Alarm systems - Intrusion and hold-up systems -- Part 3: Control and indicating equipment

This Standard specifies the requirements, performance criteria and testing procedures for control and 168 indicating equipment (CIE) intended for use in intrusion and hold-up alarm systems (I&HAS) installed 169 in buildings. This document also applies to CIE to be used in IAS or HAS. 170 The CIE may incorporate processing functions of other I&HAS components, or its processing 171 requirements may be distributed among such components. 172 This Standard specifies the requirements for CIE installed in buildings using specific or non-specific 173 wired interconnections or wire-free interconnections. These requirements also apply to ACE that are 174 installed inside or outside of the supervised premises and mounted in indoor or outdoor environments. 175 Where CIE shares means of detection, interconnection, control, communication, processing and / or 176 power supplies with other applications, these requirements apply to I&HAS functions only.

Alarmanlagen - Einbruch- und Überfallmeldeanlagen -- Teil 3: Melderzentrale

Diese Norm legt die Anforderungen, Leistungsmerkmale und die Prüfverfahren für Zentralen (Z) fest, die für den Gebrauch von in Gebäuden installierten Einbruch- und Überfallmeldeanlagen (EMA/ÜMA) bestimmt sind. Dieses Dokument gilt auch für Zentralen, die entweder in EMA oder in ÜMA verwendet werden. Die Zentrale darf Verarbeitungsfunktionen anderer EMA/ÜMA Anlageteile enthalten oder die Anforderungen an die Verarbeitung der Zentrale können in diesen Anlageteilen verteilt sein.  Diese Norm legt die Anforderungen an Zentralen fest, die in Gebäuden unter Verwendung von exklusiv oder nicht exklusiv verdrahteten oder drahtlosen Verbindungen installiert sind. Diese Anforde¬rungen gelten auch für zusätzliche Bedieneinrichtungen (ZBE), die innerhalb oder außerhalb des überwachten Objektes in Innen¬räumen oder im Freien installiert sind. Wenn Zentralen Mittel der Erkennung, Verbindung, Bedienung, Kommunikation, Verarbeitung und/oder die Energieversorgungen mit anderen Anwendungen teilen, gelten diese Anforderungen nur für EMA/ÜMA Funk¬tionen. Diese Norm beschreibt Anforderungen an die Leistungsmerkmale von Zentralen für jeden der vier Sicherheits¬grade, die in der Europäischen Norm EN 50131-1 „Alarmanlagen – Einbruch- und Überfallmelde¬anlagen – Systemanforderungen“ beschrieben sind. Auch für die vier Umweltklassen, die die Verwendung in Innenräu¬men und im Freien abdecken, sind Anforderungen festgelegt.  Diese Norm beinhaltet verbindliche Funktionen, die die Zentrale für den jeweiligen Sicherungsgrad zur Verfü¬gung stellen muss sowie wählbare Funktionen, die zusätzlich zur Verfügung gestellt werden dürfen. Diese Norm beschäftigt sich nicht mit Anforderungen, die zur Einhaltung von Europäischen Richtlinien, wie z. B. die EMV Richtlinie, Niederspannungsrichtlinie etc. gelten, ausgenommen dass sie für solche Geräte, die die Betriebsbedingungen für EMV-Störanfälligkeit wie in EN 50130-4 gefordert, erfüllen müssen, festlegt. ANMERKUNG   In dieser Norm wird durchgehend der Begriff EMA/ÜMA verwendet, außer wenn es notwendig ist, zwi¬schen EMA- und ÜMA-Anteilen einer Anlage zu unterscheiden. Der Begriff schließt EMA und ÜMA ein, wenn diese Anla¬gen einzeln installiert sind.

