Surge arresters -- Part 4: Metal-oxide surge arresters without gaps for a.c. systems

Work merged into 37/324/FDIS (pr=16386) * Standstill maintained

Überspannungsableiter -- Teil 4: Metalloxidableiter ohne Funkenstrecken für Wechselspannungsnetze

Parafoudres -- Partie 4: Parafoudres à oxyde métallique sans éclateurs pour réseaux à courant alternatif

Prenapetostni odvodniki - 4. del: Kovinsko-oksidni prenapetostni odvodniki brez iskrišč za sisteme z izmenično napetostjo

General Information

Status
Withdrawn
Withdrawal Date
31-Dec-2006
Technical Committee
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
01-Jan-2007
Due Date
01-Jan-2007
Completion Date
01-Jan-2007

Relations

Buy Standard

Amendment
EN 60099-4:200X/OprAA:2004
English language
4 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

37/307/CDV
COMMITTEE DRAFT FOR VOTE (CDV)
PROJET DE COMITÉ POUR VOTE (CDV)

Project number IEC 60099-4-A1-f2 Ed 2.0
Numéro de projet
Date of circulation Closing date for voting (Voting
IEC/TC or SC:
TC 37
Date de diffusion mandatory for P-members)
CEI/CE ou SC:

Date de clôture du vote (Vote
2004-06-04
obligatoire pour les membres (P))
2004-11-05
Titre du CE/SC: Parafoudres TC/SC Title: Surge Arresters
Secretary: J. L. Koepfinger
Secrétaire:
Also of interest to the following committees Supersedes document
Intéresse également les comités suivants Remplace le document
   37/274A/CD and 37/284B/CC
Functions concerned
Fonctions concernées
Safety EMC Environment Quality assurance
Sécurité CEM Environnement Assurance qualité
CE DOCUMENT EST TOUJOURS À L'ÉTUDE ET SUSCEPTIBLE DE THIS DOCUMENT IS STILL UNDER STUDY AND SUBJECT TO CHANGE. IT
MODIFICATION. IL NE PEUT SERVIR DE RÉFÉRENCE. SHOULD NOT BE USED FOR REFERENCE PURPOSES.
LES RÉCIPIENDAIRES DU PRÉSENT DOCUMENT SONT INVITÉS À RECIPIENTS OF THIS DOCUMENT ARE INVITED TO SUBMIT, WITH THEIR
PRÉSENTER, AVEC LEURS OBSERVATIONS, LA NOTIFICATION DES COMMENTS, NOTIFICATION OF ANY RELEVANT PATENT RIGHTS OF
DROITS DE PROPRIÉTÉ DONT ILS AURAIENT ÉVENTUELLEMENT WHICH THEY ARE AWARE AND TO PROVIDE SUPPORTING
CONNAISSANCE ET À FOURNIR UNE DOCUMENTATION EXPLICATIVE. DOCUMENTATION.



Titre : Amendment no 1-f2 a la CEI 60099-4 Ed Title : Amendment 1-f2 to IEC 60099-4 Ed 2.0 -
2.0 Parafoudres - Parte 4: Parfoudres áoxyde Surge Arresters - Part 4: Metal-oxide surge
meétallique sans éclaterures pour reeaux á arresters without faps for a.c. systems
courant alternatif



Note d'introduction Introductory note The material is base upon the comments
of the National Committees to 37/273/CD and 37/274/CD.

At the time of the preparation of this CDV the final
published version of IEC 60099-4 Ed 2.0 was not available.
Clauses are numbered according to 37/298/FDIS.



ATTENTION ATTENTION

CDV soumis en parallèle au vote (CEI) Parallel IEC CDV/CENELEC Enquiry
et à l’enquête (CENELEC)

Copyright © 2004 International Electrotechnical Commission, IEC. All rights reserved. It is
permitted to download this electronic file, to make a copy and to print out the content for the sole
purpose of preparing National Committee positions. You may not copy or "mirror" the file or
printed version of the document, or any part of it, for any other purpose without permission in
writing from IEC.

---------------------- Page: 1 ----------------------

60099-4 Amend 1/f2/Ed 2.0/CDV © IEC 2
LIGHTNING IMPULSE DISCHARGE CAPABILITY OF A METAL-OXIDE
SURGE ARRESTER

Amemdment 1 Fragment 2 to IEC 60099-4 Ed 2.0

Add new clause to 37/298/FDIS (60099-4, Ed. 2)
6.17 Impulse lightning discharge capability
When required, the lightning impulse discharge capability shall be demonstrated by tests and
procedures of Annex O.

----------------------------------------------------------------------

Add new Annex O to 37/298/FDIS (60099-4, Ed. 2)

Annex O
(normative)

TEST PROCEDURE TO DETERMINE THE LIGHTNING IMPULSE
DISCHARGE CAPABILITY

O.1 General

This procedure applies to surge arresters used on lines with system voltages exceeding
52 kV to improve the lightning performance of such lines. In general, theses arresters are
subjected to higher energy and current stresses caused by lightning than arresters installed
in stations with effective lightning protection on incoming lines. In addition, the anticipated
current waveform for decisive cases, with a duration of several tens of microseconds for
arresters applied on shielded lines and several hundreds of microseconds for arresters on
unshielded lines, considerably differs from waveforms specified in the operating duty test and
in the long duration current impulse test.
An impulse duration of 200 microseconds has been considered as a suitable compromise to
cover both the typical applications and the effect of multiple strokes.
Arresters intended for this application, therefore, shall be tested in accordance with the
lightning impulse discharge capability test to verify the rated lightning impulse discharge
capability of the arrester.

O.1.1 Selection of test samples

Three samples shall be tested. These samples shall include complete arresters, arrester
sections or resistive elements. They shall not have been subjected to any previous tests
except as necessary for evaluation purposes of this test.

---------------------- Page: 2 ----------------------

60099-4 Amend 1/f2/Ed 2.0/CDV © IEC 3
The samples to be chosen for the lightning impulse discharge capability test shall have a
residual voltage at nominal discharge current at the highest end of the variation range
declared by the manufacturer. Furthermore, in case of multi-column arresters the highest
value of uneven current distribution shall be considered. In order to comply with these
demands the following shall be fulfilled:
a) The ratio between the rated voltage of the complete arrester to the rated voltage of the
section is defined by n. The volume of the resistor elements used as test samples shall not
be greater than the minimum
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.