SIST EN 14339:2005
(Main)Underground fire hydrants
Underground fire hydrants
This European Standard specifies the requirements, test methods and marking applicable to underground fire hydrants intended for fire fighting purposes:
to be installed in a water distribution system;
in sizes DN 80 and DN 100;
suitable for an allowable operating pressure, PFA, of 10 bar or 16 bar or 25 bar with or without drain facility;
having a vertical or horizontal, flanged, socket or spigot inlet;
with one or two outlets and having outlet/s to national requirements;
of globe (screw down) or gate valve type.
This European Standard also provides for the evaluation of conformity of the underground fire hydrants to the requirements of this European Standard.
This European Standard applies to fire hydrants for potable and non-potable water and for filtered water. Additional requirements may apply for other liquids.
Couplings connected to outlets are outside the scope of this European Standard and should conform to national requirements.
Unterflurhydranten
Dieses Dokument legt die Anforderungen, Prüfverfahren und Kennzeichnung für Unterflurhydranten für Feuerlöschzwecke fest:
- zur Installation in Wasserversorgungssystemen;
- in den Nennweiten DN 80 und DN 100;
- geeignet für einen zulässigen Betriebsdruck PFA von 10 bar oder 16 bar oder 25 bar, mit oder ohne Entleerungssystem;
- mit vertikalem oder horizontalem Einlauf mit Flansch-, Muffen- oder Spitzenanschluss;
- mit einem oder zwei Abgängen nach nationalen Anforderungen;
- mit Ventil- oder Schieberabsperrung;
- für Straßenkappen und Abdeckungen.
Dieses Dokument liefert auch die Konformitätsbewertung für Unterflurhydranten für Feuerlöschzwecke nach den Anforderungen dieser Norm.
Dieses Dokument gilt für Hydranten für Trink- und Nichttrinkwasser sowie für gefiltertes Wasser. Zusätzliche Anforderungen können für andere Flüssigkeiten gelten.
Kupplungen an Abgängen fallen nicht in den Anwendungsbereich dieser Norm und müssen den nationalen Anforderungen entsprechen.
Bouches d'incendie enterrées
La présente Norme européenne donne les prescriptions, méthodes d'essai et marquages applicables aux bouches d'incendie enterrées suivantes destinées a la lutte contre l'incendie :
- devant etre installées sur un réseau de distribution d'eau ;
- de dimensions DN 80 et DN 100 ;
- appropriées a une pression de fonctionnement admissible, PFA, de 10 bar ou 16 bar ou 25 bar avec ou sans dispositif de vidange ;
- munies de raccordements d'entrée verticaux ou horizontaux a bride, a extrémité a emboîter mâle ou femelle ;
- comportant un ou plusieurs orifices de sortie, et munies de raccordements de sortie conformes aux prescriptions nationales ;
- munies d'appareils de robinetterie de type robinet a soupape (a tige non montante) ou robinet-vanne.
La présente norme peut également etre utilisée pour l'évaluation de la conformité des bouches d'incendie enterrées conformes aux prescriptions contenues dans la présente norme.
La présente norme s'applique aux bouches d'incendie enterrées alimentées en eau potable et non potable et en eau filtrée. Des prescriptions complémentaires peuvent s'appliquer dans le cas d'autres liquides.
Les manchons d'assemblage raccordés aux orifices de sortie ne sont pas du domaine d'application de la présente norme et il convient qu'ils soient conformes aux réglementations nationales.
Podzemni hidranti
General Information
Standards Content (Sample)
SLOVENSKI STANDARD
SIST EN 14339:2005
01-december-2005
Podzemni hidranti
Underground fire hydrants
Unterflurhydranten
Bouches d'incendie enterrées
Ta slovenski standard je istoveten z: EN 14339:2005
ICS:
13.220.10 Gašenje požara Fire-fighting
SIST EN 14339:2005 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
SIST EN 14339:2005
---------------------- Page: 2 ----------------------
SIST EN 14339:2005
EUROPEAN STANDARD
EN 14339
NORME EUROPÉENNE
EUROPÄISCHE NORM
July 2005
ICS 13.220.10; 93.080.30
English version
Underground fire hydrants
Bouches d'incendie enterrées Unterflurhydranten
This European Standard was approved by CEN on 20 June 2005.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the Central Secretariat or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the Central Secretariat has the same status as the official
versions.
