provided.
The test assembly shall be so designed and arranged in order to prevent the transfer of voltage to
extraneous conductive parts.
4.1.1.2 Prohibition zone
The boundary of the prohibition zone shall be determined in accordance with Table A.2 and is dependent on
the test voltage.
In case of voltages up to 1000 V, the surface of the live part is considered to be the boundary of the prohibi-
tion zone. In case of voltages exceeding 1 kV, reaching the prohibition zone is considered equal to touching
live parts.

---------------------- Page: 9 ----------------------

SIST EN 50191:2001
Page 8
EN 50191:2000
4.1.1.3 Barriers, test area
Test areas shall be separated from work areas and passageways. The barriers shall be so designed as to
- prevent access to the test area by persons other than the test persons
- prevent persons other than the test persons reaching the prohibition zone
- prevent persons outside the barrier reaching the operating devices of test installations which are located
inside the barrier
The minimum distance between the barrier enclosing the test area and the boundary of the prohibition zone
or operation devices shall be determined in accordance with Figure A.2 and Table A.3. In case of grid
barriers, the minimum distance between the barrier and the prohibition zone shall comply with Table A.4 at
any opening, where it is possible to reach through the barrier.
Barriers made of conductive materials shall be earthed or other measures shall be taken to prevent indirect
electric shock in case of a fault.
4.1.2 Indicator lights and signs
4.1.2.1 The test installations controls and test circuits shall be clearly identified.
4.1.2.2 Test installations shall have devices which indicate the operational status, e.g. indicator lights.
4.1.2.3 Test installations and test areas shall be clearly and visibly indicated by means of warning signs.
4.1.3 Emergency switching off
Test installations shall be provided with means for emergency switching off in order to cut off all electrical
energy which could result in danger. The devices or equipment shall be in accordance with the
requirements of EN 418. An adequate number of manual controls shall be provided inside and outside the
test area as appropriate to the size of the area and complexity of layout. Connection points, e.g. outlets of
the general power supply within the test area, shall be identified accordingly, if they are not interrupted by
the emergency switching off equipment.
4.1.4 Preventing unauthorized and unintentional switching-on
Test installations shall be secured against unauthorized and unintentional switching-on of test circuits.
Manual controls shall be clearly correlated to the respective test circuits.
4.1.5 Preventing automatic energizing
Automatic energizing of test circuits shall be prevented when mains voltage recovers after a power failure.
4.1.6 Protection against residual voltages and transfer of voltages
4.1.6.1 If there is a likelihood of danger due to residual voltages after switching-off test circuits, suitable
devices or equipment shall be provided for a safe discharge of energy.
4.1.6.2 Transfer of voltage to accessible conductive parts outside the test area shall be prevented by
adequate measures - e.g. earthing, shielding, appropriate cable routing - or these conductive parts shall be
protected against direct contact.
4.1.7 Protective measures against other hazards
Appropriate means of protection shall be provided, in cases where in addition to dangers due to voltages
other hazards are to be expected, e.g. due to arcs, noise, explosion, radiation, flying parts, formation of gas,
fire, dangerous substances.
4.2 Test stations with automatic protection against direct contact
4.2.1 The protection against direct contact in accordance with 4.1.1.1 must be satisfied by insulation of live
parts, covers or enclosures. The means of protection against direct contact shall guarantee at least the
defined degree of protection IP3X. in accordance with EN 60529 and include all parts of the test object.

