SCOPE
1.1 This specification covers procedures for determining whether building materials are considered flood-damage-resistant for construction intended to comply with the requirements of the National Flood Insurance Program (NFIP) (44 CFR Part 60.3(a)(3)). It was developed from and is intended to supplement specifications in Technical Bulletin 2 (TB 2) (1)2 for purposes of evaluating building materials that comply with requirements of the applicable building code that are not already recognized as acceptable in accordance with TB 2 (1).  
1.2 This specification is intended to reduce the burden on the NFIP by improving the ability to construct flood-resistant buildings and structures and thereby decrease the number and magnitude of flood insurance claims. The goal is to identify materials that, when tested as part of an assembly representative of end use configuration, would be permitted for construction below the base flood elevation (BFE) and not require repair after a flood event due to adverse effects of water immersion and subsequent drying on performance.  
1.3 This specification is intended to apply to building materials used in new construction, repair of substantially damaged buildings, and substantial improvement of existing buildings in special flood hazard areas (SFHAs) for construction used in non-habitable spaces below the BFE as permitted by the NFIP (44 CFR Part 60.3(a)(3)) and TB 2 (1) including, but not limited to, building materials used in foundations, walls, floors, ceilings, stairways, exterior cladding, and other similarly incorporated architectural and structural items. Evaluation of products for use in habitable spaces is outside of the scope of this specification.  
1.4 This specification includes requirements for the purpose of evaluating effects of flooding on specimen physical properties, drying, and the ability to be cleaned.  
1.5 The performance of a material specimen under the specified water immersion and drying conditions shall not be construed as fully representative of performance of the material for an actual flood event because actual flood conditions vary in factors such as makeup of water, and depth and duration of immersion, and drying conditions vary by factors such as ambient temperature and humidity.  
1.6 Performance requirements vary based on the type of building material and the functions the building material is required to perform. The body of the specification gives general requirements applicable to a broad range of building materials with annexes provided for material-specific requirements.  
1.7 Performance requirements for evaluation of other hazards associated with flood damage are outside the scope of this specification. These hazards include, but are not limited to, debris impact, flood velocity, wave action, water pressure differential, scour, erosion, varied biological contaminants in flood water including fungal matter and sewage, and chemical contaminants in floodwater, and other factors that would be adverse to continued use of the structure for its intended purpose including long-term occupant health impacts.  
1.8 A commentary to this specification is provided in Appendix X1.  
1.9 Units—The values stated in inch-pound units are to be regarded as the standard. The values given in parentheses are mathematical conversions to International System of Units (SI) units that are provided for information only and are not considered standard.  
1.10 The text of this standard references notes and footnotes that provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.  
1.11 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prio...

  • Technical specification
    12 pages
    English language

SIGNIFICANCE AND USE
4.1 Each Facility Rating Scale in this classification provides a means for estimating the level of serviceability of a building or facility for one topic of serviceability, and for comparing that level against the level of any other building or facility.  
4.2 This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.  
4.3 This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility, or within a group of office facilities.  
4.4 This classification can be used to estimate the following: (1) serviceability of an existing facility for uses other than its present use; (2) the serviceability (potential) of a facility that has been planned but not yet built; and (3) the serviceability (potential) of a facility for which a remodelling has been planned.  
4.5 The use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires special expertise in building engineering or technology and the use of instruments, tools, or measurements.  
4.6 This classification applies only to facilities that are building constructions or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)  
4.7 This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment nor for fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements for special facilities and technologies.  
1.2 Each pair of scales, shown in Figs. 1-4, is for classifying one topic of serviceability. Each paragraph in an Occupant Requirement Scale (DEMAND Scale see Figs. 1-4) summarizes one level of requirement for serviceability on which occupants might require. The matching paragraph in the Facility Rating Scale (SUPPLY Scale see Figs. 1-4) is an interpretation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.
FIG. 1 Demand Scale A.13.1 for Group or Shared Conference Center  
FIG. 1 Supply Scale A.13.1 for Group or Shared Conference Center (continued)
FIG. 2 Demand Scale A.13.2 for Video Conferencing Provision  
FIG. 2 Supply Scale A.13.2 for Video Conferencing Provision (continued)
FIG. 3 Demand Scale A.13.3 for Simultaneous Interpretation  
FIG. 3 Supply Scale A.13.3 for Simultaneous Interpretation (continued)
FIG. 4 Demand Scale A.13.4 for Satellite and Microwave Links  
FIG. 4 Supply Scale A.13.4 for Satellite and Microwave Links (continued)
FIG. 5 Demand and Supply Scales A.13.5 for Telecommunications Center  
1.3 The entries in the Facility Rating Scale (See Figs. 1-4) are indicative and not comprehensive. They are for quick scanning, to estimate approximately, quickly, and economically, how well an office facility is likely to meet the needs of one or another type of occupant group over time. The entries are not for measuring, knowing, and evaluating how an office facility is performing.  
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.  
1.5 This classification indicates what would cause a facility to be rated at a certain level of service...

  • Standard
    10 pages
    English language
  • Standard
    10 pages
    English language

SIGNIFICANCE AND USE
4.1 Each Facility Rating Scale (see Figs. 1-18) in this classification provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability and to compare that level against the level of any other building or facility.  
4.2 This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape. Further information may be found in ISO 19208.  
4.3 This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility, or within a group of office facilities.  
4.4 This classification can be used to estimate the following:  
4.4.1 Serviceability of an existing facility for uses other than its present use.  
4.4.2 Serviceability (potential) of a facility that has been planned but not yet built.  
4.4.3 Serviceability (potential) of a facility for which remodeling has been planned.  
4.5 Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology and the use of instruments, tools, or measurements.  
4.6 This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)  
4.7 This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment nor for fire risk assessment.
SCOPE
1.1 This classification covers matched sets of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements for performance to support typical office equipment for information technology.  
1.2 Within that aspect of serviceability, each matched set of scales, shown in Figs. 1-18, are for classifying one topic of serviceability. Each topic is typically broken down into two more demand functions and supply features. Each paragraph in an Occupant Requirement Scale (see Figs. 1-18) summarizes one level of serviceability on that topic, which occupants might require. The matching entry in the Facility Rating Scale (see Figs. 1-18) is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.
FIG. 1 Demand Scale A.5.1 for Density of Office Computers and Equipment
FIG. 2 Supply Scale A.5.1 for Density of Office Computers and Equipment
FIG. 3 Demand Scale A.5.2.1 for Location of Available Power
FIG. 4 Supply Scale A.5.2.1 for Power Distribution
FIG. 5 Demand Scale A.5.2.2 for Plug-in Points at Workstation
FIG. 6 Supply Scale A.5.2.2 for Plug-in Points per Workstation
FIG. 7 Demand Scale A.5.3 for Reliability and Quality of Supply
FIG. 8 Supply Scale A.5.3 for Reliability and Quality of Supply
FIG. 9 Demand Scale A.5.4.1 for Horizontal Distribution
FIG. 10 Supply Scale A.5.4.1 for Horizontal Distribution
FIG. 11 Demand Scale A.5.4.2 for Risers
FIG. 12 Supply Scale A.5.4.2 for Risers
FIG. 13 Demand Scale A.5.4.3 for Entrance Facility
FIG. 14 Supply Scale A.5.4.3 for Entrance Facility
FIG. 15 Demand Scale A.5.4.4 for Service to the Site
FIG. 16 Supply Scale A.5.4.4 for Service to the Site
FIG. 17 Demand Scale A.5.5 for Cable Plant
FIG. 18 Supply Scale A.5.5 for Cable Plant  
1.3 The entries in the Facility Rating Scale (see Figs. 1-18) are indicative and not comprehensive. They are for quick scanning to estimate approximately, quickly, and economically, how well ...