CEN members are the national standards bodies of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France,
Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia,
Slovenia, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36 B-1050 Brussels
© 2005 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 14339:2005: E
worldwide for CEN national Members.
---------------------- Page: 3 ----------------------
SIST EN 14339:2005
EN 14339:2005 (E)
Contents Page
Foreword .3
Introduction.4
1 Scope .5
2 Normative references .5
3 Terms and definitions.6
4 Design requirements .7
4.1 General dimensions.7
4.2 Shell .7
4.3 Elastomers.7
4.4 Obturator – main valve .7
4.5 Stem seals .9
4.6 Materials including lubricants in contact with water intended for human consumption .9
4.7 Leaktightness and mechanical strength .9
4.8 Closing direction.10
4.9 Opening turns .10
4.10 Resistance of hydrant to operating loads.10
4.11 Stem drive.10
4.12 Inlet connections.11
4.13 Outlets .11
4.14 Drainage system .11
4.15 Internal and external corrosion resistance .11
4.16 Resistance to disinfection products.11
4.17 Hydrants for non potable water systems .12
4.18 Hydraulic characteristics.12
5 Test methods.12
5.1 General .12
5.2 General dimensions.12
5.3 Operational characteristics.12
6 Marking and additional data.13
6.1 Marking .13
6.2 Additional hydrant data .13
7 Evaluation of conformity .14
7.1 General .14
7.2 Initial type testing (ITT).15
7.3 Factory product control (FPC) .16
Annex ZA (informative) Clauses of the European Standard addressing the provisions of the EU
Construction Products Directive (89/106/EEC).19
ZA.1 Scope and relevant characteristics .19
ZA.2 Procedure and system for the attestation of conformity of underground fire hydrants .21
ZA.3 CE marking.21
ZA.4 EC certificate and Declaration of conformity.23
Bibliography.24
2
---------------------- Page: 4 ----------------------
SIST EN 14339:2005
EN 14339:2005 (E)
Foreword
This European Standard (EN 14339:2005) has been prepared by Technical Committee CEN/TC 192 “Fire
service equipment”, the secretariat of which is held by BSI, in cooperation with CEN/TC164 "Water supply"
and CEN/TC 69 “Industrial Valves”.
This European Standard shall be given the status of a national standard, either by publication of an identical
text or by endorsement, at the latest by January 2006, and conflicting national standards shall be withdrawn at
the latest by January 2006.
This European Standard has been prepared under a mandate given to CEN by the European Commission
and the European Free Trade Association, and supports essential requirements of EU Directive(s).
For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this European
Standard.
This is one of a series of standards for fire hydrants.
This is the first edition of this European Standard.
No International Standard exists for underground fire hydrants.
According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following
countries are bound to implement this European Standard: Austria, Belgium, Cyprus, Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain, Sweden, Switzerland
and United Kingdom.
3
---------------------- Page: 5 ----------------------
SIST EN 14339:2005
EN 14339:2005 (E)
Introduction
The purpose of a fire hydrant installation is to provide a connection (i.e. hydrant) to the water main to which
the firefighter can connect firefighting equipment. Underground hydrants consist of one or more valves and
outlet connectors and are installed in an underground chamber with a surface box and intended primarily to
supply water for firefighting and also may be used by water utilities (as defined in 3.3).
This European Standard is in conformity with the general requirements already established by CEN/TC 164 in
the field of water supply.
In respect of quality of water intended for human consumption caused by the product covered by this
European Standard:
1) this European Standard provides no information as to whether the product may be used without
restriction in any of the Member States of the EU or EFTA;
2) it should be noted that, while awaiting the adoption of verifiable European criteria, existing national
regulations concerning the use and/or the characteristics of this product remain in force.
4
---------------------- Page: 6 ----------------------
SIST EN 14339:2005
EN 14339:2005 (E)
1 Scope
This European Standard specifies the requirements, test methods and marking applicable to underground fire
hydrants intended for fire fighting purposes:
to be installed in a water distribution system;
in sizes DN 80 and DN 100;
suitable for an allowable operating pressure, PFA, of 10 bar or 16 bar or 25 bar with or without drain
facility;
having a vertical or horizontal, flanged, socket or spigot inlet;
with one or two outlets and having outlet/s to national requirements;
of globe (screw down) or gate valve type.
