Industrial-Process control systems - Instruments with analogue inputs and two- or multi-position outputs - Part 1: Methods of evaluating the performance (IEC 61003-1:2016)

This part of IEC 61003 is applicable to pneumatic and electric industrial-process instruments
or control device using measured values that are continuous signals either a mechanical
(position, force, etc.) or a standard electric signal.
These instruments or process control systems modules may be used as controllers or as
switches for alarm and other similar purposes.
Electronic product safety issues may impact only a few products covered by this document.
Consequently this document does not address such safety issues.
This standard is intended to specify uniform terminologies and testing methods for
performance evaluation of industrial-process instruments or process control systems modules
with analogue measured values and two- or multi-position outputs.
Considerations other than the performances are listed in Clause 10.

Systeme der industriellen Prozessleittechnik - Geräte mit analogen Eingängen und Zwei- oder Mehrpunktverhalten - Teil 1: Verfahren zur Bewertung des Betriebsverhaltens (IEC 61003-1:2016)

Système de commande de processus industriels - Instruments avec entrées analogiques et sorties à deux ou plusieurs positions - Partie 1: Méthodes d’évaluation des performances (IEC 61003-1:2016)

L'IEC 61003-1:2016 est applicable aux dispositifs de commande ou instruments électriques et pneumatiques des processus industriels, utilisant des valeurs mesurées qui sont des signaux continus, c'est-à-dire soit un signal mécanique (position, force, etc.) soit un signal électrique normalisé. Elle a pour objet de spécifier des terminologies et des méthodes d'essais uniformes pour l'évaluation des performances des instruments des processus industriels ou des modules de systèmes de commande de processus avec valeurs mesurées analogiques et sorties à deux ou plusieurs positions. Cette troisième édition annule et remplace la deuxième édition parue en 2004. Cette édition constitue une révision technique. Cette édition inclut les modifications techniques majeures suivantes par rapport à l'édition précédente:
- utilisation de l'expression "sortie à deux positions" au lieu de "instrument à deux états" (voir en 3.2);
- utilisation du terme "recouvrement" au lieu de "différentiel de commutation" (voir en 3.4);
- utilisation de l'expression "Exigences relatives à l'immunité aux transitoires rapides/en salves" au lieu de "Surtensions transitoires d'alimentation", et révision de la méthode d'essai (voir en 6.2.10);
- suppression des essais du 6.2.12 "Influence en mode commun" et du 6.2.13 "Influence en mode normal (mode série)", issus de la précédente édition;
- utilisation de l'expression "champ électromagnétique" au lieu de "interférence électromagnétique rayonnée", la méthode d'essai restant inchangée (voir en 6.2.16);
- utilisation de l'expression "rigidité diélectrique" au lieu de "essai d'isolation", et révision de la référence (voir en 6.3.4);
- suppression des paragraphes "8.2 Caractéristiques de conception", "10.1 Entretien et ajustement" et "10.2 Réparation" de la précédente édition.

Nadzorni sistemi za industrijske procese - Instrumenti z analognimi vhodi in dvo- ali večpozicijskimi izhodi - 1. del: Postopki za ocenjevanje zmogljivosti (IEC 61003-1:2016)

Ta del standarda IEC 61003 se uporablja za pnevmatske in električne instrumente za industrijske procese ali nadzorne naprave, ki uporabljajo izmerjene vrednosti, ki so neprekinjeni signali, in sicer mehanski (položaj, sila itd.) ali standardni električni signali.
Ti instrumenti ali moduli za nadzorne sisteme za procese se lahko uporabljajo kot alarmni krmilniki ali stikala in za druge podobne namene.
Težave zaradi varnosti elektronskih izdelkov lahko vplivajo na le nekaj izdelkov, ki so zajeti v tem dokumentu. Zato ta dokument ne obravnava teh varnostnih vprašanj. Ta standard določa enotno terminologijo in preskusne metode za ocenjevanje zmogljivosti instrumentov za industrijske procese ali module za nadzorne sisteme za procese z analogno izmerjenimi vrednostmi in dvo- ali večpozicijskimi izhodi. Dejavniki, ki niso povezani z zmogljivostjo, so navedeni v točki 10.