  • Standard
    20 pages
    English language
  • Standard
    20 pages
    English language

SCOPE
1.1 This terminology consists of terms and definitions pertaining to the description, measurement, prediction, improvement, and management of buildings and building-related facilities, and, in particular, terms related to the standards generated by ASTM Committee E06 on Performance of Buildings.  
1.2 The purpose of this terminology is to provide meanings and explanations of technical terms, written for both the technical expert and the non-expert user.  
1.3 This terminology is one of a group of special terminologies, subsidiary to the comprehensive Terminology E631.  
1.4 Terms are listed in alphabetical sequence. Compound terms appear in the natural spoken order. Where definitions herein are adopted from other sources, they are copied exactly. The source is identified at the right margin following the definition and is listed in Section 2. The equivalent term in French is listed in parentheses after the English term.  
1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Standard
    6 pages
    English language

SIGNIFICANCE AND USE
4.1 Each Occupant Requirement Scale (see Figs. 1-5) in this classification provides a means to set the required level of serviceability of a building or facility for one topic of serviceability and to compare that level against any level of any other occupant, or of any building or facility.  
4.2 Each Facility Rating Scale (see Figs. 1-5) in this classification provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability and to compare that level against any level of requirement of any occupant, or of any other building or facility.  
4.3 This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.  
4.4 This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility, or within a group of office facilities.  
4.5 This classification can be used to estimate the following:  
4.5.1 Serviceability of an existing facility for uses other than its present use.  
4.5.2 Serviceability (potential) of a facility that has been planned but not yet built.  
4.5.3 Serviceability (potential) of a facility for which remodeling has been planned.  
4.6 Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology, and the use of instruments, tools, or measurements.  
4.7 This classification applies only to facilities that are building constructions, or part thereof. (While classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification. See discussion under definition 3.1.1.)  
4.8 This classification is not intended for, an...
SCOPE
1.1 This classification contains pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements for suitable thermal environment and indoor air conditions.  
1.2 Within this aspect of serviceability, each pair of scales shown in Figs. 1-53 is for classifying one topic of serviceability. Each topic typically is broken down into two more demand functions and supply features. Each paragraph in an Occupant Requirement Scale (DEMAND Scale, see Figs. 1-5) summarizes one level of requirement for serviceability on that function, which occupants might require. The matching paragraph in the Facility Rating Scale (SUPPLY Scale, see Figs. 1-5) is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.  
FIG. 1 Demand Scale A.4.1 for Information on Temperature and Humidity  
FIG. 1 Demand Scale A.4.1 for Information on Temperature and Humidity (continued)  
FIG. 1 Demand Scale A.4.1 for Information on Temperature and Humidity (continued)  
FIG. 1 Supply Scale A.4.1 for Information on Temperature and Humidity (continued)  
FIG. 1 Supply Scale A.4.1 for Information on Temperature and Humidity (continued)  
FIG. 1 Supply Scale A.4.1 for Information on Temperature and Humidity (continued)  
FIG. 2 Demand Scale A.4.2 for Information on Indoor Air Quality Conditions  
FIG. 2 Demand Scale A.4.2 for Information on Indoor Air Quality Conditions (continued)  
FIG. 2 Supply Scale A.4.2 for Information on Indoor Air Quality (continued)  
FIG. 2 Supply Scale A.4.2 for Information on Indoor Air Quality (continued)  
FIG. 2 Supply Scale A.4.2 for Information on Indoor Air Quality (continued)  
FIG. 3 Demand Scale A.4.3 for Information on Ventilation Supply Air  
FIG. 3 Demand Scale A.4.3 ...

  • Standard
    27 pages
    English language
  • Standard
    27 pages
    English language

SIGNIFICANCE AND USE
4.1 This practice can be applied to the requirements for facility serviceability of many functional occupant groups, provided that an appropriate set of requirement classifications for each type has been established.  
4.2 This practice can be applied to rating the facility serviceability of a building or building-related facility.  
4.3 This practice can be used to ascertain the requirements of a group or organization at the time when the group (1) needs to ascertain the serviceability of the facility it occupies; (2) is contemplating a move and needs to assess the relative capability of several existing facilities to perform as required, before deciding to rent, lease, or buy; (3) needs to compare its requirements to the serviceability of a facility that is being planned, or is designed but is not yet built; (4) is planning to remodel or rehabilitate the space it occupies and needs to establish the required level of serviceability that the remodeled or rehabilitated facility will have to meet.  
4.4 This practice is not affected by the complexity of the requirement for serviceability.  
4.5 This practice can be used by any individual with sufficient organizational, functional, and technical knowledge of buildings to act as an informed facilitator. The individual charged with the task of leading the process of establishing the functional requirements of an occupant group or organization needs basic facilitation and interviewing skills. The individual charged with rating the serviceability of a building needs sufficient knowledge of buildings to identify the features that are present.  
4.6 This practice provides a means of setting typical required serviceability levels for any serviceability topic, and of comparing the required levels of functionality for one occupant group or organization against levels set by others.  
4.7 This practice provides a means for organizations to set a profile of functional requirements for each type of occupant group within that...
SCOPE
1.1 This practice provides a definitive procedure for setting the level of requirements of the users (functionality) for the functional capability of a building or building-related facility.  
1.2 This practice provides a definitive procedure for rating the level of functional capability (serviceability) provided by an existing building or building-related facility, or to be provided according to the design for one.  
1.3 This practice provides a definitive procedure for creating or adapting a set of classifications for establishing the levels of functionality required of or the level of capability provided by a building or building-related facility.  
1.4 This practice can be used for setting the profile of requirements of an occupant group in an existing building or building-related facility, or of a group planning to move and looking at new accommodations to rent, buy, or build, and it can be used to assess the suitability of their present facilities.  
1.5 This practice can be used for setting the profile of requirements of an owner, facility manager, lender, or other investor.  
1.6 This practice does not specify what would cause a building to be rated at a given level. That information is found in classifications for specific topics of serviceability that contain a set of rating scales.  
1.7 This practice is not intended to be used for regulatory purposes.  
1.8 This practice contains the following information, in the sections indicated:    
Section  
Introduction  
1    
Scope  
1    
Referenced Documents  
2    
Terminology  
3    
Significance and Use  
4    
Essence of the Approach  
5    
Procedure for Setting the Profile of Required Functionality  
6    
Procedure for Setting the Profile of Functional Capability for a Building or for Building-Related Facilities  
7    
Rating the Plans or Proposals for a New Building or for a Remodel or Rehabilitation Project  
8    
Ke...

  • Standard
    17 pages
    English language

SIGNIFICANCE AND USE
4.1 Each Facility Rating Scale (see Figs. 1-12) in this classification provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability and to compare that level against the level of any other building or facility.  
4.2 This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.  
4.3 This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility or within a group of office facilities.  
4.4 This classification can be used to estimate the following:  
4.4.1 Serviceability of an existing facility for uses other than its present use.  
4.4.2 Serviceability (potential) of a facility that has been planned but not yet built.  
4.4.3 Serviceability (potential) of a facility for which remodeling has been planned.  
4.5 Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology and the use of instruments, tools, or measurements.  
4.6 This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)  
4.7 This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment nor for fire risk assessment.
SCOPE
1.1 This classification covers matched sets of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements for layout and building factors.  
1.2 Within that aspect of serviceability, each matched set of scales, shown in Figs. 1-12, are for classifying one topic of serviceability. Each topic is typically broken down into two or more demand functions or supply features. Each paragraph in an Occupant Requirement Scale (see Figs. 1-12) summarizes one level of serviceability on that function, which occupants might require. The matching entry in the Facility Rating Scale (see Figs. 1-12) is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.
FIG. 1 Demand Scale A.7.1.1 for Constraints on Layout  
FIG. 2 Demand Scale A.7.1.2 for Constraints of Population Density  
FIG. 3 Demand Scale A.7.1.3 for Cost of Upgrade  
FIG. 4 Supply Scale A.7.1.1 for Constraints on Layout  
FIG. 5 Supply Scale A.7.1.2 for Population Density Supported  
FIG. 6 Supply Scale A.7.1.3 for Cost of Upgrade  
FIG. 7 Demand Scale A.7.2.1 for Tolerance of Sound and Visual Conditions  
FIG. 8 Demand Scale A.7.2.2 Avoiding Glare on Monitors  
FIG. 9 Supply Scale A.7.2.1 Constraints on Layout  
FIG. 10 Supply Scale A.7.2.2 Avoiding Glare on Monitors  
FIG. 11 Demand Scale A.7.3 for Influence of Building Loss Features on Space Needs  
FIG. 12 Supply Scale A.7.3 Influence of Building Loss Features on Space Needs  
1.3 The entries in the Facility Rating Scale (see Figs. 1-12) are indicative and not comprehensive. They are for quick scanning to estimate approximately, quickly, and economically, how well an office facility is likely to meet the needs of one or another type of occupant group over time. The entries are not for measuring, knowing, or evaluating how an office facility is performing.  
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facil...