This European Standard also provides for the evaluation of conformity of the underground fire hydrants to the
requirements of this European Standard.
This European Standard applies to fire hydrants for potable and non-potable water and for filtered water.
Additional requirements may apply for other liquids.
Couplings connected to outlets are outside the scope of this European Standard and should conform to
national requirements.
2 Normative references
The following referenced documents are indispensable for the application of this European Standard. For
dated references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 681-1, Elastomeric seals — Material requirements for pipe joint seals used in water and drainage
applications — Part 1: Vulcanized rubber
EN 1074-1:2000, Valves for water supply — Fitness for purpose requirements and appropriate verification
tests — Part 1: General requirements
EN 1074-2:2000, Valves for water supply — Fitness for purpose requirements and appropriate verification
tests — Part 2: Isolating valves
EN 1074-6:2004, Valves for water supply — Fitness for purpose requirements and appropriate verification
tests — Part 6: Hydrants
EN 1092-1, Flanges and their joints — Circular flanges for pipes, valves, fittings and accessories, PN
designated — Part 1: Steel flanges
EN 1092-2, Flanges and their joints — Circular flanges for pipes, valves, fittings and accessories, PN
designated — Part 2: Cast iron flanges
EN 1503-1, Valves — Materials for bodies, bonnets and covers — Part 1: Steels specified in European
Standards
5
---------------------- Page: 7 ----------------------
SIST EN 14339:2005
EN 14339:2005 (E)
EN 1503-3, Valves — Materials for bodies, bonnets and covers — Part 3: Cast irons specified in European
Standards
EN ISO 9001:2000, Quality management systems — Requirements (ISO 9001:2000)
3 Terms and definitions
For the purposes of this European Standard, the following terms and definitions apply.
3.1
hydrant
connection to a water supply system including an isolating valve
[EN 1074-6:2004]
3.2
fire hydrant
hydrant designed to supply water for fire fighting during all phases of the fire
3.3
underground fire hydrant
fire hydrant installed in an underground chamber with a surface box, intended primarily to supply water for
firefighting and which may also be used by water utilities
3.4
obturator
movable component of the valve whose position in the fluid flow path permits, restricts or obstructs the fluid
flow (see EN 736-2). In addition it can be captive or loose
3.5
captive obturator
device for controlling the flow out of a pipeline and into a pipeline
3.6
loose obturator
device for controlling flow out of a pipeline but which prevents flow into a pipeline
3.7
shell
pressure-containing envelope of the valve
NOTE It normally comprises the body and, when included in the design, a bonnet or cover and the body bonnet or
body cover joint (see EN 736-2).
3.8
DN nominal size
alphanumeric designation of the size of pipework components used for reference purposes. It comprises the
letters DN followed by a dimensionless round number which is loosely related to the effective dimensions, in
millimetres, of the bore or external diameter of the end connections
[EN 1074-1:2000]
3.9
PN nominal pressure
alphanumeric designation used for reference purposes and related to a combination of numerical and
dimensional characteristics of a component of a pipe system. It comprises the letters PN followed by a
dimensionless round number
[EN 1074-1:2000]
6
---------------------- Page: 8 ----------------------
SIST EN 14339:2005
EN 14339:2005 (E)
3.10
allowable operating pressure PFA
maximum hydrostatic pressure that a component can withstand continuously in service
[EN 1074-1:2000]
3.11
allowable maximum operating pressure PMA
maximum hydrostatic pressure including surge that a component can withstand from time to time in service
(see EN 1074-1)
3.12
allowable test pressure PEA
maximum hydrostatic pressure that a newly installed component can withstand for a relatively short duration
when either fixed above ground level or laid and backfilled underground in order to ensure the integrity and
tightness of the pipeline
[EN 1074-1:2000]
3.13
flow coefficient Kv (Cv)
rate of flow in cubic metres per hour that will cause a differential pressure of one bar through the fire hydrant
(see EN 736-3)
4 Design requirements
4.1 General dimensions
As a minimum, the dimensions indicated in Figure 1 shall be given in the manufacturer’s catalogue.