Systèmes d’alarme - Systèmes d'alarme contre l’intrusion et les hold-up -- Partie 3: Equipement de contrôle et de signalisation

La présente norme spécifie les exigences, critères de performance et procédures d'essai pour les matériels de commande et d’affichage (centrales d’alarme) (CIE en anglais) destines à être utilisés dans les systèmes d'alarme contre l'intrusion (IAS) et les systèmes d'alarme contre les hold-up (HAS) installés dans les bâtiments. Le présent document s'applique également aux CIE destinés à être utilisés dans les systèmes IAS ou HAS. Les CIE peuvent incorporer des fonctions de traitement d'autres composants IAS et HAS ou leurs besoins de traitement peuvent être répartis entre ces composants. La présente norme spécifie les exigences relatives aux CIE installés dans des bâtiments qui utilisent des liaisons filaires spécifiques ou non spécifiques ou des liaisons radio. Ces exigences s'appliquent également aux ACE installés à l'intérieur ou à l'extérieur des bâtiments surveillés et montés dans un environnement intérieur ou extérieur. Lorsque le CIE partage des moyens de détection, d'interconnexion, de commande, de communication, de traitement et/ou des alimentations avec d'autres applications, ces exigences ne s'appliquent qu'aux fonctions IAS et HAS. La présente norme spécifie les exigences de performance pour les CIE pour chacun des quatre grades de sécurité identifiés dans la Norme Européenne EN 50131 1, “Systèmes d'alarme - Systèmes d'alarme contre l’intrusion et les hold-up – Partie 1: Exigences système”. Des exigences sont également spécifiées pour quatre classes d'environnement couvrant des applications pour des emplacements intérieurs et extérieurs. La présente norme inclut des fonctions obligatoires, qui doivent être assurées pour tous les CIE pour le grade approprié de sécurité, ainsi que des fonctions facultatives complémentaires. La présente norme ne traite pas des exigences de conformité aux Directives réglementaires de l'Union Européenne, telles que la Directive relative à la compatibilité électromagnétique, la Directive relative aux basses tensions, etc. à ceci près qu'elle spécifie les conditions de fonctionnement de l'équipement pour les essais de susceptibilité de compatibilité électromagnétique tels que requis par la EN 50130-4.  NOTE   Dans la présente norme, il est fait référence au terme “I&HAS” dans l'intégralité de celle-ci sauf lorsqu'il est spécifiquement nécessaire de différencier les parties IAS et HAS d'un système. Le terme est destiné à inclure IAS et HAS lorsque ces systèmes sont installés séparément.

Alarmni sistemi - Sistemi za javljanje vloma in ropa - 3. del: Kontrolna in indikacijska oprema

General Information

Status
Published
Publication Date
10-Sep-2009
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
18-Aug-2009
Due Date
23-Oct-2009
Completion Date
11-Sep-2009

Relations

Buy Standard

Standard
EN 50131-3:2009
English language
73 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 50131-3:2009
01-oktober-2009
1DGRPHãþD
SIST EN 50131-6:1999
SIST-TS CLC/TS 50131-3:2004
Alarmni sistemi - Sistemi za javljanje vloma in ropa - 3. del: Kontrolna in
indikacijska oprema
Alarm systems - Intrusion and hold-up systems -- Part 3: Control and indicating
equipment
Alarmanlagen - Einbruch- und Überfallmeldeanlagen -- Teil 3: Melderzentrale
Systèmes d’alarme - Systèmes d'alarme contre l’intrusion et les hold-up -- Partie 3:
Equipement de contrôle et de signalisation
Ta slovenski standard je istoveten z: EN 50131-3:2009
ICS:
13.310 Varstvo pred kriminalom Protection against crime
13.320 Alarmni in opozorilni sistemi Alarm and warning systems
SIST EN 50131-3:2009 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 50131-3:2009

---------------------- Page: 2 ----------------------

SIST EN 50131-3:2009

EUROPEAN STANDARD
EN 50131-3

NORME EUROPÉENNE
March 2009
EUROPÄISCHE NORM

ICS 13.310 Supersedes CLC/TS 50131-3:2003


English version


Alarm systems -
Intrusion and hold-up systems -
Part 3: Control and indicating equipment



Systèmes d’alarme -  Alarmanlagen -
Systèmes d'alarme contre l’intrusion Einbruch- und Überfallmeldeanlagen -
et les hold-up - Teil 3: Melderzentrale
Partie 3: Equipement de contrôle
et de signalisation





This European Standard was approved by CENELEC on 2009-02-01. CENELEC members are bound to
comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and
notified to the Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the
Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy,
Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia,
Slovenia, Spain, Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: avenue Marnix 17, B - 1000 Brussels