  • Standard
    15 pages
    English language
  • Standard
    15 pages
    English language

SIGNIFICANCE AND USE
5.1 This test method establishes water immersion, drying, and cleaning procedures to be used when determining whether building materials noted in 1.1 are flood damage resistant for applications that comply with the National Flood Insurance Program (NFIP) [44 CFR § 60.3(a)(3)].  
5.2 This test method exposes the test specimen to water immersion and drying conditions to simulate the effects of wetting and subsequent drying that occurs with a flood event. The wetting and drying exposure is followed by surface cleaning. This test method provides a measure of how test specimens may respond to water immersion, subsequent drying, and cleaning that occur with flood events.  
5.3 This test method is useful for determining water absorption characteristics of different test specimens in terms of percent increase in test specimen weight, their drying characteristics in terms of elapsed time to dry to equilibrium weight, and changes in physical appearance following water immersion and surface cleaning.  
5.4 This test method is useful in comparing the water absorption characteristics of different test specimens, their drying characteristics, and changes in physical appearance following water immersion and surface cleaning. This test method is also useful in comparing test specimen physical dimensions before water immersion, immediately following removal from water immersion, after drying, and after cleaning.  
5.5 The ability to directly compare test results will vary by many factors including test specimen size and whether test specimens are individual building materials or composite assemblies of building materials.
SCOPE
1.1 This test method is intended to apply to building materials used in construction below the base flood elevation (BFE) including, but not limited to: individual building materials and composite assemblies of building materials that constitute permanent integral parts of a finished building including walls, floors, ceilings, stairways, built-in partitions, finishes, cladding, and other similarly incorporated architectural and structural items.  
1.2 Requirements for evaluation of other hazards associated with flood damage including, but not limited to: debris impact, flood velocity, wave action, water pressure differential, scour, erosion, biological and chemical contaminants in floodwater, and other factors that would be adverse to continued use of the structure for its intended purpose including long-term occupant health impacts are outside of the scope of the methods presented herein.  
1.3 The water immersion, drying, and cleaning procedures specified in this test method establishes standard conditions for laboratory evaluation of test specimen response to water immersion, subsequent drying, and cleaning. The results of these tests are one factor in assessing the characteristics of building materials with regard to water immersion, drying, and ability to be cleaned. Application of these test results to predict these characteristics for actual building construction requires the evaluation of test conditions as compared to conditions of end-use.  
1.4 The water immersion and drying procedures shall not be construed as representative of water makeup, duration of immersion, or conditions of drying during an actual flood event because actual flood conditions vary with such factors as makeup of water, depth and duration of immersion, and ambient temperature and humidity.  
1.5 The cleaning procedures specified in this test method are intended to simulate surface cleaning that normally occurs after flooding.  
1.6 The cleaning procedures specified in this test method shall not be construed as superseding standards or manufacturer’s recommended methods for cleaning and restoration after flooding.  
1.7 A commentary to this test method is provided in Appendix X1.  
1.8 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mat...

  • Standard
    6 pages
    English language
  • Standard
    6 pages
    English language

SIGNIFICANCE AND USE
4.1 Each Facility Rating Scale in this classification provides a means for estimating the level of serviceability of a building or facility for one topic of serviceability, and for comparing that level against the level of any other building or facility.  
4.2 This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.  
4.3 This classification can be used to estimate the amount of variance of serviceability from target or from requirement for a single office facility or within a group of office facilities.  
4.4 This classification can be used to estimate the following: (1) the serviceability of an existing facility for uses other than its present use; (2) the serviceability (potential) of a facility that has been planned but not yet built; and (3) the serviceability (potential) of a facility for which a remodelling has been planned.  
4.5 The use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires special expertise in building engineering or technology and the use of instruments, tools, or measurements.  
4.6 This classification applies only to facilities that are building constructions or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)  
4.7 This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment or fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements to accommodate changes in working method, and frequent relocations of staff, and realignment of workstations.  
1.2 Each pair of scales shown in Figs. 1-5, printed side by side on a page, are for classifying one topic of serviceability within that aspect of serviceability. Each paragraph in an Occupant Requirement Scale (see Figs. 1-5) summarizes one level of serviceability on that topic that occupants might require. The matching entry in the Facility Rating Scale (see) is a translation of the requirement into a description of certain features of a facility that, taken in combination, indicate that the facility is likely to meet that level of required serviceability.
FIG. 1 Scale A.6.1 for Disruption Due to Physical Change  
FIG. 1 Scale A.6.1 for Disruption Due to Physical Change (continued)  
FIG. 2 Scale A.6.2 for Illumination, HVAC, and Sprinklers  
FIG. 2 Scale A.6.2 for Illumination, HVAC, and Sprinklers (continued)  
FIG. 3 Scale A.6.3 for Minor Changes to Layout  
FIG. 3 Scale A.6.3 for Minor Changes to Layout (continued)  
FIG. 4 Scale A.6.4 for Partition Wall Relocations  
FIG. 4 Scale A.6.4 for Partition Wall Relocations (continued)  
FIG. 5 Scale A.6.5 for Lead Time for Facilities Group  
FIG. 5 Scale A.6.5 for Lead Time for Facilities Group (continued)  
1.3 The entries in the Facility Rating Scale (see Figs. 1-5) are indicative and not comprehensive. They are for quick scanning, to estimate approximately, quickly, and economically how well an office facility is likely to meet the needs of one or another type of occupant group over time. The entries are not for measuring, knowing, and evaluating how an office facility is performing.  
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.  
1.5 This classification indi...

  • Standard
    11 pages
    English language

SIGNIFICANCE AND USE
4.1 Each Facility Rating Scale (see Figs. 1-4) in this classification provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability and to compare that level against the level of any other building or facility.  
4.2 This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.  
4.3 This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility, or within a group of office facilities.  
4.4 This classification can be used to estimate the following:  
4.4.1 Serviceability of an existing facility for uses other than its present use.  
4.4.2 Serviceability (potential) of a facility that has been planned but not yet built.  
4.4.3 Serviceability (potential) of a facility for which remodeling has been planned.  
4.5 Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology and the use of instruments, tools, or measurements.  
4.6 This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)  
4.7 This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment nor for fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements to be able to do normal office tasks outside scheduled hours.  
1.2 Within that aspect of serviceability, each pair of scales, shown in Figs. 1-4,  are for classifying one topic of serviceability. Each paragraph in an Occupant Requirement Scale (see Figs. 1-4) summarizes one level of serviceability on that topic, which occupants might require. The matching entry in the Facility Rating Scale (see Figs. 1-4) is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.  
FIG. 1 Scale A.10.1 for Operation Outside Normal Hours  
FIG. 1 Scale A.10.1 for Operation Outside Normal Hours (continued)  
FIG. 2 Scale A.10.2 for Support After Hours  
FIG. 2 Scale A.10.2 for Support After Hours (continued)  
FIG. 3 Scale A.10.3 for Temporary Loss of External Services  
FIG. 3 Scale A.10.3 for Temporary Loss of External Services (continued)  
FIG. 4 Scale A.10.4 for Continuity of Work (During Breakdowns)  
FIG. 4 Scale A.10.4 for Continuity of Work (During Breakdowns) (continued)  
1.3 The entries in the Facility Rating Scale (see Figs. 1-4) are indicative and not comprehensive. They are for quick scanning to estimate approximately, quickly, and economically, how well an office facility is likely to meet the needs of one or another type of occupant group over time. The entries are not for measuring, knowing, or evaluating how an office facility is performing.  
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.  
1.5 This classification indicates what would cause a facility to be rated at a certain level of serviceability, but does not state how to conduct a serviceability rating nor how to assign...

