Lamp controlgear -- Part 2-7: Particular requirements for d.c. supplied electronic ballasts for emergency lighting

This part of IEC 61347 specifies particular safety requirements for d.c. supplied electronic ballasts for maintained and non-maintained emergency lighting purposes. It includes specific requirements for ballasts and control units for luminaires for emergency lighting as specified by IEC 60598-2-22. DC supplied electronic ballasts for emergency lighting may or may not include batteries. This standard also includes operational requirements for ballasts which, in the case of other d.c. supplied electronic ballasts, are regarded as performance requirements. This is because non-operational emergency lighting equipment presents a safety hazard.

Geräte für Lampen -- Teil 2-7: Besondere Anforderungen an gleichstromversorgte elektronische Vorschaltgeräte für die Notbeleuchtung

Appareillages de lampes -- Partie 2-7: Exigences particulières pour les ballasts électroniques alimentés en courant continu pour l'éclairage de secours

La présente partie de la CEI 61347 spécifie les exigences particulières de sécurité pour les ballasts électroniques alimentés en courant continu prévus pour l'éclairage de secours permanent ou non permanent. Cette norme comprend des exigences particulières pour les ballasts et pour les blocs de commande pour l'éclairage de secours spécifiés dans la CEI 60598-2-22.

Stikalne naprave za sijalke – 2-7. del: Posebne zahteve za enosmerno napajane elektronske predstikalne naprave za nujnostno razsvetljavo (IEC 61347-2-7:2006)

General Information

Status
Withdrawn
Publication Date
19-Jul-2007
Withdrawal Date
01-Nov-2015
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
29-Oct-2015
Due Date
21-Nov-2015
Completion Date
02-Nov-2015

Relations

Buy Standard

Standard
EN 61347-2-7:2007
English language
26 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 61347-2-7:2007
01-september-2007
1DGRPHãþD
SIST EN 61347-2-7:2002
Stikalne naprave za sijalke – 2-7. del: Posebne zahteve za enosmerno napajane
elektronske predstikalne naprave za nujnostno razsvetljavo (IEC 61347-2-7:2006)
Lamp controlgear -- Part 2-7: Particular requirements for d.c. supplied electronic ballasts
for emergency lighting
Geräte für Lampen -- Teil 2-7: Besondere Anforderungen an gleichstromversorgte
elektronische Vorschaltgeräte für die Notbeleuchtung
Appareillages de lampes -- Partie 2-7: Exigences particulières pour les ballasts
électroniques alimentés en courant continu pour l'éclairage de secours
Ta slovenski standard je istoveten z: EN 61347-2-7:2006
ICS:
29.130.01 Stikalne in krmilne naprave Switchgear and controlgear
na splošno in general
29.140.99 Drugi standardi v zvezi z Other standards related to
žarnicami lamps
SIST EN 61347-2-7:2007 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

EUROPEAN STANDARD
EN 61347-2-7

NORME EUROPÉENNE
December 2006
EUROPÄISCHE NORM

ICS 29.140.99 Supersedes EN 61347-2-7:2001


English version


Lamp controlgear
Part 2-7: Particular requirements for d.c. supplied electronic ballasts
for emergency lighting
(IEC 61347-2-7:2006)


Appareillages de lampes  Geräte für Lampen
Partie 2-7: Exigences particulières Teil 2-7: Besondere Anforderungen
pour les ballasts électroniques alimentés an gleichstromversorgte elektronische
en courant continu pour l'éclairage Vorschaltgeräte für die Notbeleuchtung
de secours (IEC 61347-2-7:2006)
(CEI 61347-2-7:2006)




This European Standard was approved by CENELEC on 2006-11-01. CENELEC members are bound to comply
with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and notified
to the Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Cyprus, the Czech
Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: rue de Stassart 35, B - 1050 Brussels