© 2009 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 50131-3:2009 E

---------------------- Page: 3 ----------------------

SIST EN 50131-3:2009
EN 50131-3:2009 – 2 –
Foreword
This European Standard was prepared by the Technical Committee CENELEC TC 79, Alarm systems.
The text of the draft was submitted to the Unique Acceptance Procedure and was approved by
CENELEC as EN 50131-3 on 2009-02-01.
This European Standard supersedes CLC/TS 50131-3:2003.
The following dates were fixed:
– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2010-02-01
– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2012-02-01
EN 50131 will consist of the following parts, under the general title “Alarm systems – Intrusion and
hold-up systems”:
Part 1 System requirements
Part 2-2 Intrusion detectors - Passive infrared detectors
Part 2-3 Requirements for microwave detectors
Part 2-4 Requirements for combined passive infrared and microwave detectors
Part 2-5 Requirements for combined passive infrared and ultrasonic detectors
Part 2-6 Opening contacts (magnetic)
Part 2-7-1 Intrusion detectors – Glass break detectors (acoustic)
Part 2-7-2 Intrusion detectors – Glass break detectors (passive)
Part 2-7-3 Intrusion detectors – Glass break detectors (active)
Part 3 Control and indicating equipment
Part 4 Warning devices
Part 5-3 Requirements for interconnections equipment using radio frequency techniques
Part 6 Power supplies
Part 7 Application guidelines

Part 8 Security fog device/systems
__________

---------------------- Page: 4 ----------------------

SIST EN 50131-3:2009
– 3 – EN 50131-3:2009
Introduction
This document is based on the revision of the Technical Specification originally edited by the
CENELEC TC 79/WG 3, then submitted to the formal vote and finally approved by CENELEC as
CLC/TS 50131-3 on 2003-05-19.
The work done by WG 3 is the result of the comments raised by the National Committees, members of
CENELEC and of harmonisation with EN 50131-1:2006 + A1:2009 prepared by TC 79/WG 1; for this
reason the reader has to take into account EN 50131-1:2006 + A1:2009, which has to be considered
as a “master” document for this EN 50131-3.
Repetition of definitions and requirements contained in EN 50131-1 have been eliminated from this
EN 50131-3, in order to minimise conflict in the event of changes to EN 50131-1, except where
repetition is deemed essential for the clarity of this document.

Reference has been included to various implications arising from the detector standards. Full detail of
the interconnection requirements could be the subject of a future standard.

A number of requirements are contained in this standard for which a formal test procedure can only be
written by defining (and hence restricting) the technology by which the requirement is achieved.
Accordingly, it has been recognised that such functions can be tested only by agreement between
manufacturer and test house, according to documented information relating to how the required
functionality has been achieved.

A table to cross reference EN 50131-1 requirements against this EN 50131-3 and tests has been
included in Annex D.

---------------------- Page: 5 ----------------------

SIST EN 50131-3:2009
EN 50131-3:2009 – 4 –
Contents
Introduction . 3
1 Scope . 6
2 Normative references . 7
3 Definitions and abbreviations . 7
3.1 Definitions . 7
3.2 Abbreviations .10
4 Equipment attributes .10
4.1 General .10
4.2 Functionality .11
5 CIE construction .11
6 Security grade .11
7 Environmental performance .11
7.1 Requirements .11
7.2 Environmental and EMC tests .11
8 Functional requirements .12
8.1 Inputs .12
8.2 Outputs .13
8.3 Operation .13
8.4 Processing .18
8.5 Indication .19
8.6 Notification outputs .20
8.7 Tamper security (detection/protection) .21
8.8 Interconnections .23
8.9 Timing .24
8.10 Event recording .24
8.11 Power supply .25
9 Product documentation .25
9.1 Installation and maintenance .25
9.2 Operating instructions .26
10 Marking and labelling .26
11 Tests .26
11.1 Test conditions .27
11.2 Test procedures .28
11.3 Reduced functional test .28
11.4 Functional tests .29
11.5 Access level .40
11.6 Authorization requirements .41
11.7 Operational tests .46
11.8 Tamper security tests .56
11.9 Substitution tests .59
11.10 Testing of I&HAS timing performance .59
11.11 Testing for interconnections .60
11.12 Event log .61
11.13 Marking and documentation .62
11.14 Environmental and EMC tests .63
Annex A (informative) Interconnection types .65
Annex B (informative) Summary of timing requirements .67
Annex C (normative) Use of non-I&HAS interface .68

