Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 3-41: Cables with special fire performance - Single core non-sheathed cables with halogen-free crosslinked insulation, and low emission of smoke

EN 50525-2-41 applies to cross-linked silicone rubber insulated single core cables. The types included are either insulated only, or insulated and braided, or insulated and sheathed. The cables are of rated voltages U0/U up to and including 300/500 V. The cables are intended for use in fixed installations within high temperature zones. The maximum conductor operating temperature for each of the cables in this standard is 180 °C.

Kabel und Leitungen - Starkstromleitungen mit Nennspannungen bis 450/750 V (U0/U) - Teil 3-41: Leitungen mit verbessertem Verhalten im Brandfall - Halogenfreie, raucharme Ader- und Verdrahtungsleitungen mit vernetzter Isolierung

Câbles électriques - Câbles d’énergie basse tension de tension assignée au plus égale à 450/750 V (U0/U) - Partie 3-41: Câbles à performances spéciales au feu - Conducteurs isolés en matériau élastomère réticulé sans halogène, à faible dégagement de fumée

Električni kabli - Nizkonapetostni energetski kabli z nazivno napetostjo do vključno 450/750 V (U0/U) - 3-41. del: Kabli s posebnimi ognjevarnimi lastnostmi - Enožilni neoplaščeni kabli z zamreženo izolacijo brez halogenov in z nizko emisijo dima

EN 50525-2-41 velja za enožilne kable z zamreženo izolacijo iz silikonske gume. Tipi, ki so vključeni, so ali samo izolirani ali izolirani in pleteni ali pa izolirani in oplaščeni. Ti kabli imajo nazivno napetost U0/U do vključno 300/500 V. Kabli se uporabljajo pri fiksnih inštalacijah na območjih z visokimi temperaturami. Maksimalna delovna temperatura pretvornika za vsakega od kablov iz tega standarda je 180 °C.

General Information

Status
Published
Public Enquiry End Date
28-Feb-2009
Publication Date
12-Jun-2011
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
08-Jun-2011
Due Date
13-Aug-2011
Completion Date
13-Jun-2011

Relations

Buy Standard

Standard
EN 50525-3-41:2011
English language
11 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 50525-3-41:2011
01-september-2011
(OHNWULþQLNDEOL1L]NRQDSHWRVWQLHQHUJHWVNLNDEOL]QD]LYQRQDSHWRVWMRGR
YNOMXþQR9 88 GHO.DEOLVSRVHEQLPLRJQMHYDUQLPLODVWQRVWPL
(QRåLOQLQHRSODãþHQLNDEOL]]DPUHåHQRL]RODFLMREUH]KDORJHQRYLQ]QL]NRHPLVLMR
GLPD
Electric cables - Low voltage energy cables of rated voltages up to and including 450/750
V (U0/U) - Part 3-41: Cables with special fire performance - Single core non-sheathed
cables with halogen-free crosslinked insulation, and low emission of smoke
Kabel und Leitungen - Starkstromleitungen mit Nennspannungen bis 450/750 V (U0/U) -
Teil 3-41: Leitungen mit verbessertem Verhalten im Brandfall - Halogenfreie, raucharme
Ader- und Verdrahtungsleitungen mit vernetzter Isolierung
Câbles électriques - Câbles d’énergie basse tension de tension assignée au plus égale à
450/750 V (U0/U) - Partie 3-41: Câbles à performances spéciales au feu - Conducteurs
isolés en matériau élastomère réticulé sans halogène, à faible dégagement de fumée
Ta slovenski standard je istoveten z: EN 50525-3-41:2011
ICS:
29.060.20 Kabli Cables
SIST EN 50525-3-41:2011 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 50525-3-41:2011

---------------------- Page: 2 ----------------------

SIST EN 50525-3-41:2011

EUROPEAN STANDARD
EN 50525-3-41

NORME EUROPÉENNE
May 2011
EUROPÄISCHE NORM

ICS 29.060.20 Supersedes HD 22.9 S3:2007


English version


Electric cables -
Low voltage energy cables of rated voltages up to and including 450/750 V
(U /U) -
0
Part 3-41: Cables with special fire performance -
Single core non-sheathed cables with halogen-free crosslinked insulation,
and low emission of smoke