© 2006 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 61347-2-7:2006 E

---------------------- Page: 2 ----------------------

EN 61347-2-7:2006 - 2 -
Foreword
The text of document 34C/754/FDIS, future edition 2 of IEC 61347-2-7, prepared by SC 34C,
Auxiliaries for lamps, of IEC TC 34, Lamps and related equipment, was submitted to the
IEC-CENELEC parallel vote and was approved by CENELEC as EN 61347-2-7 on 2006-11-01.
This European Standard supersedes EN 61347-2-7:2001 + corrigendum July 2003.
This EN 61347-2-7:2006 provides technical updating to take account of the practical usage of this type
of control gear, alignment with the safety requirements for emergency lighting luminaires
(EN 60598-2-22), and advances in the field of lamp and control gear.
This standard shall be used in conjunction with EN 61347-1:2001.
In this standard, the following print types are used:
– requirements : in roman type;
– test specifications: in italic type;
– notes: in smaller roman type.
The following dates were fixed:
– latest date by which the EN has to be implemented
at national level by publication of an identical
(dop) 2007-08-01
national standard or by endorsement
– latest date by which the national standards conflicting
(dow) 2009-11-01
with the EN have to be withdrawn
Annex ZA has been added by CENELEC.
__________
Endorsement notice
The text of the International Standard IEC 61347-2-7:2006 was approved by CENELEC as a European
Standard without any modification.
__________

---------------------- Page: 3 ----------------------

- 3 - EN 61347-2-7:2006

Annex ZA
(normative)

Normative references to international publications
with their corresponding European publications

The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.

NOTE  When an international publication has been modified by common modifications, indicated by (mod), the relevant EN/HD
applies.

Publication Year Title EN/HD Year
1) 2)
IEC 60081 - Double-capped fluorescent lamps - EN 60081 1998
Performance specifications


IEC 60598-2-22 1997 Luminaires EN 60598-2-22 1998
(mod) Part 2-22: Particular requirements - + corr. December 2005
Luminaires for emergency lighting


1) 2)
IEC 60901 - Single-capped fluorescent lamps - EN 60901 1996
Performance specifications


1) 2)
IEC 60921 - Ballasts for tubular fluorescent lamps - EN 60921 2004
Performance requirements


1) 2)
IEC 60929 - AC-supplied electronic ballasts for tubular EN 60929 2006
fluorescent lamps - Performance + corr. December 2006
requirements


1) 2)
IEC 61347-1 - Lamp controlgear EN 61347-1 2001
Part 1: General and safety requirements + corr. July 2003


1) 2)
IEC 61347-2-3 - Lamp controlgear EN 61347-2-3 2001
Part 2-3: Particular requirements for a.c. + corr. July 2003
supplied electronic ballasts for fluorescent
lamps


3)
IEC 61558-1 (mod) 1997 Safety of power transformers, power EN 61558-1 1997
supply units and similar + corr. April 2003
Part 1: General requirements and tests + A11 2003


IEC 61558-2-1 1997 Safety of power transformers, power EN 61558-2-1 1997
supply units and similar
Part 2-1: Particular requirements for
separating transformers for general use



1)
Undated reference.
2)
Valid edition at date of issue.
3)
EN 61558-1 is superseded by EN 61558-1:2005, which is based on IEC 61558-1:2005.

---------------------- Page: 4 ----------------------

EN 61347-2-7:2006 - 4 -
Publication Year Title EN/HD Year
IEC 61558-2-6 1997 Safety of power transformers, power EN 61558-2-6 1997
supply units and similar
Part 2-6: Particular requirements for safety
isolating transformers for general use


IEC 61558-2-17 1997 Safety of power transformers, power EN 61558-2-17 1997
supply units and similar
Part 2-17: Particular requirements for
transformers for switch mode power supplies

---------------------- Page: 5 ----------------------

NORME CEI
INTERNATIONALE
IEC



61347-2-7
INTERNATIONAL


Deuxième édition
STANDARD

Second edition

2006-08


Appareillages de lampes –
Partie 2-7:
Exigences particulières pour les ballasts
électroniques alimentés en courant continu pour
l'éclairage de secours

Lamp controlgear –
Part 2-7:
Particular requirements for d.c. supplied
electronic ballasts for emergency lighting

 IEC 2006 Droits de reproduction réservés  Copyright - all rights reserved
Aucune partie de cette publication ne peut être reproduite ni No part of this publication may be reproduced or utilized in any
utilisée sous quelque forme que ce soit et par aucun procédé, form or by any means, electronic or mechanical, including
électronique ou mécanique, y compris la photocopie et les photocopying and microfilm, without permission in writing from
microfilms, sans l'accord écrit de l'éditeur. the publisher.
International Electrotechnical Commission, 3, rue de Varembé, PO Box 131, CH-1211 Geneva 20, Switzerland
Telephone: +41 22 919 02 11 Telefax: +41 22 919 03 00 E-mail: inmail@iec.ch Web: www.iec.ch
CODE PRIX
S
PRICE CODE
Commission Electrotechnique Internationale
International Electrotechnical Commission
МеждународнаяЭлектротехническаяКомиссия
Pour prix, voir catalogue en vigueur
For price, see current catalogue