---------------------- Page: 6 ----------------------

SIST EN 50131-3:2009
– 5 – EN 50131-3:2009
Annex D (informative) Summary of function cross references .69
Figures
Figure A.1 – Specific wired interconnections .65
Figure A.2 – Non-specific wired interconnections .65
Figure A.3 – Wire-free interconnections .66
Tables
Table 1 – Recognition of additional fault conditions .12
Table 2 – Recognition of biometric keys .15
Table 3 – Time intervals for methods of authorization used in combination .15
Table 4 – Detection of repeated invalid authorization attempts .16
Table 5 – Monitoring of processing .19
Table 6 – Indications supplementary to those of EN 50131-1 .20
Table 7 – Tamper protection .22
Table 8 – Tamper detection.22
Table 9 – Tool dimension for tamper detection .23
Table 10 – Removal from mounting .23
Table 11 – Additional events to be included in event log .24
Table 12 – Reduced functional test .29
Table 13 – Tests of the processing of intruder signals or messages .30
Table 14 – Tests of the processing of hold-up signals or messages .32
Table 15 – Tests of the processing of tamper signal or messages .33
Table 16 – Test of processing of fault signals or messages .35
Table 17 – Test of processing of masking signals or messages .37
Table 18 – Test of processing of reduction of range signals or messages .38
Table 19 – Test of CIE processing in the presence of non-I&HAS inputs .40
Table 20 – Test of the access to the functions and controls .41
Table 21 – Test for disabling user input device by invalid keys .45
Table 22 – Test for generation of tamper by invalid keys .46
Table 23 – Test of setting procedure .47
Table 24 – Test of prevention of setting and overriding of prevention of setting procedure .48
Table 25 – Test for unsetting procedure .50
Table 26 – Test of setting and/or unsetting automatically at pre-determined times.52
Table 27 – Inhibit and isolate functions .53
Table 28 – Verification of test functions .54
Table 29 – Test of CIE process monitoring .55
Table 30 – Test of availability of indications .56
Table 31 – Test of event log .62
Table 32 – Environmental and EMC tests .64
Table B.1 – Timing table .67
Table C.1 – Conditions for use of non-I&HAS interface for control and indicating purposes .68
Table D.1 – Cross references.69
Bibliography .73

---------------------- Page: 7 ----------------------

SIST EN 50131-3:2009
EN 50131-3:2009 – 6 –

1 Scope
This standard specifies the requirements, performance criteria and testing procedures for control and
indicating equipment (CIE) intended for use in intrusion and hold-up alarm systems (I&HAS) installed
in buildings. This document also applies to CIE to be used in IAS or HAS.
The CIE may incorporate processing functions of other I&HAS components or its processing
requirements may be distributed among such components.
This standard specifies the requirements for CIE installed in buildings using specific or non-specific
wired interconnections or wire-free interconnections. These requirements also apply to ACE that are
installed inside or outside of the supervised premises and mounted in indoor or outdoor environments.
Where CIE shares means of detection, interconnection, control, communication, processing and/or
power supplies with other applications, these requirements apply to I&HAS functions only.
This standard specifies performance requirements for CIE at each of the four security grades identified
in the European Standard EN 50131-1, “Alarm Systems – Intrusion and hold-up systems – System
requirements”. Requirements are also specified for four environmental classes covering applications
for indoor and outdoor locations.
This standard includes mandatory functions, which shall be provided on all CIE for the appropriate
security grade, as well as optional functions that may additionally be provided.
This standard does not deal with requirements for compliance with EU regulatory Directives, such as
the EMC Directive, Low Voltage Directive, etc. except in that it specifies the equipment operating
conditions for EMC susceptibility testing as required by EN 50130-4.
NOTE In this standard reference to the term “I&HAS” is used throughout, except where there is specific need to differentiate
between the IAS and HAS portions of a system. The term is intended to include IAS and HAS when such systems are installed
separately.

