Abstract

IEC 61009-1:2024, Clause 1 is applicable except for the first paragraph and the last paragraph,
which are replaced by the following, respectively:
This document applies to residual current operated circuit-breakers with integral overcurrent
protection for household and similar uses (hereafter referred to as RCBOs), classified according
to IEC 61009-1:2024, 4.1.1. RCBOs according to this document are intended for voltages not
exceeding 440 V AC with frequencies of 50 Hz, 60 Hz or 50/60 Hz and currents not exceeding
125 A and rated short-circuit capacities not exceeding 25 000 A for operation at 50 Hz or 60 Hz.
This document applies in conjunction with IEC 61009-1:2024. It specifies requirements, tests
and test sequences to verify compliance and is used for certification purposes.

Status
Not Published
Public Enquiry End Date
27-Feb-2026
Technical Committee
EPR - Electrical accessories
Current Stage
5020 - Formal vote (FV) (Adopted Project)
Start Date
27-Oct-2026
Due Date
15-Dec-2026

Buy Documents

Draft

oSIST prEN IEC 61009-2-1:2026/oprAA:2026

English language (9 pages)
Preview
Preview
e-Library read for
×1 day

kSIST FprEN IEC 61009-2-1:2026/kFprAA:2026 is the Slovene adoption of a CENELEC draft amendment to prEN IEC 61009-2-1:2026. It covers residual current operated circuit-breakers with integral overcurrent protection for household and similar uses (RCBOs) classified according to IEC 61009-1:2024, 4.1.1, and it sets out the test requirements used to check conformity for certification.

What does kSIST FprEN IEC 61009-2-1:2026/kFprAA:2026 specify?

kSIST FprEN IEC 61009-2-1:2026/kFprAA:2026 specifies the extra requirements, tests and test sequences that apply to RCBOs of classification 4.1.1 when they are read together with IEC 61009-1:2024. It is aimed at RCBOs for voltages up to 440 V AC, frequencies of 50 Hz, 60 Hz or 50/60 Hz, currents up to 125 A, and rated short-circuit capacities up to 25 000 A at 50 Hz or 60 Hz.

The document is organized as an amendment with targeted changes to the base part. Its contents cover:

Clause or annexWhat it covers
Clause 1Modification to the scope of the base standard
9.9.1.1Test circuit and test procedure
9.15.1General test conditions
9.Z1Low ambient air temperature verification
Figure 2Test circuit and low-temperature behaviour
Figure Z6Low-temperature test cycle
Tables A.1 to A.5Test sequences and sample numbers
Annex ZANormative references and European publications
Annex ZBSpecial National Conditions

What are the key requirements of kSIST FprEN IEC 61009-2-1:2026/kFprAA:2026?

The main technical content is about how RCBOs are tested for conformity. The amendment changes test conditions, adds a low-temperature verification, and adjusts the test sequences and sample allocation used for certification.

Test conditions and test circuit

The document modifies the test circuit and procedure in 9.9.1.1 and the general test conditions in 9.15.1. In practice, this means laboratories must use the updated arrangement when proving operating characteristics and trip-free behaviour, instead of relying on the unchanged wording from the base part.

Low-temperature verification

Clause 9.Z1 adds a specific verification for RCBOs intended for use between -25 °C and +40 °C. The RCBO is conditioned through a repeated temperature and humidity cycle, first at normal ambient conditions, then down to low temperature, and then back again.

For this test, the RCBO must remain in the ON position without load during the cycles, and it must not trip during the environmental cycling. At the end of the low-temperature part of the fifth cycle, the document requires operation checks with residual current, including special treatment for general type RCBOs, type S RCBOs, and type A RCBOs. After the test, a visual inspection and a switch-on check at -25 °C confirm that the device still works and has not suffered damage that would affect further use.

Figures used in the tests

Figure 2 is revised so that one circuit serves for operating characteristics, trip-free mechanism, and low-temperature behaviour. Figure Z6 gives the low-temperature test cycle used in 9.Z1. For users, this means the test set-up and the temperature profile are both defined visually, which reduces ambiguity during laboratory work.

Test sequences and sample numbers

Annex A is updated in several places: the test sequences in Tables A.1 to A.5 are revised, and the number of samples for full and simplified test procedures is adjusted. This matters for manufacturers because it affects how many devices must be submitted and which tests are performed on which samples.