---------------------- Page: 6 ----------------------

61347-2-7  IEC:2006 – 3 –
CONTENTS
FOREWORD.7
INTRODUCTION.11

1 Scope.13
2 Normative references .13
3 Definitions .15
4 General requirements .19
5 General notes on tests .19
6 Classification.21
7 Marking .21
8 Protection against accidental contact with live parts .21
9 Terminals .23
10 Provisions for earthing.23
11 Moisture resistance and insulation.23
12 Electric strength .23
13 Thermal endurance test for windings .23
14 Pulse voltages for ballast for central battery systems .23
15 Starting conditions.23
16 Lamp current and ballast lumen factor (BLF) .25
17 Supply current .25
18 Maximum current in any lead (with cathode preheating) .27
19 Lamp operating current waveforms.27
20 Functional safety (EBLF) .27
21 Change over operation .29
22 Recharging device.29
23 Protection against excessive discharge .33
24 Indicator .33
25 Remote control .33
26 Temperature cycling test and endurance test .33
27 Polarity reversal .35
28 Fault conditions .35
29 Construction .35
30 Creepage distances and clearances .35
31 Screws, current-carrying parts and connections.35
32 Resistance to heat, fire and tracking.35
33 Resistance to corrosion .35

---------------------- Page: 7 ----------------------

61347-2-7  IEC:2006 – 5 –
Annex A (normative) Test to establish whether a conductive part is a live part, which
may cause an electric shock .39
Annex B (normative) Particular requirements for thermally protected lamp control gear .39
Annex C (normative) Particular requirements for electronic lamp control gear with
means of protection against overheating.39
Annex D (normative) Requirements for carrying out the heating test of thermally
protected lamp control gear .39
Annex E (normative) Use of constant S other than 4 500 in t tests .41
w
Annex F (normative) Draught-proof enclosure.41
Annex G (normative) Explanation of the derivation of the values of pulse voltages .41
Annex H (normative) Tests .41
Annex I (normative) Batteries for emergency lighting luminaires .41
Annex J (informative) Rest mode and inhibition mode facilities .43

Figure 1 – Suitable circuits for the measurement of lamp current and luminous flux .37

Table 1 – Pulse voltages.23
Table 2 – Voltage per cell to which the battery is discharged .31

---------------------- Page: 8 ----------------------

61347-2-7  IEC:2006 – 7 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________

LAMP CONTROLGEAR –

Part 2-7: Particular requirements for d.c. supplied electronic ballasts
for emergency lighting


FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with an IEC Publication.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 61347-2-7 has been prepared by subcommittee 34C: Auxiliaries
for lamps, of IEC technical committee 34: Lamps and related equipment.
This second edition cancels and replaces the first edition published in 2000 and constitutes a
technical revision. This new edition of IEC 61347-2-7 provides technical updating to take
account of the practical usage of this type of control gear, alignment with the safety
requirements for emergency lighting luminaires (IEC 60598-2-22), and advances in the field of
lamp and control gear designs that have occurred since this standards last technical revision
in 1993 (formerly IEC 60924).

---------------------- Page: 9 ----------------------

61347-2-7  IEC:2006 – 9 –
The text of this standard is based on the following documents:
FDIS Report on voting
34C/754/FDIS 34C/761/RVD

Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
This standard shall be used in conjunction with IEC 61347-1. It was established on the basis
of the first (2000) edition of that standard.
This part 2 supplements or modifies the corresponding clauses in IEC 61347-1, so as to
convert that publication into the IEC Standard: Particular requirements for d.c. supplied
electronic ballasts for emergency lighting.
NOTE In this standard, the following print types are used:
− requirements: in roman type;
− test specifications: in italic type;
− notes: in small roman type.
A list of all parts of the IEC 61347 series, published under the general title Lamps controlgear,
can be found on the IEC website.
The committee has decided that the contents of this publication will remain unchanged until
the maintenance result date indicated on the IEC web site under "http://webstore.iec.ch" in
the data related to the specific publication. At this date, the publication will be
• reconfirmed;
• withdrawn;
• replaced by a revised edition, or
• amended.