---------------------- Page: 8 ----------------------

SIST EN 50131-3:2009
– 7 – EN 50131-3:2009

2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
Publication Year Title
EN 50130-4 1995 Alarm systems - Part 4: Electromagnetic compatibility - Product family
standard: Immunity requirements for components of fire, intruder and
social alarm systems
EN 50130-5 1998 Alarm systems - Part 5: Environmental test methods
EN 50131-1 2006 Alarm systems - Intrusion and hold-up systems - Part 1: System
A1 2009 requirements
EN 50131-5-3 2005 Alarm systems - Intrusion systems - Part 5-3: Requirements for
interconnections equipment using radio frequency techniques
EN 50131-6 2008 Alarm systems - Intrusion and hold-up systems - Part 6: Power
supplies
EN 60068-1 1994 Environmental testing - Part 1: General and guidance
(IEC 60068-1:1988 + corr. Oct. 1988 + A1:1992)
EN 60068-2-75 1997 Environmental testing - Part 2-75: Tests - Test Eh: Hammer tests
(IEC 60068-2-75:1997)
EN 60529 Degrees of protection provided by enclosures (IP code) (IEC 60529)
EN 62262 Degrees of protection provided by enclosures for electrical equipment
against external mechanical impacts (IK code) (IEC 62262)
3 Definitions and abbreviations
3.1 Definitions
For the purposes of this document, the following terms and definitions apply in addition to those given
in EN 50131-1:2006.
3.1.1
acknowledge
action of a user to accept an indication
3.1.2
alarm point
one or more detector(s) providing a common signal or message, at the CIE or at the ACE for the
purpose of indication or processing
3.1.3
alarm signal or message
signal or message generated by an alarm point
3.1.4
biometric key
use of biometric characteristic by an authorized user to gain access to restricted functions or parts of a
CIE (EXAMPLE: finger print or iris recognition)

---------------------- Page: 9 ----------------------

SIST EN 50131-3:2009
EN 50131-3:2009 – 8 –
3.1.5
conditioning
exposure of the Equipment Under Test (EUT) to environmental conditions in order to determine the
effect of such conditions on the EUT
3.1.6
detector
device designed to generate an alarm signal or message in response to the sensing of an abnormal
condition indicating the presence of a hazard
3.1.7
digital key
portable device containing digitally coded information used by an authorized user to gain access to
restricted functions or parts of a CIE (EXAMPLE: magnetic card, electronic token or similar)
3.1.8
entry route facility
means to ignore signals or messages from specified detectors during unsetting for a specified time
period
3.1.9
entry time
time permitted for unsetting procedure where entry route is used
3.1.10
exit route facility
means to ignore signals or messages from specified detectors during setting for a specified period
3.1.11
external power source (EPS)
energy supply external to the I&HAS which may be non-continuous (EXAMPLE: main power supply)
NOTE  For Type A and Type B PS only. The EPS is derived as described in EN 50131-6.
3.1.12
fail to set
condition when defined setting procedure has not been completed within a specific time so that I&HAS
is left in the “setting mode”
3.1.13
false acceptance rate (FAR)
proportion of biometric verification transactions with wrongful claims of identity that are incorrectly
accepted
3.1.14
false rejection rate (FRR)
proportion of biometric verification transactions with truthful claims of identity that are incorrectly
denied
3.1.15
interaction
any deliberate operation or act by the user to control or vary the function of the I&HAS
3.1.16
intrusion
entry into the supervised premises by an unauthorised person(s)

---------------------- Page: 10 ----------------------

SIST EN 50131-3:2009
– 9 – EN 50131-3:2009
3.1.17
logical key
logical information used by an authorized user to gain access to restricted functions or parts of a CIE
(EXAMPLE: PIN code, digital key, biometric key)
3.1.18
mechanical key
implement relying solely on physical shape to determine its uniqueness, used by an authorized user to
gain access to restricted functions or parts of a CIE
3.1.19
non-I&HAS interface
device external to the I&HAS used to carry out some or all ACE functions (EXAMPLES: Computer,
PDA)

3.1.20
operating mode
set, unset, setting and unsetting are the four operating modes