  • Standard
    10 pages
    English language

SIGNIFICANCE AND USE
4.1 Each Facility Rating Scale (see Figs. 1-6) in this classification provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability and to compare that level against the level of any other building or facility.  
4.2 This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.  
4.3 This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility, or within a group of office facilities.  
4.4 This classification can be used to estimate the following:  
4.4.1 Serviceability of an existing facility for uses other than its present use.  
4.4.2 Serviceability (potential) of a facility that has been planned but not yet built.  
4.4.3 Serviceability (potential) of a facility for which remodeling has been planned.  
4.5 Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology and the use of instruments, tools, or measurements.  
4.6 This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)  
4.7 This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment nor for fire risk assessment.
SCOPE
1.1 This classification contains pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements for locating the building and finding the way inside the building.  
1.2 Within that aspect of serviceability, each pair of scales, shown in Figs. 1-6, are for classifying one topic of serviceability. Each paragraph in an Occupant Requirement Scale (see Figs. 1-6) summarizes one level of serviceability on that topic, which occupants might require. The matching entry in the Facility Rating Scale (see Figs. 1-6) is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.
FIG. 1 Scale A.14.1 for Public Transportation (Urban Sites)  
FIG. 2 Scale A.14.2 for Staff Visits to Other Offices  
FIG. 3 Scale A.14.3 for Vehicular Entry and Parking  
FIG. 3 Scale A.14.3 for Vehicular Entry and Parking  (continued)  
FIG. 4 Scale A.14.4 for Wayfinding to Building and Lobby  
FIG. 4 Scale A.14.4 for Wayfinding to Building and Lobby (continued)  
FIG. 5 Scale A.14.5 for Capacity of Internal Movement Systems  
FIG. 5 Scale A.14.5 for Capacity of Internal Movement Systems  (continued)  
FIG. 6 Scale A.14.6 for Public Circulation and Wayfinding in Building  
FIG. 6 Scale A.14.6 for Public Circulation and Wayfinding in Building (continued)  
1.3 The entries in the Facility Rating Scale (see Figs. 1-6) are indicative and not comprehensive. They are for quick scanning to estimate approximately, quickly, and economically, how well an office facility is likely to meet the needs of one or another type of occupant group over time. The entries are not for measuring, knowing, or evaluating how an office facility is performing.  
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.  
1.5 This classificatio...

  • Standard
    12 pages
    English language

SIGNIFICANCE AND USE
4.1 Each Facility Rating Scale (see Figs. 1-6) in this classification provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability and to compare that level against the level of any other building or facility.  
4.2 This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.  
4.3 This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility, or within a group of office facilities.  
4.4 This classification can be used to estimate the following:  
4.4.1 Serviceability of an existing facility for uses other than its present use.  
4.4.2 Serviceability (potential) of a facility that has been planned but not yet built.  
4.4.3 Serviceability (potential) of a facility for which a remodeling has been planned.  
4.5 Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology, and the use of instruments, tools, or measurements.  
4.6 This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)  
4.7 This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment nor for fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements for suitable sound and visual conditions.  
1.2 Within that aspect of serviceability, each pair of scales, shown in Figs. 1-6, are for classifying one topic of serviceability. Each paragraph in an Occupant Requirement Scale (see Figs. 1-6) summarizes one level of serviceability on that topic, which occupants might require. The matching entry in the Facility Rating Scale (see Figs. 1-6) is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.
FIG. 1 Scale A.3.1 for Privacy and Speech Intelligibility  
FIG. 1 Scale A.3.1 for Privacy and Speech Intelligibility (continued)  
FIG. 2 Scale A.3.2 for Distraction and Disturbance  
FIG. 2 Scale A.3.2 for Distraction and Disturbance (continued)  
FIG. 3 Scale A.3.3 for Vibration  
FIG. 4 Scale A.3.4 for Lighting and Glare  
FIG. 4 Scale A.3.4 for Lighting and Glare (continued)  
FIG. 5 Scale A.3.5 for Adjustment of Lighting by Occupants  
FIG. 5 Scale A.3.5 for Adjustment of Lighting by Occupants (continued)  
FIG. 6 Scale A.3.6 for Distant and Outside Views  
1.3 The entries in the Facility Rating Scale (see Figs. 1-6) are indicative and not comprehensive. They are for quick scanning to estimate approximately, quickly, and economically, how well an office facility is likely to meet the needs of one or another type of occupant group over time. The entries are not for measuring, knowing, or evaluating how an office facility is performing.  
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.  
1.5 This classification indicates what would cause a facility to be rated at a certain level of serviceability but does not state how to condu...

  • Standard
    12 pages
    English language

SIGNIFICANCE AND USE
4.1 Each Facility Rating Scale (see Fig. 1 through Fig. 6) in this classification provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability and to compare that level against the level of any other building or facility.  
4.2 This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.  
4.3 This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility, or within a group of office facilities.  
4.4 This classification can be used to estimate the following:  
4.4.1 Serviceability of an existing facility for uses other than its present use.  
4.4.2 Serviceability (potential) of a facility that has been planned but not yet built.  
4.4.3 Serviceability (potential) of a facility for which remodeling has been planned.  
4.5 Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology and the use of instruments, tools, or measurements.  
4.6 This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)  
4.7 This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment nor for fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements for performance to support typical office work.  
1.2 Within that aspect of serviceability, each pair of scales, shown in Fig. 1 through Fig. 6,  are for classifying one topic of serviceability. Each paragraph in an Occupant Requirement Scale (see Fig. 1 through Fig. 6) summarizes one level of serviceability on that topic, which occupants might require. The matching entry in the Facility Rating Scale (see Fig. 1 through Fig. 6) is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.  
FIG. 1 Scale A.1.1 for Photocopying  
FIG. 1 Scale A.1.1 for Photocopying (continued)  
FIG. 1 Scale A.1.1 for Photocopying  (continued)  
FIG. 2 Scale A.1.2 for Training Rooms, General  
FIG. 2 Scale A.1.2 for Training Rooms, General (continued)  
FIG. 2 Scale A.1.2 for Training Rooms, General (continued)  
FIG. 3 Scale A.1.3 for Training Rooms for Computer Skills  
FIG. 3 Scale A.1.3 for Training Rooms for Computer Skills (continued)  
FIG. 4 Scale A.1.4 for Interview Rooms  
FIG. 4 Scale A.1.4 for Interview Rooms (continued)  
FIG. 5 Scale A.1.5 for Storage and Floor Loading  
FIG. 5 Scale A.1.5 for Storage and Floor Loading (continued)  
FIG. 6 Scale A.1.6 for Shipping and Receiving  
FIG. 6 Scale A.1.6 for Shipping and Receiving  (continued)  
1.3 The entries in the Facility Rating Scale (see Fig. 1 through Fig. 6) are indicative and not comprehensive. They are for quick scanning to estimate approximately, quickly, and economically, how well an office facility is likely to meet the needs of one or another type of occupant group over time. The entries are not for measuring, knowing, or evaluating how an office facility is performing.  
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been plan...