General Information

Status
Published
Publication Date
19-Feb-2017
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
08-Nov-2016
Due Date
13-Jan-2017
Completion Date
20-Feb-2017

Relations

Buy Standard

Standard
EN 61003-1:2017
English language
27 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 61003-1:2017
01-marec-2017
1DGRPHãþD
SIST EN 61003-1:2004
1DG]RUQLVLVWHPL]DLQGXVWULMVNHSURFHVH,QVWUXPHQWL]DQDORJQLPLYKRGLLQGYR
DOLYHþSR]LFLMVNLPLL]KRGLGHO3RVWRSNL]DRFHQMHYDQMH]PRJOMLYRVWL ,(&

Industrial-Process control systems - Instruments with analogue inputs and two- or multi-
position outputs - Part 1: Methods of evaluating the performance (IEC 61003-1:2016)
Systeme der industriellen Prozessleittechnik - Geräte mit analogen Eingängen und Zwei-
oder Mehrpunktverhalten - Teil 1: Verfahren zur Bewertung des Betriebsverhaltens (IEC
61003-1:2016)
Système de commande de processus industriels - Instruments avec entrées analogiques
et sorties à deux ou plusieurs positions - Partie 1: Méthodes d’évaluation des
performances (IEC 61003-1:2016)
Ta slovenski standard je istoveten z: EN 61003-1:2016
ICS:
25.040.40 Merjenje in krmiljenje Industrial process
industrijskih postopkov measurement and control
SIST EN 61003-1:2017 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 61003-1:2017

---------------------- Page: 2 ----------------------

SIST EN 61003-1:2017


EUROPEAN STANDARD EN 61003-1

NORME EUROPÉENNE

EUROPÄISCHE NORM
November 2016
ICS 25.040.40; 35.240.50 Supersedes EN 61003-1:2004
English Version
Industrial-process control systems - Instruments with analogue
inputs and two- or multi-position outputs - Part 1: Methods for
evaluating performance
(IEC 61003-1:2016)
Systèmes de commande de processus industriels - Systeme der industriellen Prozessleittechnik - Geräte mit
Instruments avec entrées analogiques et sorties à deux ou analogen Eingängen und Zwei- oder Mehrpunktverhalten -
plusieurs positions - Partie 1: Méthodes d'évaluation des Teil 1: Verfahren zur Bewertung des Betriebsverhaltens
performances (IEC 61003-1:2016)
(IEC 61003-1:2016)
This European Standard was approved by CENELEC on 2016-07-19. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.


European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2016 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
 Ref. No. EN 61003-1:2016 E

---------------------- Page: 3 ----------------------

SIST EN 61003-1:2017
EN 61003-1:2016
European foreword
The text of document 65B/1040/FDIS, future edition 3 of IEC 61003-1, prepared by SC 65B
"Measurement and control devices", of IEC/TC 65 "Industrial-process measurement, control and
automation" was submitted to the IEC-CENELEC parallel vote and approved by CENELEC as
EN 61003-1:2016.
The following dates are fixed:
• latest date by which the document has to be implemented at (dop) 2017-05-04
national level by publication of an identical national
standard or by endorsement
(dow) 2019-11-04
• latest date by which the national standards conflicting with
the document have to be withdrawn

This document supersedes EN 61003-1:2004.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC [and/or CEN] shall not be held responsible for identifying any or all such
patent rights.
Endorsement notice
The text of the International Standard IEC 61003-1:2016 was approved by CENELEC as a European
Standard without any modification.
In the official version, for Bibliography, the following note has to be added for the standard indicated :
IEC 61326-1:2012 NOTE Harmonized as EN 61326-1:2013 (not modified).

2

---------------------- Page: 4 ----------------------

SIST EN 61003-1:2017
EN 61003-1:2016
Annex ZA
(normative)

Normative references to international publications
with their corresponding European publications
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any amendments) applies.
NOTE 1 When an International Publication has been modified by common modifications, indicated by (mod),
the relevant EN/HD applies.
NOTE 2 Up-to-date information on the latest versions of the European Standards listed in this annex is
available here: www.cenelec.eu.