---------------------- Page: 10 ----------------------

SIST EN 50191:2001
Page 9
EN 50191:2000
It shall not be possible to switch on the test voltages until the means of protection are fully operational and
functioning correctly. Opening the means of protection must disconnect the test voltage automatically.
Residual voltages shall be automatically reduced to a non-hazardous level before live parts can be touched.
Single fault conditions shall not prevent the test voltages from being switched off when the means of
protection are opened. The occurrence of the fault shall ensure that it is impossible to switch the test
voltages on again. It must not be possible to bypass the means of protection in an easy way.
4.2.2 Mechanical means of protection shall be adequately strong.
4.2.3 The degree of protection against direct contact IP3X. may be omitted if the enclosure complies with
the following requirements:
- means of protection for the automatic protection against direct contact shall be solid walls or barrier grids
(side length or diameter of the openings not exceeding 40 mm) at least 1800 mm high;
- the test enclosure must be equipped with devices which do not permit doors to the test area to be opened
until the test voltage has been switched off and secured against being switched on again and - if
necessary - earthed and short-circuited. It shall not be possible to disable these protective measures until
the doors have been closed.
4.2.4 The degree of protection, required in 4.2.1, may be omitted in exceptional cases, if the test object and
all live parts are fully protected against direct contact and a measure for protection in case of a fault
(protection against indirect contact) is efficient for the test object and the test apparatus during the test.
4.2.5 In the case of test stations with automatic protection against direct contact, barriers in accordance
with 4.1.1.3 and emergency switching off devices in accordance with 4.1.3 may be omitted.
4.3 Test stations without automatic protection against direct contact
4.3.1 Test stations without automatic protection against direct contact shall only be installed if the erection
of test stations with automatic protection against direct contact is not practicable, e.g.
- due to frequently changing test duties;
- in case of varying types of test objects;
- in case of serious difficulties in performing the work;
- when test duties occur only occasionally.
4.3.2 The barriers in accordance with 4.1.1.3 may be e.g. walls, grids, ropes, chains or bars subject to
national regulations. They shall be so designed that visual contact with the operator can be maintained from
outside at all times.
4.3.3 At least one emergency switching device shall be installed outside the test areas.
4.3.4 An adequate number of red signal lights, indicating the operational status, shall be installed.
4.3.5 If test circuits are electrically connected to the general power supply system, additional protection
shall be provided by means of a RCD with a rated difference current ≤ 30 mA. If the residual current includes
d.c. components, an appropriate RCD shall be used.
4.3.6 Test workbench tops shall be made of insulating materials.
4.3.7 Electrical equipment, e.g. measuring instruments, variable resistors, shall be incorporated in an
effective protective measure for protection in case of a fault (protection against indirect contact). This also
applies to the exposed conductive parts of test objects unless these parts of the test object are also included
in the test (e.g. insulation test, leakage current test, see Figure 1). Electrical equipment with protective
insulation or supplied by means of isolating transformers shall preferably be used.
4.3.8 The working area of test stations shall be such that movement of test personnel is not impeded.
National regulations shall be taken into consideration.
4.3.9 When safety test probes are used with voltages exceeding 1 kV, the high voltage side of the test
apparatus shall be electrically isolated from the supply mains and insulated from earth, same applying to test
probes and their leads. The test object shall also be isolated from earth where practicable.
The r.m.s. value of the leakage current (see IEC 60050-826) on the high voltage side of the test apparatus
shall not exceed 3 mA. This value shall not be exceeded even when a highly resistive connection is made
between the high voltage side and earth, e.g. for adjustment of potential of a measuring instrument (see
Figure 1).

---------------------- Page: 11 ----------------------

SIST EN 50191:2001
Page 10
EN 50191:2000

 1 Supply mains
 2 High voltage measuring instrument
 3 Test object ( isolated from earth)
 4 Protective conductor (connecting point) of the test object
 5 Ammeter with an internal resistance (including a necessary external
  resistance) of 2000 Ω (equivalent resistance for test personnel)
Figure 1 — Measurement of discharge current
4.3.10 In case of test stations in electric workshops, laboratory stands, measurement and experimental
stands, barriers in accordance with 4.3.2 and red signal lights in accordance with 4.3.3 may be omitted, if
the safety of bystanders is obtained otherwise by means of the arrangement or design of the test station and
the test installations are reliably controlled by the person carrying out the tests.
4.4 Test laboratories and experimental stations
4.4.1 The barriers in accordance with 4.1.1.3 shall be solid walls or grids (see Table A.4) at least 1800 mm
high. Entrances shall be provided with a warning sign "No unauthorized persons beyond this point" in
accordance with EN 61310-1.
In case of voltages up to 1000 V, the barriers may also be ropes, chains or bars. Solid walls or grids shall be
at least 1000 mm high.
4.4.2 A sufficient number of red and green signal lights shall be installed to indicate the operational status;
green signal lights are not required in case of voltages up to 1000 V.
When there are separate test areas within the test laboratory
- the operational status of each of the test areas shall be indicated by means of signal lights;
- red signal lights shall indicate "danger" for the entire test laboratory whenever the operational status
ready for operation or in operation exists in at least one of the test areas. In this case care should be
taken if access is required in other test areas.
4.4.3 Emergency escape doors, gates, etc. shall be able to be opened from the inside of the test area.
National regulations on escape routes and emergency exits shall be taken into account.
4.4.4 In test laboratories measures are required to prevent unauthorized entry and shall not hinder persons
from leaving.
4.4.5 In test laboratories with voltages exceeding 1 kV devices or provisions for earthing shall be available
(cf. EN 50110-1 and EN 61219).
4.4.6 Where the test voltages exceed 1 kV, all areas including those outside the test area where capacitive
charging is likely to take place, shall be separated by additional barriers for the duration of the testing.
These additional barriers shall meet as a minimum the requirements for temporary test installations in 4.5.1.

---------------------- Page: 12 ----------------------

SIST EN 50191:2001
Page 11
EN 50191:2000
4.4.7 For experimental stations, the requirements of 4.4.1 to 4.4.6 are generally applicable. If, however,
compliance with individual safety measures required by these subclauses should not be appropriate with
regard to the type of construction, the protection of personnel required in test areas shall be secured by
equally effective other means or measures.
NOTE  One such measure is, e.g. with reference to 4.4.4, continuous supervision of access.
4.5 Temporary test station
4.5.1 Unauthorized persons shall be prevented from access to temporary test areas by means of walls,
grids, ropes, chains, bars or similar barriers. Entrances shall b
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.