The amendment also changes the sequences for RCBOs with different instantaneous tripping currents and for RCBOs of different classification according to IEC 61009-1:2024, 4.3. In practice, certification bodies use these tables to plan testing efficiently while still covering the relevant device variants.

Special national conditions

Annex ZB adds Special National Conditions. It records that Germany does not permit the use of RCBOs of type AC, and it keeps specific national notes for Ireland and the United Kingdom in Tables A.3 and A.5. This is important for market access because national conditions can affect whether a device can be offered or how it is tested in a specific country.

What terms does kSIST FprEN IEC 61009-2-1:2026/kFprAA:2026 define?

  • RCBO - A residual current operated circuit-breaker with integral overcurrent protection, used to provide both residual-current and overcurrent protection.
  • Type A - An RCBO category tested here with pulsating DC residual currents as well as AC residual current in the low-temperature verification.
  • Type S - A selective RCBO type that is tested with different residual current values and breaking-time limits in the added low-temperature clause.
  • Residual current - The current used in the trip tests to verify that the device opens correctly when an imbalance occurs.
  • Trip-free mechanism - The device behaviour that prevents manual closing from overriding a tripping condition.
  • Protected pole - A pole that is covered by the RCBO’s protection function, used in the tables for sample selection.
  • Special National Conditions - National provisions that remain normative where they apply and can affect harmonization.

Who uses kSIST FprEN IEC 61009-2-1:2026/kFprAA:2026?

Manufacturers of RCBOs use this document to design products and prepare certification samples. Test laboratories use it to run the required electrical and environmental tests.

Certification bodies and conformity assessment teams use it to judge whether a device meets the test sequences for classification 4.1.1. Quality managers and buyers in the electrical installation field use it to understand which device types are covered, which temperature range is addressed, and what evidence is needed for certification and market entry.

What changed in kSIST FprEN IEC 61009-2-1:2026/kFprAA:2026 from the previous edition?

kSIST FprEN IEC 61009-2-1:2026/kFprAA:2026 modifies prEN IEC 61009-2-1:2026. The amendment adds low-temperature verification, revises the main test circuit and general test conditions, updates the test sequences and sample numbers in Annex A, and adds Annex ZA and Annex ZB.

Which standards are used with kSIST FprEN IEC 61009-2-1:2026/kFprAA:2026?

  • IEC 61009-1:2024 - The base standard that supplies the general rules for RCBOs and is applied together with this document.
  • IEC 61543:2022 - Used for electromagnetic compatibility requirements for residual current-operated protective devices.
  • IEC 62873-2 - Supplies vocabulary for residual current devices and helps keep terminology consistent.

What does the kSIST FprEN IEC 61009-2-1:2026/kFprAA:2026 document contain?

The document contains revised test circuits, test procedures, and test sequences for RCBOs of classification 4.1.1. It also includes a new low-temperature test cycle, shown in Figure Z6, and revised references in Figure 2 for operating characteristics, trip-free mechanism, and low-temperature behaviour.

Annex A contains the sample numbers and test sequences used in full and simplified test procedures. Annex ZA links the cited international publications to their European publications, and Annex ZB records the special national conditions that affect use in specific countries.

Buy Documents

Draft

oSIST prEN IEC 61009-2-1:2026/oprAA:2026

English language (9 pages)
Preview
Preview
e-Library read for
×1 day

Get Certified

Connect with accredited certification bodies for this standard

IMQ S.p.A. (Certification)

Italian electrical product certification.

ACCREDIA Italy Verified

SLG Prüf- und Zertifizierungs GmbH

German testing and certification body.

DAKKS Germany Verified

UL Solutions

Global safety science company with testing, inspection and certification.

ANAB United States Verified

Sponsored listings

Frequently Asked Questions

kSIST FprEN IEC 61009-2-1:2026/kFprAA:2026 is a draft published by the Slovenian Institute for Standardization (SIST). Its full title is "Residual current operated circuit-breakers with integral overcurrent protection for household and similar uses (RCBOs) - Part 2-1: RCBOs according to classification 4.1.1". This standard covers: IEC 61009-1:2024, Clause 1 is applicable except for the first paragraph and the last paragraph, which are replaced by the following, respectively: This document applies to residual current operated circuit-breakers with integral overcurrent protection for household and similar uses (hereafter referred to as RCBOs), classified according to IEC 61009-1:2024, 4.1.1. RCBOs according to this document are intended for voltages not exceeding 440 V AC with frequencies of 50 Hz, 60 Hz or 50/60 Hz and currents not exceeding 125 A and rated short-circuit capacities not exceeding 25 000 A for operation at 50 Hz or 60 Hz. This document applies in conjunction with IEC 61009-1:2024. It specifies requirements, tests and test sequences to verify compliance and is used for certification purposes.