Publication Year Title EN/HD Year
IEC 60050 series International Electrotechnical Vocabulary - -
(IEV)
IEC 60050-300 -  International Electrotechnical Vocabulary - - -
Electrical and electronic measurements
and measuring instruments -
Part 311: General terms relating to
measurements -
Part 312: General terms relating to
electrical measurements -
Part 313: Types of electrical measuring
instruments -
Part 314: Specific terms according to the
type of instrument
IEC 60050-351 -  International Electrotechnical Vocabulary - - -
Part 351: Control technology
IEC 61298-1 2008 Process measurement and control EN 61298-1 2008
devices - General methods and
procedures for evaluating performance -
Part 1: General considerations
IEC 61298-2 2008 Process measurement and control EN 61298-2 2008
devices - General methods and
procedures for evaluating performance -
Part 2: Tests under reference conditions
IEC 61298-3 2008 Process measurement and control EN 61298-3 2008
devices - General methods and
procedures for evaluating performance -
Part 3: Tests for the effects of influence
quantities
IEC 61298-4 -  Process measurement and control EN 61298-4 -
devices - General methods and
procedures for evaluating performance -
Part 4: Evaluation report content

3

---------------------- Page: 5 ----------------------

SIST EN 61003-1:2017

---------------------- Page: 6 ----------------------

SIST EN 61003-1:2017



IEC 61003-1

®


Edition 3.0 2016-06




INTERNATIONAL



STANDARD




NORME



INTERNATIONALE











Industrial-process control systems – Instruments with analogue inputs and two-

or multi-position outputs –

Part 1: Methods for evaluating performance




Systèmes de commande de processus industriels – Instruments avec entrées

analogiques et sorties à deux ou plusieurs positions –


Partie 1: Méthodes d'évaluation des performances












INTERNATIONAL

ELECTROTECHNICAL

COMMISSION


COMMISSION

ELECTROTECHNIQUE


INTERNATIONALE




ICS 25.040.40; 35.240.50 ISBN 978-2-8322-3406-8



Warning! Make sure that you obtained this publication from an authorized distributor.

Attention! Veuillez vous assurer que vous avez obtenu cette publication via un distributeur agréé.

® Registered trademark of the International Electrotechnical Commission
Marque déposée de la Commission Electrotechnique Internationale

---------------------- Page: 7 ----------------------

SIST EN 61003-1:2017
– 2 – IEC 61003-1:2016 © IEC 2016
CONTENTS
FOREWORD . 4
INTRODUCTION . 6
1 Scope . 7
2 Normative references. 7
3 Terms and definitions . 8
4 General conditions for tests . 9
4.1 Documentary information . 9
4.1.1 General reference documents. 9
4.1.2 Collect data . 10
4.2 Electrical safety . 10
4.3 Installation . 10
4.4 Supply conditions . 10
5 General testing procedures and precautions . 10
5.1 Checking of calibration made prior to delivery . 10
5.2 Set point . 10
5.3 Differential gap . 11
6 Test methods and procedures . 11
6.1 Tests under reference conditions . 11
6.1.1 Switching accuracy related factors. 11
6.1.2 Mean switching point . 12
6.1.3 Set point . 12
6.2 Tests for the effects of influence quantities . 12
6.2.1 Ambient temperature . 12
6.2.2 Humidity . 13
6.2.3 Vibrations . 13
6.2.4 Shock, drop and topple . 14
6.2.5 Mounting position . 14
6.2.6 Over-range . 14
6.2.7 Output load effects . 14
6.2.8 Supply voltage and frequency variations . 14
6.2.9 Short-term supply voltage interruptions . 14
6.2.10 Fast transient/burst immunity requirements . 15
6.2.11 Supply pressure variations . 15
6.2.12 Common mode interference. 15
6.2.13 Normal mode interference (series mode) . 15
6.2.14 Earthing . 15
6.2.15 Magnetic field effects . 15
6.2.16 Electromagnetic field . 16
6.2.17 Electrostatic discharge (ESD) . 16
6.2.18 Effect of open-circuited and short-circuited input . 16
6.2.19 Effect of open-circuited and short-circuited output . 16
6.2.20 Effect of process medium temperature . 16
6.2.21 Atmospheric pressure effects . 17
6.2.22 Start-up drift . 17
6.2.23 Accelerated operational life test . 17
6.3 Other tests . 17

---------------------- Page: 8 ----------------------

SIST EN 61003-1:2017
IEC 61003-1:2016 © IEC 2016 – 3 –
6.3.1 Transient response of a two-position output . 17
6.3.2 Indication of the measured value . 18
6.3.3 Adjustable differential gap . 18
6.3.4 Dielectric strength . 18
6.3.5 Insulation resistance . 19
7 Multi-position output . 19
7.1 Action . 19
7.2 Test . 19
7.2.1 Characteristics of the multi-position output . 19
7.2.2 Mutual influence of pairs of switching points . 19
7.2.3 Determination of switching range . 19
8 General observations . 19
8.1 Protective finishes . 19
8.2 Tools and equipment . 19
9 Test report and summary of tests . 20
10 Partial evaluation . 23
Bibliography . 24