4.2 Shell
The shell material of the hydrant shall be chosen from Table 1.
Table 1 — Shell material
Material Reference standard
Flake graphite cast iron EN 1503-3
Spheroidal graphite cast iron EN 1503-3
Stainless steel EN 1503-1
4.3 Elastomers
All elastomeric seals within the hydrant shall comply with EN 681-1. They shall be either type WA for cold
potable water use or suitable for the fluid with which they come into contact (see 4.6).
4.4 Obturator – main valve
The hydrant obturator shall be either captive or loose type.
The manufacturer shall declare if the design of the hydrant permits the obturator to be replaced in situ.
NOTE For safety reasons this replacement should only be carried out when the fire hydrant is not under pressure.
7
---------------------- Page: 9 ----------------------
SIST EN 14339:2005
EN 14339:2005 (E)
7
3
8
9
4
H
H
1
2
A
C
5
B
R
1
R
2
D
6
Key
1 Vertical inlet DN 5 Maximum size of hydrant (A max, B max)
2 Horizontal inlet DN 6 Minimum clear area of Surface box and Covers (D, R1min, R2min)
3 Drive 7 Ground level
4 Outlet connector 8 Height of the ground level above spindle
9 Height of the ground level above outlet H Depth of the outlet from the spindle
Figure 1 — Typical fire hydrant
8
---------------------- Page: 10 ----------------------
SIST EN 14339:2005
EN 14339:2005 (E)
4.5 Stem seals
Stem seal provision and servicing facilities shall be in accordance with national requirements valid in the
country of use of the product.
NOTE 1 Stem seals of globe (screw down) hydrants are capable of being replaced with the valve closed and under
operating pressure.
NOTE 2 Stem seals of gate valve hydrants are capable of being replaced with the valve fully open and under operating
pressure.
NOTE 3 The term ‘stem’ is also known as ‘spindle’.
NOTE 4 A future revision of this European Standard will give a list of acceptable provisions, allowing each Member
State to choose those provisions they wish.
4.6 Materials including lubricants in contact with water intended for human consumption
Pending the introduction of a common European Approvals Scheme ‘E.A.S.’, all materials including lubricants
in the construction of a hydrant, that are likely to come into contact with water for human consumption, shall
comply with the National Regulations in the country of use.
4.7 Leaktightness and mechanical strength
4.7.1 General
The hydrant shall be suitable for use at the relevant pressures shown in Table 2, and shall meet the
requirements of 4.7.2 to 4.7.3.
Table 2 — Pressures
a
PN PFA PMA PEA
MPa (bar) MPa (bar) MPa (bar)
10 1,0 (10) 1,2 (12) 1,7 (17)
16 1,6 (16) 2,0 (20) 2,5 (25)
25 2,5 (25) 3,5 (35) 3,75 (37,5)
a
PEA only applies to valves not in the closed position.
4.7.2 Shell and all pressure containing components (including stem seals)
4.7.2.1 Leaktightness
When tested in accordance with the Annex A of EN 1074-1:2000, using the values of PEA from Table 2, there
shall be no visible sign of leakage past the valve.
NOTE This is equivalent to rate "A" as defined in EN 1074-1:2000.
4.7.2.2 Mechanical strength
Having successfully passed the leak tightness test 4.7.2.1, the hydrant shall not show any sign of defect.
9
---------------------- Page: 11 ----------------------
SIST EN 14339:2005
EN 14339:2005 (E)
4.7.3 Obturator
4.7.3.1 Leaktightness
When tested in accordance with Annex B of EN 1074-1:2000, using the values of 1,1 × PFA from Table 2 and
the appropriate MOT values from Table 3, there shall be no visible sign of leakage past the valve.
NOTE This is equivalent to rate "A" as defined in EN 1074-1:2000.
4.7.3.2 Mechanical strength
Having successfully passed the leak tightness test 4.7.3.1, there shall be no other sign of defect.
4.7.4 Endurance
The requirements and test method shall be according to EN 1074-6:2004, 5.5.1.