IEC 61009-1:2024, Clause 1 is applicable except for the first paragraph and the last paragraph, which are replaced by the following, respectively: This document applies to residual current operated circuit-breakers with integral overcurrent protection for household and similar uses (hereafter referred to as RCBOs), classified according to IEC 61009-1:2024, 4.1.1. RCBOs according to this document are intended for voltages not exceeding 440 V AC with frequencies of 50 Hz, 60 Hz or 50/60 Hz and currents not exceeding 125 A and rated short-circuit capacities not exceeding 25 000 A for operation at 50 Hz or 60 Hz. This document applies in conjunction with IEC 61009-1:2024. It specifies requirements, tests and test sequences to verify compliance and is used for certification purposes.

kSIST FprEN IEC 61009-2-1:2026/kFprAA:2026 is classified under the following ICS (International Classification for Standards) categories: 29.120.50 - Fuses and other overcurrent protection devices. The ICS classification helps identify the subject area and facilitates finding related standards.

kSIST FprEN IEC 61009-2-1:2026/kFprAA:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)


SLOVENSKI STANDARD
oSIST prEN IEC 61009-2-1:2026/oprAA:2026
01-februar-2026
Odklopniki na preostali (residualni) tok brez vgrajene nadtokovne zaščite za
gospodinjsko in podobno rabo (RCBOs) - 2-1. del: RCBO v skladu s klasifikacijo
4.1.1
Residual current operated circuit-breakers with integral overcurrent protection for
household and similar uses (RCBOs) - Part 2-1: RCBOs according to classification 4.1.1
Fehlerstrom-/Differenzstrom-Schutzschalter mit eingebauten Überstromschutz für
Hausinstallationen und für ähnliche Anwendungen (RCBOs) - Teil 2-1: RCBOs nach
Klassifikation 4.1.1
Ta slovenski standard je istoveten z: prEN IEC 61009-2-1:2026/prAA:2026
ICS:
29.120.50 Varovalke in druga Fuses and other overcurrent
nadtokovna zaščita protection devices
oSIST prEN IEC 61009-2- en
1:2026/oprAA:2026
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

oSIST prEN IEC 61009-2-1:2026/oprAA:2026

oSIST prEN IEC 61009-2-1:2026/oprAA:2026

EUROPEAN STANDARD DRAFT
prEN IEC 61009-2-1:2026
NORME EUROPÉENNE
EUROPÄISCHE NORM
prAA
January 2026
ICS 29.120.50 -
English Version
Residual current operated circuit-breakers with integral
overcurrent protection for household and similar uses (RCBOs) -
Part 2-1: RCBOs according to classification 4.1.1
To be completed Fehlerstrom-/Differenzstrom-Schutzschalter mit
eingebauten Überstromschutz für Hausinstallationen und
für ähnliche Anwendungen (RCBOs) - Teil 2-1: RCBOs
nach Klassifikation 4.1.1
This draft amendment prAA, if approved, will modify the European Standard prEN IEC 61009-2-1:2026; it is submitted to CENELEC
members for enquiry.
Deadline for CENELEC: 2026-04-24.

It has been drawn up by CLC/TC 23E.

If this draft becomes an amendment, CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this amendment the status of a national standard without any alteration.

This draft amendment was established by CENELEC in three official versions (English, French, German).
A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to
the CEN-CENELEC Management Centre has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Türkiye and the United Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to
provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and
shall not be referred to as a European Standard.