Figure 1 – Action of two-position output . 8
Figure 2 – Action of three-position output . 9

Table 1 – An example of a report (1 of 4) . 20

---------------------- Page: 9 ----------------------

SIST EN 61003-1:2017
– 4 – IEC 61003-1:2016 © IEC 2016
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________

INDUSTRIAL-PROCESS CONTROL SYSTEMS – INSTRUMENTS WITH
ANALOGUE INPUTS AND TWO- OR MULTI-POSITION OUTPUTS –

Part 1: Methods for evaluating performance

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 61003-1 has been prepared by subcommittee SC 65B:
Measurement and control devices, of IEC technical committee TC 65: Industrial-process
measurement, control and automation.
This third edition cancels and replaces the second edition published in 2004. This edition
constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous
edition:
a) use of the term “two-position output” instead of “two-state instrument” (see 3.2);
b) use of the term “differential gap” instead of “switching differential” (see 3.4);
c) use of “fast transient/burst immunity requirements” instead of “power supply transient
overvoltages”, and revision of the test method (see 6.2.10);

---------------------- Page: 10 ----------------------

SIST EN 61003-1:2017
IEC 61003-1:2016 © IEC 2016 – 5 –
d) deletion of 6.2.12 “common mode interference” and 6.2.13 “normal mode interference
(series mode) ”tests of the previous edition;
e) use of the term “electromagnetic field” instead of “radiated electromagnetic interference”,
the test method remained the same (see 6.2.16);
f) use of the term “dielectric strength” instead of “isolation test”, and revision of the reference
(see 6.3.4);
g) deletion of Subclauses “8.2 Design features”, “10.1 Routine maintenance and adjustment”
and “10.2 Repair” of the previous edition.
The text of this standard is based on the following documents:
FDIS Report on voting
65B/1040/FDIS 65B/1050/RVD

Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
A list of all parts of the IEC 61003 series, published under the general title Industrial-process
control systems – Instruments with analogue inputs and two or multi-position outputs, can be
found on the IEC website.
The committee has decided that the contents of this publication will remain unchanged until
the stability date indicated on the IEC website under "http://webstore.iec.ch" in the data
related to the specific publication. At this date, the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.

---------------------- Page: 11 ----------------------

SIST EN 61003-1:2017
– 6 – IEC 61003-1:2016 © IEC 2016
INTRODUCTION
The methods of evaluation specified in this part of IEC 61003 are intended for use by
manufacturers to determine the performance of their products and by users, or independent
testing establishments, to verify the manufacturer's performance specifications.
The test conditions in this standard, for example the range of ambient temperatures and
power supply, represent those, which commonly arise in use.
The tests specified in this standard are not necessarily sufficient for instruments specifically
designed for unusually arduous duties. Conversely, a restricted series of tests may be
suitable for instruments designed to perform within a more limited range of conditions.
It will be appreciated that the closest communication should be maintained between the
evaluating body and the manufacturer. Note should be taken of the manufacturer's
specifications for the instrument, when the test program is being decided, and the
manufacturer should be invited to comment on both the test program and the results. His
comments on the results should be included in any report produced by the testing
organization.

---------------------- Page: 12 ----------------------

SIST EN 61003-1:2017
IEC 61003-1:2016 © IEC 2016 – 7 –
INDUSTRIAL-PROCESS CONTROL SYSTEMS – INSTRUMENTS WITH
ANALOGUE INPUTS AND TWO- OR MULTI-POSITION OUTPUTS –

Part 1: Methods for evaluating performance



1 Scope
This part of IEC 61003 is applicable to pneumatic and electric industrial-process instruments
or control device using measured values that are continuous signals either a mechanical
(position, force, etc.) or a standard electric signal.
These instruments or process control systems modules may be used as controllers or as
switches for alarm and other similar purposes.
Electronic product safety issues may impact only a few products covered by this document.
Consequently this document does not address such safety issues.
This standard is intended to specify uniform terminologies and testing methods for
performance evaluation of industrial-process instruments or process control systems modules
with analogue measured values and two- or multi-position outputs.
Considerations other than the performances are listed in Clause 10.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and
are indispensable for its application. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any
amendments) applies.
IEC 60050 (all parts), International Electrotechnical Vocabulary (available at
)
IEC 60050-300, International Electrotechnical Vocabulary – Electrical and electronic
measurements and measuring instruments (comprising Parts 311, 312, 313 and 314)
IEC 60050-351, International Electrotechnical Vocabulary – Part 351: Control technology
IEC 61298-1:2008, Process measurement and control devices – General methods and
procedures for evaluating performance – Part 1: General considerations
IEC 61298-2:2008, Process measurement and control devices – General methods and
procedures for evaluating performance – Part 2: Tests under reference conditions
IEC 61298-3:2008, Process measurement and control devices – General methods and
procedures for evaluating performance – Part 3: Tests for the effects of influence quantities
IEC 61298-4, Process measurement and control devices – General methods and procedures
for evaluating performance – Part 4: Evaluation report content