4.7.5 Endurance of the non-return device (where fitted)
The requirements and test method shall be in accordance with EN 1074-6:2004, 5.5.2.
4.8 Closing direction
The hydrant shall be closed by turning the stem in a clockwise direction when viewed from above.
4.9 Opening turns
4.9.1 Total turns
When testing in accordance with 5.3.1, the number of turns "N" required to fully open the valve shall be
between 5 and 15 for DN 80 and between 6 and 15 for DN 100.
4.9.2 Start of flow (dead turns)
The maximum number of turns to commence flow shall not exceed 4 and in addition the manufacturer shall
declare the number of turns to start the flow.
When tested in accordance with 5.3.2, flow shall occur.
4.10 Resistance of hydrant to operating loads
4.10.1 Maximum operating torque (MOT) for operating loads
When tested in accordance with EN 1074-6:2004, Annex C, the torque required to seal the hydrant shall meet
the appropriate value given in Table 2 of EN 1074-6:2004.
4.10.2 Minimum strength torque (mST)
When tested in accordance with EN 1074-2:2000, Annex A, the torque required for the resistance of the
hydrant shall meet the appropriate value given in Table 2 of EN 1074-6:2004.
4.11 Stem drive
The stem drive shall comply with national requirements valid in the country of use of the product. Where fitted,
the stem cap shall be securely fixed in position during normal use. The means of fixing shall be such as to
10
---------------------- Page: 12 ----------------------
SIST EN 14339:2005
EN 14339:2005 (E)
permit removal of the cap by authorised users but also to prevent unintentional removal. The design of the
stem cap recess shall suit the stem end of the valve.
NOTE 1 The term ‘stem’ is also known as ‘spindle’.
NOTE 2 A future revision of this European Standard will give a list of acceptable provisions, allowing each Member
State to choose those provisions they wish.
4.12 Inlet connections
Inlet flanges shall be suitable for connecting to flanges conforming with EN 1092-1 or EN 1092-2, depending
on the shell material.
Depending on the customer need, the flanges may additionally accommodate older pattern flanges in
accordance with national requirements.
Where the inlet is of a proprietary type the manufacturer shall declare its dimensions.
NOTE A future revision of this European Standard will give a list of acceptable provisions, allowing each Member
State to choose those provisions they wish.
4.13 Outlets
The design of the outlet shall conform to National Requirements valid in the country of use of the hydrant.
4.14 Drainage system
The performance of the draining system, where fitted to the hydrant, shall comply with the requirements of
EN 1074-6:2004, 5.6. In addition, the manufacturer shall declare the volume of retained water and the time for
draining.
4.15 Internal and external corrosion resistance
4.15.1 General
The internal surfaces which are in continuous contact with the water, and all external surfaces of the hydrant
(including bolts) which are in continuous contact with the surrounding soil, water or atmosphere, shall be
resistant to corrosion and ageing by appropriate selection of materials.
4.15.2 Coatings
All cast iron components shall be coated to protect against corrosion and protect the quality of the water
intended for human consumption contained within the hydrant, if applicable.
NOTE The colour of the coatings may be to technical specifications depending on the conditions of use.
4.15.3 Other components
Other component parts of the hydrant to those in 4.15.1 shall be manufactured from materials that will resist
corrosion for the design life of the product under the conditions of use for which it is intended.
4.16 Resistance to disinfection products
Where applicable, the requirement and test shall be in accordance with 5.4 of EN 1074-1:2000.
11
---------------------- Page: 13 ----------------------
SIST EN 14339:2005
EN 14339:2005 (E)
4.17 Hydrants for non potable water systems
In cases where the hydrant does not transport water intended for human consumption, the manufacturer shall
ensure that all materials used in the hydrant (where they come into contact with the fluid) shall not be
adversely affected by that fluid.
4.18 Hydraulic characteristics
The hydraulic characteristics of each model of hydrant shall be determined in accordance with EN 1074-
6:2004, 5.3.
The manufacturer shall declare the Kv value (with captive or with loose obturator) taking into account the DN
of the inlet and the internal diameter of the outlets.
The minimum flow value shall be 60 for DN 80 and 75 for DN 100.
NOTE Higher values are recommended.
5 Test methods
5.1 General
For safety reasons, before applying any hydrostatic pressure, release all air from within the component under
test.