  • Standard
    16 pages
    English language

SIGNIFICANCE AND USE
4.1 Each facility rating scale in this classification (see Figs. 1-8) provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability, and to compare that level against the level of any other building or facility.  
4.2 This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such aslocation, structure, mechanical systems, age, and building shape.  
4.3 This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility, or within a group of office facilities.  
4.4 This classification can be used to estimate the following:  
4.4.1 Serviceability of an existing facility for uses other than its present use.  
4.4.2 Serviceability (potential) of a facility that has been planned but not yet built.  
4.4.3 Serviceability (potential) of a facility for which a remodeling has been planned.  
4.5 Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology, and the use of instruments, tools, or measurements.  
4.6 This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)  
4.7 This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment nor fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales (see Figs. 1-8) for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements for manageability. (A) The anticipated remaining service life on the items listed in this table should be on file, likely in an asset management plan for the facility. Otherwise, rating on this aspect of serviceability requires expert judgement on each item, and cannot be completed within a normal half-day site visit. If information is not available, then omit this item from the rating, and note that on the rating form.(B) Do not add pro rata counts for any remaining life that is estimated to be less than the threshold years given in the legend. The count in this table is not a sliding scale, for example, give all points or no points.      
1.6 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Standard
    15 pages
    English language

SIGNIFICANCE AND USE
4.1 Each Facility Rating Scale (see Figs. 1-4) in this classification provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability and to compare that level against the level of any other building or facility.  
4.2 This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.  
4.3 This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility, or within a group of office facilities.  
4.4 This classification can be used to estimate the following:  
4.4.1 Serviceability of an existing facility for uses other than its present use.  
4.4.2 Serviceability (potential) of a facility that has been planned but not yet built.  
4.4.3 Serviceability (potential) of a facility for which a remodeling has been planned.  
4.5 Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology and the use of instruments, tools, or measurements.  
4.6 This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)  
4.7 This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment nor for fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements to enable work groups or project groups to function effectively and productively.  
1.2 Within that aspect of serviceability, each pair of scales, shown in Figs. 1-4, are for classifying one topic of serviceability. Each paragraph in an Occupant Requirement Scale (see Figs. 1-4) summarizes one level of serviceability on that topic, which occupants might require. The matching entry in the Facility Rating Scale (see Figs. 1-4) is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.
FIG. 1 Scale A.2.1 for Meeting and Conference Rooms
FIG. 1 Scale A.2.1 for Meeting and Conference Rooms (continued)
FIG. 1 Scale A.2.1 for Meeting and Conference Rooms (continued)
FIG. 2 Scale A.2.2 for Informal Meetings and Interaction
FIG. 2 Scale A.2.2 for Informal Meetings and Interaction (continued)
FIG. 3 Scale A.2.3 for Group Layout and Territory
FIG. 3 Scale A.2.3 for Group Layout and Territory (continued)
FIG. 4 Scale A.2.4 for Group Workrooms
FIG. 4 Scale A.2.4 for Group Workrooms (continued)  
1.3 The entries in the Facility Rating Scale (see Figs. 1-4) are indicative and not comprehensive. They are for quick scanning to estimate approximately, quickly, and economically, how well an office facility is likely to meet the needs of one or another type of occupant group over time. The entries are not for measuring, knowing, or evaluating how an office facility is performing.  
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.  
1.5 This classification indicates what would cause a facility to be rated at a certain level of serviceability but does not state how to conduct a serviceabi...

  • Standard
    12 pages
    English language

SIGNIFICANCE AND USE
4.1 Each Facility Rating Scale (see Figs. 1-6) in this classification provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability and to compare that level against the level of any other building or facility.  
4.2 This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.  
4.3 This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility, or within a group of office facilities.  
4.4 This classification can be used to estimate the following:  
4.4.1 Serviceability of an existing facility for uses other than its present use.  
4.4.2 Serviceability (potential) of a facility that has been planned but not yet built.  
4.4.3 Serviceability (potential) of a facility for which remodeling has been planned.  
4.5 Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology and the use of instruments, tools, or measurements.  
4.6 This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)  
4.7 This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment nor for fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements in support of recruiting and keeping quality employees.  
1.2 Within that aspect of serviceability, each pair of scales, shown in Figs. 1-6, are for classifying one topic of serviceability. Each paragraph in an Occupant Requirement Scale (see Figs. 1-6) summarizes one level of serviceability on that topic, which occupants might require. The matching entry in the Facility Rating Scale (see Figs. 1-6) is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.
FIG. 1 Scale A.12.1 for Food  
FIG. 1 Scale A.12.1 for Food (continued)  
FIG. 2 Scale A.12.2 for Shops  
FIG. 3 Scale A.12.3 for Daycare  
FIG. 4 Scale A.12.4 for Exercise Room  
FIG. 5 Scale A.12.5 for Bicycle Racks for Staff  
FIG. 6 Scale A.12.6 for Seating Away from Work Areas  
FIG. 6 Scale A.12.6 for Seating Away from Work Areas (continued)  
1.3 The entries in the Facility Rating Scale (see Figs. 1-6) are indicative and not comprehensive. They are for quick scanning to estimate approximately, quickly, and economically, how well an office facility is likely to meet the needs of one or another type of occupant group over time. The entries are not for measuring, knowing, or evaluating how an office facility is performing.  
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.  
1.5 This classification indicates what would cause a facility to be rated at a certain level of serviceability but does not state how to conduct a serviceability rating nor how to assign a serviceability score. That information is found in Practice E1334. The scales in this classification are complimentary to and compatible with Practice E1334. Each...

  • Standard
    9 pages
    English language

SIGNIFICANCE AND USE
4.1 Each Facility Rating Scale (see Figs. 1-4) in this classification provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability and to compare that level against the level of any other building or facility.  
4.2 This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.  
4.3 This classification can be used to estimate the following:  
4.3.1 Serviceability of an existing facility for uses other than its present use.  
4.3.2 Serviceability (potential) of a facility that has been planned but not yet built.  
4.3.3 Serviceability (potential) of a facility for which remodeling has been planned.  
4.4 Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology and the use of instruments, tools, or measurements.  
4.5 This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)  
4.6 This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment nor for fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements for operations and maintenance.  
1.2 Within that aspect of serviceability, each pair of scales, shown in Figs. 1-4, are for classifying one topic of serviceability. Each paragraph in an Occupant Requirement Scale (see Figs. 1-4) summarizes one level of serviceability on that topic, which occupants might require. The matching entry in the Facility Rating Scale (see Figs. 1-4) is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.  
FIG. 1 Scale B.3.1 for Strategy and Program for Operations and Maintenance  
FIG. 1 Scale B.3.1 for Strategy and Program for Operations and Maintenance (continued)  
FIG. 2 Scale B.3.2 for Competences of In-house Staff  
FIG. 2 Scale B.3.2 for Competences of In-house Staff (continued)  
FIG. 3 Scale B.3.3 for Occupant Satisfaction  
FIG. 3 Scale B.3.3 for Occupant Satisfaction (continued)  
FIG. 4 Scale B.3.4 for Information on Unit Costs and Consumption  
FIG. 4 Scale B.3.4 for Information on Unit Costs and Consumption (continued)  
1.3 The entries in the Facility Rating Scale (see Figs. 1-4) are indicative and not comprehensive. They are for quick scanning and rating a facility and not for evaluating or diagnosing it.  
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.  
1.5 This classification indicates what would cause a facility to be rated at a certain level of serviceability but does not state how to conduct a serviceability rating nor how to assign a serviceability score. That information is found in Practice E1334. The scales in this classification are complimentary to and compatible with Practice E1334. Each requires the other.  
1.6 The values stated in inch-pound units are to be regarded as standard. No other units of measurement are included in this standard.  
1.7 This international standard was developed in accordance wit...