---------------------- Page: 13 ----------------------

SIST EN 61003-1:2017
– 8 – IEC 61003-1:2016 © IEC 2016
3 Terms and definitions
For the purposes of this document, the terms and definitions given in IEC 60050-300,
IEC 60050-351, IEC 61298-2 and the following apply.
3.1
switching point
x
i
measured value (with the input moving either upscale or downscale), at which the output (y)
changes from one position to another
3.2
two-position output
output variable which may assume one of two discrete values
EXAMPLE
Action illustrated in Figure 1, where x is the value of the input variable and y is the value of the output signal.
The two-position output, having one pair of switching points x and x (x greater than x ) has the relationships:
1 2 2 1
y , x< x

1 1
y=

y , x> x
 2 2
For x < x < x , y may be either y or y .
1 2 1 2
It is y if the last switching point crossed by x was x .
1 1
It is y if the last switching point crossed by x was x .
2 2
y
X
sd
y
2
y
1
x x x
x
1 m 2
IEC

Figure 1 – Action of two-position output
3.3
multi-position output
output variable which may assume any of a set of discrete values
EXAMPLE
A multi-position output has n possible output values and n-1 pairs of switching points, (see Figure 2, a three-
position output). Each pair of switching points may be investigated by the procedure given for the two-position
output.

---------------------- Page: 14 ----------------------

SIST EN 61003-1:2017
IEC 61003-1:2016 © IEC 2016 – 9 –
y
X X
sd sd
1 2
y
22
y = y
12 21
y
11
x x x x x x
x
11 m 12 21 m 22
1 2
X
sr

IEC
Figure 2 – Action of three-position output
3.4
differential gap
X
sd
absolute value of difference between the switching point x with the measured value moving
2
upscale and the switching point x with the measured value moving downscale
1
SEE: Figure 1 and Figure 2.
3.5
mean switching point

x
m
mean of the values of upscale and downscale switching points
SEE: Figure 1 and Figure 2.
3.6
switching range
X
sr
in a multi-position output, range of measured values corresponding to the extreme switching
points
SEE: Figure 2.
3.7
set point
w
or x as specified) should occur
point value at which it is desired that switching (at x
2 1
4 General conditions for tests
4.1 Documentary information
4.1.1 General reference documents
For the purpose of this standard, the general test conditions (e.g. environmental test
conditions, supply conditions, load conditions, mounting position, externally induced

---------------------- Page: 15 ----------------------

SIST EN 61003-1:2017
– 10 – IEC 61003-1:2016 © IEC 2016
vibrations, external mechanical constraints, and delivery of the instrument) specified in
Clause 6 of IEC 61298-1:2008 apply, together with Clause 4 of this part of IEC 61003.
The general testing procedures and precautions, specified in Clause 7 of IEC 61298-1:2008,
shall be applied, together with Clause 5 of this part of IEC 61003.
The tests general methods and procedures – if any – specified in IEC 61298-2 and
IEC 61298-3 apply, together with Clause 6 of this part of IEC 61003.
4.1.2 Collect data
The manufacturer shall supply to the evaluating body information for installation,
commissioning, operation, routine maintenance and repair of the instrument. A spare parts list,
together with a recommendation of the spare parts to be held in stock, shall be supplied. The
language of written information for installation should be primary or accepted language of the
country where implemented.
Installation and use guidelines including diagrams, operation instructions, spare parts
requirements, and all specifications should be clearly stated.
Additionally, any certificates indicating the degree of intrinsic safety and flameproofing, etc. of
electrically powered instruments should be listed. This information should give details of the
certificate numbers and the degree of protection provided.
Procedures for installation, routine maintenance and adjustment, repairs and overhaul should
be examined by the actual performance of the required operation. This should be perform
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.