3.1.21
open by normal means
opening of the equipment housing by the procedure defined by the manufacturer
3.1.22
Personal Identification Number (PIN Code)
code used by an authorised user to gain access to restricted functions or parts of a CIE (example,
numeric or alphanumeric)
3.1.23
soak
an attribute of an alarm point such that signals or messages that normally create notifications are
prevented from doing so, but continue to be recorded in the event log
3.1.24
storage device (SD)
device which stores energy (EXAMPLE: a battery)
3.1.25
Supervised Premises Transceiver (SPT)
this document uses the definition of EN 50131-1:2006
3.1.26
test condition
condition of an alarm system in which the normal functions are modified for test purposes
3.1.27
user input
command generated by a deliberate user action
3.1.28
user input device
device used for user input (EXAMPLES: ACE, physical lock with electrical contacts)

---------------------- Page: 11 ----------------------

SIST EN 50131-3:2009
EN 50131-3:2009 – 10 –
3.2 Abbreviations
For the purposes of this European Standard the following abbreviations are used:
ACE Ancillary control equipment
APS Alternative power source
ARC Alarm receiving centre
ATS Alarm transmission system
CIE Control and indicating equipment
EPS External power source
EUT Equipment under test
FAR False acceptance rate
FRR False rejection rate
HAS Hold-up alarm system
IAS Intrusion alarm system
I&HAS Intrusion and hold-up alarm system
PDA Personal digital assistant
PIN Personal identification number
PS Power supply
SD Storage device
SPT Supervised premises transceiver
WD Warning device

4 Equipment attributes
4.1 General
CIE shall include attributes for the reception of signals and/or messages, processing the information,
notification and indication as appropriate. The detailed requirements are provided in Clause 8.
NOTE  If a function is provided that is optional for a particular grade and a claim of compliance is made, it shall meet the
applicable requirements for the grade for which compliance is claimed (if any are given). If there are no specifications for the
function at the grade in question, the requirements for any higher grade (as identified by the manufacturer) shall apply.
Compliance with this standard shall be demonstrated by assessment of Clause 4 through to Clause 10
and the application of the tests of Clause 11.
Annex D provides a cross reference between the requirements of EN 50131-1 and the requirements
and tests of this standard.

---------------------- Page: 12 ----------------------

SIST EN 50131-3:2009
– 11 – EN 50131-3:2009
4.2 Functionality
Functions additional to the mandatory functions specified in this standard may be included in I&HAS
providing they do not influence the correct operation of the mandatory functions.
Where provided, these additional functions shall not affect compliance with the requirements of this
standard, except as permitted by EN 50131-1:2006, 8.3.13.
It is permitted for the CIE to include functionality for special purposes that would render the
I&HAS non-compliant with EN 50131-1. The manufacturer’s documentation shall include a
warning to this effect.
If use of a function(s) or combination of functions within the CIE would result in the installed I&HAS not
being compliant with EN 50131-1 or being compliant at a lower security grade (EXAMPLE: function(s)
reducing the security of the I&HAS) the manufacturer shall, either:
a) detail the configuration(s) which are compliant with EN 50131-1;
or
b) detail the function(s) or combination of functions that would result in the installed I&HAS not being
compliant with EN 50131-1.
The manufacturer shall document the fact that compliance labelling should be removed or adjusted if
non-compliant configurations are selected.

5 CIE construction
The CIE may be in a single housing or be distributed in multiple housings and may be combined with
other I&HAS components.
Provision shall be made to allow adequate fixing of the housing to the mounting surface.
Use of equipment not part of the I&HAS may be used to carry out ACE functions (EXAMPLE:
computer, PDA) if the conditions specified in Annex C are met.
6 Security grade
The CIE and ACE shall be declared to comply with one of four security grades (with grade 1 being the
lowest and grade 4 being the highest) and shall meet all the requirements of that grade.
The requirements for the performance of the CIE will vary depending upon its grade. Any testing will
be carried out according to the grade declared in the CIE documentation and marking.
7 Environmental performance
7.1 Requirements
CIE and ACE shall be suitable for use in at least one of the environmental classes defined in
EN 50131-1.
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.