  • Standard
    10 pages
    English language

SIGNIFICANCE AND USE
4.1 Each Facility Rating Scale (see Figs. 2-7) in this classification provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability and to compare that level against the level of any other building or facility.  
4.2 This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.  
4.3 This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility, or within a group of office facilities.  
4.4 This classification can be used to estimate the following:  
4.4.1 Serviceability of an existing facility for uses other than its present use.  
4.4.2 Serviceability (potential) of a facility that has been planned but not yet built.  
4.4.3 Serviceability (potential) of a facility for which remodeling has been planned.  
4.5 Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology and the use of instruments, tools, or measurements.  
4.6 This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)  
4.7 This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment nor for fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements for protection of a building or site.  
1.2 Within that aspect of serviceability, each pair of scales, shown in Figs. 2-7, are for classifying one topic of serviceability. Each paragraph in an Occupant Requirement Scale (see Figs. 2-7) summarizes one level of serviceability on that topic, which occupants might require. The matching entry in the Facility Rating Scale (see Figs. 2-7) is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.
FIG. 1 Zones of Physical Security
FIG. 2 Scale A.9.1 for Protection Around Building
FIG. 2 Scale A.9.1 for Protection Around Building (continued)  
FIG. 3 Scale A.9.2 for Protection from Unauthorized Access to Site and Parking
FIG. 3 Scale A.9.2 for Protection from Unauthorized Access to Site and Parking (continued)
FIG. 4 Scale A.9.3 for Protective Surveillance of Site
FIG. 4 Scale A.9.3 for Protective Surveillance of Site (continued)
FIG. 5 Scale A.9.4 for Perimeter of Building
FIG. 5 Scale A.9.4 for Perimeter of Building (continued)
FIG. 6 Scale A.9.5 for Public Zone of Building
FIG. 6 Scale A.9.5 for Public Zone of Building (continued)
FIG. 7 Scale A.9.6 for Facility Protection Services
FIG. 7 Scale A.9.6 for Facility Protection Services (continued)  
1.3 The entries in the Facility Rating Scale (see Figs. 2-7) are indicative and not comprehensive. They are for quick scanning to estimate approximately, quickly, and economically, how well an office facility is likely to meet the needs of one or another type of occupant group over time. The entries are not for measuring, knowing, or evaluating how an office facility is performing.  
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line...

  • Standard
    14 pages
    English language

SIGNIFICANCE AND USE
4.1 Each Facility Rating Scale (see Figs. 1-7) in this classification provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability and to compare that level against the level of any other building or facility.  
4.2 This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.  
4.3 This classification can be used to estimate the amount of variance of serviceability from target or from requirement for a single office facility or within a group of office facilities.  
4.4 This classification can be used to estimate the following:  
4.4.1 Serviceability of an existing facility for uses other than its present use.  
4.4.2 Serviceability (potential) of a facility that has been planned but not yet built.  
4.4.3 Serviceability (potential) of a facility for which remodeling has been planned.  
4.5 Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology and the use of instruments, tools, or measurements.  
4.6 This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)  
4.7 This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment nor for fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements for image to the public and occupants.  
1.2 Within that aspect of serviceability, each pair of scales, shown in Figs. 1-7, are for classifying one topic of serviceability. Each paragraph in an Occupant Requirement Scale (see Figs. 1-7) summarizes one level of serviceability on that topic, which occupants might require. The matching entry in the Facility Rating Scale (see Figs. 1-7) is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.  
FIG. 1 Scale A.11.1 for Exterior Appearance  
FIG. 1 Scale A.11.1 for Exterior Appearance (continued)  
FIG. 2 Scale A.11.2 for Public Lobby of Building  
FIG. 2 Scale A.11.2 for Public Lobby of Building (continued)  
FIG. 3 Scale A.11.3 for Public Spaces Within the Building  
FIG. 3 Scale A.11.3 for Public Spaces Within the Building (continued)  
FIG. 4 Scale A.11.4 for Appearance and Spaciousness of Office Spaces  
FIG. 5 Scale A.11.5 for Finishes and Materials in Office Spaces  
FIG. 6 Scale A.11.6 for Identity Outside the Building  
FIG. 6 Scale A.11.6 for Identity Outside the Building (continued)  
FIG. 7 Scale A.11.7 for Neighborhood and Site  
FIG. 7 Scale A.11.7 for Neighborhood and Site (continued)  
1.3 The entries in the Facility Rating Scale (see Figs. 1-7) are indicative and not comprehensive. They are for quick scanning to estimate approximately, quickly, and economically, how well an office facility is likely to meet the needs of one or another type of occupant group over time. The entries are not for measuring, knowing, or evaluating how an office facility is performing.  
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.  ...

  • Standard
    14 pages
    English language

SIGNIFICANCE AND USE
4.1 Each Facility Rating Scale (see Figs. 1-5) in this classification provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability and to compare that level against the level of any other building or facility.  
4.2 This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.  
4.3 This classification can be used to estimate the following:  
4.3.1 Serviceability of an existing facility for uses other than its present use.  
4.3.2 Serviceability (potential) of a facility that has been planned but not yet built.  
4.3.3 Serviceability (potential) of a facility for which remodeling has been planned.  
4.4 Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology and the use of instruments, tools, or measurements.  
4.5 This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)  
4.6 This classification is not intended for, and is not suitable for, use for regulatory purposes nor for fire hazard assessment nor for fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements for cleanliness.  
1.2 Within that aspect of serviceability, each pair of scales, shown in Figs. 1-5, are for classifying one topic of serviceability. Each paragraph in an Occupant Requirement Scale (see Figs. 1-5) summarizes one level of serviceability on that topic, which occupants might require. The matching entry in the Facility Rating Scale (see Figs. 1-5) is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.
FIG. 1 Scale B.4.1 for Exterior and Public Areas  
FIG. 1 Scale B.4.1 for Exterior and Public Areas (continued)  
FIG. 2 Scale B.4.2 for Office Areas (Interior)  
FIG. 3 Scale B.4.3 for Toilets and Washrooms  
FIG. 4 Scale B.4.4 for Special Cleaning  
FIG. 5 Scale B.4.5 for Waste Disposal for Building  
FIG. 5 Scale B.4.5 for Waste Disposal for Building (continued)  
1.3 The entries in the Facility Rating Scale (see Figs. 1-5) are indicative and not comprehensive. They are for quick scanning and rating a facility and not for evaluating or diagnosing it.  
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.  
1.5 This classification indicates what would cause a facility to be rated at a certain level of serviceability but does not state how to conduct a serviceability rating nor how to assign a serviceability score. That information is found in Practice E1334. The scales in this classification are complimentary to and compatible with Practice E1334. Each requires the other.  
1.6 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Standard
    8 pages
    English language

SIGNIFICANCE AND USE
4.1 Each facility rating scale in this classification provides a means for estimating the level of serviceability of a building or facility for one topic of serviceability, and for comparing that level against the level of any other building or facility.  
4.2 This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.  
4.3 This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility, or within a group of office facilities.  
4.4 This classification can be used to estimate the following: (1) the serviceability of an existing facility for uses other than its present use; (2) the serviceability (potential) of a facility that has been planned but not yet built; and (3) the serviceability (potential) of a facility for which a remodeling has been planned.  
4.5 The use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology and the use of instruments, tools, or measurements.  
4.6 This classification applies only to facilities that are building constructions or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)  
4.7 This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment or fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements to protect occupant assets.  
1.2 Each pair of scales, shown in Figs. 1-8, printed side by side on a page, are for classifying one topic of serviceability within that aspect of serviceability. Each paragraph in an Occupant Requirement Scale (see Figs. 1-8) summarizes one level of serviceability on that topic that occupants might require. The matching entry in the Facility Rating Scale (see Figs. 1-8) is a translation of the requirement into a description of certain features of a facility that, taken in combination, indicate that the facility is likely to meet that level of required serviceability.  
FIG. 1 Scale A.8.1 for Control of Access from Building Public Zone to Occupant Reception Zone
FIG. 1 Scale A.8.1 for Control of Access from Building Public Zone to Occupant Reception Zone (continued)
FIG. 2 Scale A.8.2 for Interior Zones of Security
FIG. 2 Scale A.8.2 for Interior Zones of Security (continued)
FIG. 3 Scale A.8.3 for Vaults and Secure Rooms
FIG. 3 Scale A.8.3 for Vaults and Secure Rooms (continued)
FIG. 4 Scale A.8.4 for Security of Cleaning Service Systems
FIG. 4 Scale A.8.4 for Security of Cleaning Service Systems (continued)
FIG. 5 Scale A.8.5 for Security of Maintenance Service Systems
FIG. 6 Scale A.8.6 for Security of Renovations Outside Active Hours
FIG. 6 Scale A.8.6 for Security of Renovations Outside Active Hours (continued)
FIG. 7 Scale A.8.7 for Systems for Secure Garbage
FIG. 8 Scale A.8.8 for Security of Key and Card Control Systems  
1.3 The entries in the Facility Rating Scale (see Figs. 1-8) are indicative and not comprehensive. They are for quick scanning, to estimate approximately, rapidly, and economically, how well an office facility is likely to meet the needs of one or another type of occupant group over time. The entries are not for measuring, knowing, and evaluating how an office facility is performing.  
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be...