---------------------- Page: 10 ----------------------

61347-2-7  IEC:2006 – 11 –
INTRODUCTION
The formatting into separately published parts provides for ease of future amendments and
revisions. Additional requirements will be added as and when a need for them is recognized.
This standard is intended for ballasts for fluorescent lamps, but it is also applicable, as far as
possible, to incandescent, high pressure discharge lamps and LED’s.
This standard, and the parts which make up IEC 61347-2, in referring to any of the clauses of
IEC 61347-1, specify the extent to which such a clause is applicable and the order in which
the tests are to be performed; they also include additional requirements, as necessary. All
parts, which make up IEC 61347-2 are self-contained and, therefore, do not include reference
to each other.
Where the requirements of any of the clauses of IEC 61347-1 are referred to in this standard
by the phrase “The requirements of Clause n of IEC 61347-1 apply", this phrase is interpreted
as meaning that all requirements of the clause in question of Part 1 apply, except any which
are clearly inapplicable to the specific type of lamp control gear covered by this particular part
of IEC 61347-2.

---------------------- Page: 11 ----------------------

61347-2-7  IEC:2006 – 13 –
LAMP CONTROLGEAR –

Part 2-7: Particular requirements for d.c. supplied electronic ballasts
for emergency lighting



1 Scope
This part of IEC 61347 specifies particular safety requirements for d.c. supplied electronic
ballasts for maintained and non-maintained emergency lighting purposes.
It includes specific requirements for ballasts and control units for luminaires for emergency
lighting as specified by IEC 60598-2-22.
DC supplied electronic ballasts for emergency lighting may or may not include batteries.
This standard also includes operational requirements for ballasts which, in the case of other
d.c. supplied electronic ballasts, are regarded as performance requirements. This is because
non-operational emergency lighting equipment presents a safety hazard.
NOTE Annex J of IEC 61347-2-3 applies to a.c. supplied ballasts (normal operation) that are also suitable for
emergency lighting operation from ac/dc supplies.
2 Normative references
For the purpose of this part of IEC 61347, the normative references given in Clause 2 of
IEC 61347-1, which are mentioned in this standard, apply, together with the following
normative references.
IEC 60081, Double-capped fluorescent lamps – Performance specifications
IEC 60598-2-22:1997, Luminaires – Part 2: Particular requirements – Luminaires for
emergency lighting
IEC 60901, Single-capped fluorescent lamps – Performance specifications
IEC 60921, Ballasts for tubular fluorescent lamps – Performance requirements
IEC 60929, AC-supplied electronic ballasts for tubular fluorescent lamps – Performance
requirements
IEC 61347-1, Lamp controlgear – Part 1: General and safety requirements
IEC 61347-2-3, Lamp controlgear – Part 2-3: Particular requirements for a.c. supplied electronic
ballasts for fluorescent lamps

---------------------- Page: 12 ----------------------

61347-2-7  IEC:2006 – 15 –
IEC 61558-1:1997, Safety of power transformers, power supplies, reactors and similar
products – Part 1: General requirements and tests
IEC 61558-2-1:1997, Safety of power transformers, power supply units and similar – Part 2-1:
Particular requirements for separating transformers for general use.
IEC 61558-2-6:1997, Safety of power transformers, power supply units and similar – Part 2-6:
Particular requirements for safety isolating transformers for general use
IEC 61558-2-17:1997,Safety of power transformers, power supply units and similar – Part 2-
17: Particular requirements for transformers for switch mode power supplies
3 Definitions
For the purpose of this part of IEC 61347, the definitions of Clause 3 of IEC 61347-1 and
Clause 22.3 in IEC 60598-2-22:1997 applies, together with the following:
3.1
emergency lighting
lighting provided for use when the supply to the normal lighting fails
1
[CIE 17.4]
3.2
continual operation ballast
ballast for operating a lamp from the normal lighting supply with normal switching and also
from the emergency lighting supply when failure of the normal lighting supply occurs
3.3
intermittent operation ballast
ballast for operating a lamp from the emergency lighting supply only when failure of the
normal lighting supply occurs
3.4
changeover operation
automatic connection of the lamp to emergency lighting supply when failure of the normal
lighting supply occurs, and connecting automatically back to the normal lighting supply when
it is restored
3.5
recharging device
device to maintain the battery charge and to recharge the battery within a specified time
3.6
protection device against extensive discharge
automatic device to disconnect the ballast from the battery when the battery voltage drops
below a certain value
—————————
1
 International Lighting Vocabulary