Câbles électriques -  Kabel und Leitungen -
Câbles d’énergie basse tension de tension Starkstromleitungen mit Nennspannungen
assignée au plus égale à 450/750 V bis 450/750 V (U /U) -
0
(U /U) - Teil 3-41: Starkstromleitungen mit
0
Partie 3-41: Câbles à performances verbessertem Verhalten im Brandfall -
spéciales au feu - Halogenfreie, raucharme Ader- und
Conducteurs isolés en matériau Verdrahtungsleitungen mit vernetzter
élastomère réticulé sans halogène, à Isolierung
faible dégagement de fumée

This European Standard was approved by CENELEC on 2011-01-17. CENELEC members are bound to comply
with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and notified
to the Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus,
the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy,
Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia,
Spain, Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Management Centre: Avenue Marnix 17, B - 1000 Brussels


© 2011 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 50525-3-41:2011 E

---------------------- Page: 3 ----------------------

SIST EN 50525-3-41:2011
EN 50525-3-41:2011 - 2 -
Foreword
This European Standard was prepared by the Technical Committee CENELEC TC 20, Electric
cables.

The text of the draft was submitted to the formal vote and was approved by CENELEC as
EN 50525-3-41 on 2011-01-17.

This document, which is one of a multipart series, supersedes HD 22.9 S3:2007.

Attention is drawn to the possibility that some of the elements of this document may be the
subject of patent rights. CEN and CENELEC shall not be held responsible for identifying any
or all such patent rights.

The following dates were fixed:

– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2012-01-17

– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2014-01-17
____________

---------------------- Page: 4 ----------------------

SIST EN 50525-3-41:2011
- 3 - EN 50525-3-41:2011
Contents
Page
1 Scope . 4
2 Normative references . 4
3 Terms and definitions . 5
4 Heat resistant cables (90 °C) . 5
4.1 Cables for fixed wiring – H07Z-U and H07Z-R . 5
4.2 Cables for fixed wiring – H07Z-K . 5
4.3 Cables for internal wiring – H05Z-U . 6
4.4 Cables for internal wiring – H05Z-K . 7
Annex A (normative) Tests for cables to EN 50525-3-41 . 8
Annex B (normative) General data . 9
Bibliography . 11

Tables
Table A.1 . 8
Table B.1 − Cables with rigid conductor (450/750 V) . 9
Table B.2 − Cables with flexible conductor (450/750 V) . 10
Table B.3 − Cables with rigid conductor (300/500 V) . 10
Table B.4 − Cables with flexible conductor (300/500 V) . 10

---------------------- Page: 5 ----------------------

SIST EN 50525-3-41:2011
EN 50525-3-41:2011 - 4 -
1 Scope
EN 50525-3-41 applies to non-sheathed single core cables insulated with halogen-free
crosslinked compound and having low emission of smoke and corrosive gases when exposed
to fire.
NOTE 1 Low emission of smoke is checked in accordance with EN 61034-2. Low emission of corrosive gases is checked as
part of the check for absence of halogens (see Annex B of EN 50525-1).
The cables are of rated voltages U /U up to and including 450/750 V.
0
NOTE 2 Cables rated 450/750 V may be used at 600/1 000 V when this cable is used in fixed installations with
mechanical protection, within switchgear and control gear - see HD 516.
The cables are intended for fixed wiring applications.
The maximum conductor operating temperature for each of the cables in this standard is
90 °C.
NOTE 3 HD 516 contains extensive guidance on the safe use of cables in this standard.
This EN 50525-3-41 should be read in conjunction with EN 50525-1, which specifies general
requirements.
2 Normative references
The following referenced documents are indispensable for the application of this document.
For dated references, only the edition cited applies. For undated references, the latest edition
of the referenced document (including any amendments) applies.
NOTE One or more references to the standards below are in respect of a specific sub-division of that standard,
for instance a clause, a table, a class or a type. Cross-references to these standards are undated and, at all times,
the latest version applies.

EN 50363-5 Insulating, sheathing and covering materials for low voltage
energy cables - Part 5: Halogen-free, cross-linked insulating
compounds
EN 50395 Electrical test methods for low voltage energy cables
EN 50396 Non electrical test methods for low voltage energy cables
EN 50525-1 Electric cables - Low voltage energy cables of rated voltages up
to and including 450/750 V (U /U) - Part 1: General requirements
0
EN 60228 Conductors of insulated cables (IEC 60228)
EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions -
Part 1-2: Test for vertical flame propagation for a single insulated
wire or cable - Procedure for 1 kW pre-mixed flame
(IEC 60332-1-2)
EN 60811-1-4 Insulating and sheathing materials of electric and optical cables -
Common test methods - Part 1-4: General application - Test
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.