  • Standard
    15 pages
    English language

SIGNIFICANCE AND USE
4.1 Use this practice to identify and measure the amount of actual and effective floor area that will be unavailable to occupants for the placement of people’s workplaces, furniture, and equipment or for circulation.  
4.2 Findings from use of this practice are intended for optional inclusion with reports of floor area measured in accordance with Practice E1836/E1836M or in accordance with ANSI/BOMA Z65.1–1996.
Note 1: The choice between using Practice E1836/E1836M or ANSI/BOMA Z65.1–1996 as the basis for measurement depends on the objectives of the analysis. Practice E1836/E1836M is oriented to the traditional interests of design professionals and would be particularly suitable for single-tenant buildings whereas some categories of space measured by ANSI/BOMA Z65.1–1996 are oriented to the leasing of multi-tenant buildings by real estate professionals.  
4.3 this practice is not intended for use for regulatory purposes, nor for fire hazard assessment, nor for fire risk assessment.
SCOPE
1.1 This practice specifies how to measure certain characteristics of a building, known as building loss features, inside the exterior gross area of a floor and how to calculate the amount of actual and effective floor area that will be not be available for the placement of people’s workplaces, furniture, equipment, or for circulation, if using standard furnishings and orthogonal furniture systems.  
1.2 This practice can be used to specify a performance requirement to limit the amount of floor area that may be taken up by building loss features.  
1.3 This practice can be used to assess how well a design(s) for an office facility meets a performance requirement regarding floor area.  
1.4 This practice can be used to assess how well a constructed office building has met a performance requirement regarding floor area.  
1.5 This practice is not intended for and not suitable for use for regulatory purposes, fire hazard assessment, and fire risk assessment.  
1.6 Users of this practice should recognize that, in some situations, the amount of certain actual and effective floor area losses may be mitigated to some degree at some cost by custom-tailoring spaces and creating specially fitted furnishings and carpentry to get some value from space which would not otherwise be usable.  
1.7 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.  
1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Standard
    11 pages
    English language
  • Standard
    11 pages
    English language

SIGNIFICANCE AND USE
4.1 Each Facility Rating Scale in this classification (see Figs. 1-24) provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability, and to compare that level against the level of any other building or facility.  
4.2 This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.  
4.3 This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility, or within a group of office facilities.  
4.4 This classification can be used to estimate the following:  
4.4.1 Serviceability of an existing facility for uses other than its present use.  
4.4.2 Serviceability (potential) of a facility that has been planned but not yet built.  
4.4.3 Serviceability (potential) of a facility for which a remodeling has been planned.  
4.5 Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology, and the use of instruments, tools, or measurements.  
4.6 This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)
SCOPE
1.1 This classification covers matched sets of scales (see Figs. 1-24) for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements for structure and building envelope.  
1.2 Within that aspect of serviceability, each matched set of scales (see Figs. 1-24) is for classifying one topic of serviceability. Each topic is typically broken down into two more demand functions and supply features. Each paragraph in an Occupant Requirement Scale summarizes one level of serviceability on that function, which occupants might require. The matching entry in the Facility Rating Scale is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.  
1.3 The entries in the Facility Rating Scale (see Figs. 1-24) are indicative and not comprehensive. They are for quick scanning, to estimate approximately, quickly, and economically, how well an office facility is likely to meet the needs of one or another type of occupant group, over time. The entries are not for measuring, knowing, or evaluating how an office facility is performing.  
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.  
1.5 This classification indicates what would cause a facility to be rated at a certain level of serviceability, but does not state how to conduct a serviceability rating nor how to assign a serviceability score. That information is found in Practice E1679. The scales in Figs. 1-24 are complimentary to and compatible with Practice E1679. Each requires the other.  
1.6 The scales are intended to identify the levels of various requirements unique to a particular user, and the serviceability (capability) of a building to meet those requirements. The scales thus supplement rather than include code requirements. It remains the responsibility of designers, builders, and building managers to meet applicable code requirements relative to their respective roles in facility design, construction, and...

  • Standard
    25 pages
    English language
  • Standard
    25 pages
    English language

SIGNIFICANCE AND USE
5.1 This practice is intended for use as a voluntary standard by parties who wish to undertake the seismic risk assessment of properties. The goal is for users to objectively and reliably compare the financial risks of earthquake damage to buildings, or groups of buildings, on a consistent basis.  
5.2 This practice is designed to provide requirements for the evaluation of earthquake damage risk so that technical reports prepared for the evaluation and rating of seismic risk of a building(s) will be adequate for use by other entities. Potential users including, but are not be limited to, those making equity investments, lending, and financial transactions, including securitized mortgage lending by mortgage originators, loan servicers, underwriters, rating agencies, and purchasers of bonds secured by the real estate.  
5.3 The use of this practice may permit a user to satisfy, in part, their requirements for due diligence in assessing a property's potential for losses associated with earthquakes for real estate transactions.
SCOPE
1.1 This practice establishes standard-of-care for evaluation and classification of the financial risks from earthquake damage to real estate improvements for use in financial mortgage transactions and capital investment evaluation. As such, this practice permits a user to satisfy, in part, their real estate transaction due-diligence requirements with respect to assessing and characterizing a property’s potential losses from earthquakes. This practice is intended to address only physical damage to the property from site and building response.  
1.1.1 Hazards addressed in this practice include earthquake ground shaking, earthquake-caused site instability, including faulting, subsidence, settlement landslides and soil liquefaction, earthquake-caused tsunamis and seiches, and earthquake-caused flooding from dam or dike failures.  
1.1.2 Earthquake-caused fires and toxic materials releases are not hazards considered in this practice.  
1.1.3 This practice does not purport to provide for the preservation of life safety, or prevention of building damage associated with its use, or both.
1.1.3.1 This practice does not address requirements of any federal, state, or local laws and regulations of building construction or maintenance. Users are cautioned that current federal, state, and local laws and regulations may differ from those in effect at the times of construction or modification of the building(s), or both.
1.1.3.2 This practice does not address the contractual and legal obligations between prior and subsequent Users of seismic risk assessment reports or between providers who prepared the report and those who would like to use such prior reports.
1.1.3.3 This practice does not address the contractual and legal obligations between a provider and a user, and other parties, if any.  
1.1.4 It is the responsibility of the owner of the building(s) to establish appropriate life-safety and damage prevention practices and determine the applicability of current regulatory limitations prior to use.  
1.2 Considerations not included in the scope: the impacts of damage to contents, loss of income(s), rents, or other economic benefits of use of the property, or from legal judgments, fire sprinkler water-induced damage or fire.  
1.3 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.