5.2 General dimensions
Measure or gauge the general dimensions specified in 4.1.
5.3 Operational characteristics
5.3.1 Number of turns to fully open the hydrant
Close the valve with a torque sufficient to seal the hydrant. Fully open the valve and determine the number of
turns, which shall be in conformity with 4.9.
5.3.2 Start of flow
Connect the hydrant to a water supply at the pressure of PFA and close the valve with a torque to seal the
hydrant using MOT. Open the valve by the number of turns specified in 4.9.2 and determine if flow has started.
12
---------------------- Page: 14 ----------------------
SIST EN 14339:2005
EN 14339:2005 (E)
6 Marking and additional data
6.1 Marking
All hydrants shall be durably marked on the upper part with the following:
direction of opening;
number of turns to start flow and fully open.
In addition, all hydrants shall be securely and durably marked with the following:
number of this European Standard, i.e. EN 14339;
DN;
PN;
loose obturator (if applicable);
manufacturer's mark;
date of manufacture;
suitability for the conveyed fluid; If potable water, reference to EN 1074-6:2004.
NOTE Where ZA.3 covers the same information as this subclause, the requirements of this subclause are met.
6.2 Additional hydrant data
The manufacturer's catalogue shall give the information listed in 6.1 and provide the following additional
information:
13
---------------------- Page: 15 ----------------------
SIST EN 14339:2005
EN 14339:2005 (E)
Number of this European Standard i.e. EN 14339 Inlet flanges:
EN 1092-1 or EN 1092-2;
Dimensions:
need to accommodate older pattern flanges;
according to 4.1, with reference to Figure 1.
inlet is of a proprietary type.
Shell material:
Outlet connectors:
according to Table 1.
details of conformity to national requirements
in the country of use.
Details of obturator.
Draining (if applicable):
Approvals of materials for contact with water
volume of retained water;
intended for human consumption (if relevant):
time for draining.
details of compliance with national
regulations in the country of use.
Hydraulic characteristics: Kv value.
Internal and external corrosion resistance.
Stem seals:
details of compliance with national
Coatings (if applicable):
requirements in the country of use.
details of coating type, colour and thickness.
Stem drive:
Resistance to corrosion of other component parts.
details of compliance with national
requirements in the country of use.
Resistance to disinfection products (if relevant).
Compatibility with the conveyed fluid (if relevant):
Resistance to operating loads:
MOT value;
hydrant for non potable water systems.
mST value.
Hydrant for potable water systems, EN 1074-6:2004.
Installation and maintenance guide
NOTE Where ZA.3 covers the same information as this subclause, the requirements of this subclause are met.
7 Evaluation of conformity
7.1 General
The compliance of an underground hydrant with the requirements of this European Standard shall be
demonstrated by:
– initial type testing;
– factory production control by the manufacturer, including product assessment.
NOTE The manufacturer is a natural or legal person, who places the hydrant on the market under his own name.
Normally, the manufacturer designs and manufactures the hydrant himself. As a first alternative, he may have it designed,
manufactured, assembled, packed, processed or labelled by subcontracting. As a second alternative he may assemble,
pack, process, or label ready-made products.
14
---------------------- Page: 16 ----------------------
SIST EN 14339:2005
EN 14339:2005 (E)
The manufacturer shall ensure:
– initial type testing in accordance with this European Standard is initiated and carried out (where relevant,
under the control of a product certification body); and
– that the product continuously complies with the initial type testing samples, for which compliance with
this European Standard has been verified.
The manufacturer shall always retain the overall control and shall have the necessary competence to take
responsibility for the product.
The manufacturer shall be fully responsible for the conformity of the hydrant to all relevant regulatory
requirements. However, where the manufacturer uses components already shown to conform to those
requirements relevant for that component (e.g. by CE marking), the manufacturer is not required to repeat the
evaluation which leads to such conformity. Where the manufacturer uses components not shown to conform,
it is his responsibility to undertake the necessary evaluation to show conformity.
7.2 Initial type testing (ITT)
7.2.1 General
Initial type testing shall be performed to demonstrate conformity with this European Standard.
All characteristics given in Clause
...
Questions, Comments and Discussion