---------------------- Page: 13 ----------------------

61347-2-7  IEC:2006 – 17 –
3.7
rated duration of emergency operation
time, as claimed by the manufacturer, for which the rated emergency ballast lumen factor is
achieved
3.8
maximum d.c. operating voltage
maximum supply voltage declared by the ballast manufacturer. For battery supplied ballasts
this is the maximum battery voltage available in the fully charged condition
3.9
rated d.c. operating voltage
nominal supply voltage declared by the ballast manufacturer. For battery supplied ballasts
this is the nominal battery voltage declared by the battery manufacturer
3.10
minimum d.c. operating voltage
minimum supply voltage declared by the ballast manufacturer. For battery supplied ballasts
this is the minimum battery voltage available at the end of emergency operation
3.11
d.c. voltage range
voltage range between minimum and maximum rated d.c. operating voltages
3.12
maximum a.c. operating voltage
maximum supply voltage declared by the ballast manufacturer for battery charger or
maintained ballast operation
3.13
rated a.c. operating voltage
nominal supply voltage declared by the ballast manufacturer for battery charger or maintained
ballast operation
3.14
minimum a.c. operating voltage
minimum supply voltage declared by the ballast manufacturer for battery charger or
maintained ballast operation
3.15
a.c. voltage range
voltage range between minimum and maximum rated a.c. operating voltages
3.16
remote control
device to prevent discharge of the battery by the lamp operating circuit, when normal
illumination has been switched off centrally, e.g. during night-time

---------------------- Page: 14 ----------------------

61347-2-7  IEC:2006 – 19 –
3.17
indicator
device to indicate that:
a) the battery is being charged
b) circuit continuity exists through the tungsten filament of emergency lighting lamps where
appropriate
3.18
ballast lumen factor
BLF
ratio of the luminous flux of the lamp when the ballast under test is operated at its rated
voltage, to the luminous flux of the same lamp operated with the appropriate reference ballast
supplied at its rated voltage and frequency
3.19
emergency ballast lumen factor
EBLF
ratio of the emergency luminous flux of the lamp supplied by the emergency ballast to the
luminous flux of the same lamp operated with the appropriate reference ballast at its rated
voltage and frequency. The emergency ballast lumen factor is the minimum of the values
measured at the appropriate time after failure of the normal supply and continuously to the
end of the rated time duration
3.20
starting aid
conductive strip affixed to the outer surface of a lamp or a conductive plate, which is placed at
an appropriate distance from a lamp
3.21
control unit
unit or units comprising a supply change-over system, a battery charging device and where
appropriate, a means for testing
4 General requirements
The requirements of Clause 4 of IEC 61347-1 apply.
For ballasts that are rated for operation of a range of lamp types the tests of Clauses 15, 16,
17, 18, 19, 20 and 22 shall be repeated with each rated lamp type. For other tests the lamp
type having the highest rated power should be selected.
5 General notes on tests
The requirements of Clause 5 of IEC 61347-1 apply, together with the following additional
requirement:
– Number of specimens
The following number of specimens shall be submitted for testing:
– 1 unit for the tests of Clauses 6 to 12, 14 to 27 and 29 to 31.
– 1 unit for the test of Clause 28, fault conditions (additional units or components, where
necessary, may be required in consultation with the manufacturer).

---------------------- Page: 15 ----------------------

61347-2-7  IEC:2006 – 21 –
6 Classification
The requirements of Clause 6 of IEC 61347-1 apply.
7 Marking
7.1 Items to be marked
Ballasts shall be clearly and durably marked, in accordance with the requirements of 7.2 of
IEC 61347-1, with the following mandatory markings:
– items a), b), c), d), e), f), k) and l) of 7.1 of IEC 61347-1, together with open circuit voltage
(for warning only, not to be tested);
– indication of type and current rating of the fuse, if applicable.