European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2026 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Project: 82334 Ref. No. prEN IEC 61009-2-1:2026/prAA:2026 E

oSIST prEN IEC 61009-2-1:2026/oprAA:2026
prEN IEC 61009-2-1:2026/prAA:2026 (E)
1 Contents Page
2 European foreword . 3
3 1 Modification to 9.9.1.1, “Test circuit and test procedure” . 4
4 2 Modification to 9.15.1, “General test conditions” . 4
5 3 Addition of 9.Z1, “Verification of the correct operation at low ambient air temperatures for
6 RCBOs for use at temperatures between −25 °C and +40 °C” . 4
7 4 Modification to Figure 2, “Test circuit for the verification of operating characteristics, and
8 trip-free mechanism for RCBOs classified according to 4.1.1” . 5
9 5 Addition of Figure Z6, “Test cycle for low temperature test (9.Z1)”. 5
10 6 Modification to Table A.1, “Test sequences” . 5
11 7 Modification to A.2, “Number of samples to be submitted for full test procedure” . 6
12 8 Modification to Table A.2, “Number of samples for full test procedure” . 6
13 9 Modification to Table A.3, “Number of samples for simplified test procedure” . 6
14 10 Modification to Table A.4, “Test sequences for RCBOs having different instantaneous
15 tripping currents” . 7
16 11 Modification to Table A.5, “Test sequences for RCBOs of different classification
17 according to 4.3 of IEC 61009-1:2024” . 7
18 12 Addition of Annex ZA, “Normative references to international publications with their
19 corresponding European publications” . 7
20 13 Addition of Annex ZB, “Special National Conditions” . 8
oSIST prEN IEC 61009-2-1:2026/oprAA:2026
prEN IEC 61009-2-1:2026/prAA:2026 (E)
21 European foreword
22 This document (prEN IEC 61009-2-1:2026/prAA:2026) has been prepared by CLC/TC 23E “Circuit breakers
23 and similar devices for household and similar applications”.
24 This document is currently submitted to the Enquiry.
25 The following dates are proposed:
• latest date by which the existence of this (doa) dav + 6 months
document has to be announced at national
level
• latest date by which this document has to be (dop) dav + 12 months
implemented at national level by publication of
an identical national standard or by
endorsement
• latest date by which the national standards (dow) dav + 60 months (to
conflicting with this document have to be be confirmed or
withdrawn modified when voting)
26 This document is read in conjunction with prEN IEC 61009-2-1:2026.
27 This document includes the following significant technical modifications with respect to
28 prEN IEC 61009-2-1:2026:
29 — Only the essential common changes existing in EN 61009-2-1:1994 and all of its amendments and
30 corrigenda (if any) are maintained in this document.
oSIST prEN IEC 61009-2-1:2026/oprAA:2026
prEN IEC 61009-2-1:2026/prAA:2026 (E)
32 1 Modification to 9.9.1.1, “Test circuit and test procedure”
33 Delete the last paragraph
34 2 Modification to 9.15.1, “General test conditions”
35 Delete the 2nd paragraph.
36 3 Addition of 9.Z1, “Verification of the correct operation at low ambient air
37 temperatures for RCBOs for use at temperatures between −25 °C and +40 °C”
38 Add the following subclause:
39 “9.Z1 Verification of the correct operation at low ambient air temperatures for RCBOs for use at
40 temperatures between −25 °C and +40 °C
41 Enclosed-type RCBOs are tested in their enclosure, unenclosed-type RCBOs are mounted in an individual
42 enclosure with a degree of protection IP55, and are connected as for normal use (see Figure 2).
43 No drain hole in the enclosure shall be opened for this test.
44 NOTE RCBOs tested in enclosures IP55 are suitable to be used in enclosures of a degree of protection other than
45 IP55 within the temperature range of –25 °C to +40 °C.
46 The RCBO (including the enclosure) is brought into a suitable test chamber with an ambient air temperature of
47 (23 ± 2) °C and a relative humidity of (93 ± 3) %. The volume ratio of the test chamber to the test samples
48 (including enclosures) shall be greater than 50.
49 The RCBO is in the ON-position without load and shall be subjected to the following cycle (see Figure Z6).
50 For the first 6 h (stabilization period) the temperature is kept at (23 ± 2) °C and the humidity at (93 ± 3) %.
51 Within the next 6 h the ambient air temperature is decreased to (−25 ± 2) °C without any supply of humidity.
52 This temperature of (−25 ± 2) °C is kept for 6 h. Within the next 6 h the temperature is increased to (+
53 23 ± 2) °C and the relative humidity is increased to (93 ± 3) % (end of the first cycle). This cycle is performed
54 five times.
55 During these cycles the RCBO shall not trip.
56 During the fifth cycle, at the end of the period at (−25 ± 2) °C, an AC residual current is passed through one
57 pole of the RCBO (see Figure 2)
58 — for RCB
...