  • Standard
    14 pages
    English language
  • Standard
    14 pages
    English language

ABSTRACT
This guide provides guidance on conducting seismic risk assessments for buildings. As such, this guide assists a User to assess a property’s potential for losses from earthquake occurrences. Hazards addressed in this guide include earthquake ground shaking, earthquake-caused site instability, including fault rupture, landslides and soil liquefaction, lateral spreading and settlement, and earthquake-caused off-site response impacting the property, including flooding from dam or dike failure, tsunamis and seiches. This guide is intended to reflect a commercially prudent and reasonable investigation for performance of seismic risk assessments. Seismic risk assessments may be performed for an individual building or a group of buildings. This guide provides suggested approaches for the performance of five different types of seismic risk assessments. Building stability, site stability, building damageability, contents damageability, business interruption, and application and temporal relevance of report. Each is intended to serve different financial and management needs of the User. An earthquake ground motion assessment should be conducted in conjuction with probable loss evaluations for building damageability and may have applications in some scenario loss studies, as well as building stability or site stability assessments. Seismic risk assessments may consider varying degrees of assessment of a building or buildings from Level 0 to Level 3.
SIGNIFICANCE AND USE
4.1 Uses—This Guide is intended for use on a voluntary basis by parties such as lenders, loan servicers, insurers and equity investors in real estate (Users) who wish to estimate possible earthquake losses to buildings. This guide outlines procedures for conducting a seismic risk assessment for a specific User considering the User's requirements for due diligence. The specific purpose of this guide is to provide Users with seismic risk assessment during the anticipated term for holding either the mortgage or the deed. A seismic risk assessment prepared in accordance with this guide should reference or state that the guidance in this document was used as a basis for the report and should also identify any deviations from the guidelines. This guide is intended to reflect a commercially prudent and reasonable investigation for performance of seismic risk assessments.  
4.1.1 Users—This Guide is designed to assist the User in developing information about the earthquake-related damage potential of a building, or groups of buildings.
4.1.1.1 Use of this guide may permit a User to satisfy, in part, their requirements for due diligence in assessing a building’s potential for losses associated with earthquakes for real estate transactions.  
4.1.2 Types of Investigations—This guide provides suggested approaches for the performance of five different types of assessments. Each is intended to serve different financial and management needs of the User. Several of these types of assessment specifically depend on characterization of the earthquake ground motion as given in Section 7.
4.1.2.1 Building Stability (BS)—Assessment of whether the building will maintain vertical load-carrying capacity in whole or in part during considered earthquake ground motions (see Section 8).
4.1.2.2 Site Stability (SS)—Assessment of the likelihood that the site will remain stable in earthquakes and is not subject to failure through faulting, soil liquefaction, landslide, or other site respo...
SCOPE
1.1 This guide provides guidance on conducting seismic risk assessments for buildings. As such, this guide assists a User to assess a property's potential for losses from earthquake occurrences.  
1.1.1 Hazards addressed in this guide include:
1.1.1.1 Earthquake ground shaking,
1.1.1.2 Earthquake-caused site instability, including fault rupture, landslides, soil liquefaction, lateral spreading and settlement, and
1.1.1.3 Earthquake-caused off-site response impacting ...

  • Guide
    18 pages
    English language
  • Guide
    18 pages
    English language

SIGNIFICANCE AND USE
4.1 This practice can be used to facilitate comparison of areas that have been measured but it does not specify what measurements must be conducted.  
4.2 This practice can be used in space programming and forecasting of space requirements.  
4.3 This practice can be used to classify areas for internal cost accounting purposes.  
4.4 This practice can be used to compare space use between organizations.
SCOPE
1.1 This practice provides a definitive procedure for measuring and classifying floor area in buildings for use in facility management, specifying occupant requirements, space planning, and for strategic facility planning.  
1.2 This practice specifies the sequence in which to measure floor area.  
1.3 This practice is applicable to owned, rented, and leased buildings.  
1.4 Use Annex A1 to measure floor area in office facilities. The measurement practice in Annex A1 may also be suitable for use in other functional types of building which include offices, such as research, laboratory, or manufacturing buildings and building-related facilities.  
1.5 The practice in Annex A1 is not intended for use in lease negotiations with owners of commercial office buildings or related properties. For that purpose, refer to the American National Standard published by the American National Standards Institute under the designation ANSI/BOMA Z65.1–1996 and commonly known as the ANSI-BOMA standard.  
1.6 This practice is not intended for and not suitable for use for regulatory purposes, fire hazard assessment, and fire risk assessment.  
1.7 This practice was developed for use within North America and includes some rules comparable to ISO 9836 Performance Standards in Building—Definition and Calculation of Area and Space Indicators.  
1.8 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.  
1.9 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

  • Standard
    17 pages
    English language

SIGNIFICANCE AND USE
4.1 Each Facility Rating Scale (see Figs. 1-6) in this classification provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability and to compare that level against the level of any other building or facility.  
4.2 This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape. Further information may be found in ISO 6240.  
4.3 This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility, or within a group of office facilities.  
4.4 This classification can be used to estimate the following:  
4.4.1 Serviceability of an existing facility for uses other than its present use.  
4.4.2 Serviceability (potential) of a facility that has been planned but not yet built.  
4.4.3 Serviceability (potential) of a facility for which remodeling has been planned.  
4.5 Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology and the use of instruments, tools, or measurements.  
4.6 This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)  
4.7 This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment nor for fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements for performance to support typical office equipment for information technology.  
1.2 Within that aspect of serviceability, each pair of scales, shown in Figs. 1-6, are for classifying one topic of serviceability. Each paragraph in an Occupant Requirement Scale (see Figs. 1-6) summarizes one level of serviceability on that topic, which occupants might require. The matching entry in the Facility Rating Scale (see Figs. 1-6) is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.
FIG. 1 Scale A.5.1 for Office Computers and Related Equipment
FIG. 1 Scale A.5.1 for Office Computers and Related Equipment (continued)
FIG. 2 Scale A.5.2 for Power at the Workplace
FIG. 2 Scale A.5.2 for Power at the Workplace (continued)
FIG. 3 Scale A.5.3 for Building Power
FIG. 3 Scale A.5.3 for Building Power (continued)
FIG. 4 Scale for A.5.4 for Telecommunications Core
FIG. 4 Scale for A.5.4 for Telecommunications Core (continued)
FIG. 4 Scale for A.5.4 for Telecommunications Core (continued)
FIG. 5 Scale for A.5.5 for Cable Plant
FIG. 6 Scale A.5.6 for Cooling  
1.3 The entries in the Facility Rating Scale (see Figs. 1-6) are indicative and not comprehensive. They are for quick scanning to estimate approximately, quickly, and economically, how well an office facility is likely to meet the needs of one or another type of occupant group over time. The entries are not for measuring, knowing, or evaluating how an office facility is performing.  
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.  
1.5 This classification indicates what would...

  • Standard
    13 pages
    English language
  • Standard
    13 pages
    English language

SIGNIFICANCE AND USE
4.1 Each Occupant Requirement Scale (see Figs. 1-5) in this classification provides a means to set the required level of serviceability of a building or facility for one topic of serviceability and to compare that level against any level of any other occupant, or of any building or facility.  
4.2 Each Facility Rating Scale (see Figs. 1-5) in this classification provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability and to compare that level against any level of requirement of any occupant, or of any other building or facility.  
4.3 This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.  
4.4 This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility, or within a group of office facilities.  
4.5 This classification can be used to estimate the following:  
4.5.1 Serviceability of an existing facility for uses other than its present use.  
4.5.2 Serviceability (potential) of a facility that has been planned but not yet built.  
4.5.3 Serviceability (potential) of a facility for which remodeling has been planned.  
4.6 Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology, and the use of instruments, tools, or measurements.  
4.7 This classification applies only to facilities that are building constructions, or part thereof. (While classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification. See discussion under definition 3.1.1.)  
4.8 This classification is not intended for, an...
SCOPE
1.1 This classification contains pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements for suitable thermal environment and indoor air conditions.  
1.2 Within this aspect of serviceability, each pair of scales, shown in Figs. 1-5,3 is for classifying one topic of serviceability. Each paragraph in an Occupant Requirement Scale (see Figs. 1-5) summarizes one level of requirement for serviceability on that topic, which occupants might require. The matching paragraph in the Facility Rating Scale (see Figs. 1-5) is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.  
FIG. 1 Scale A.4.1 for Temperature and Humidity  
FIG. 1 Scale A.4.1 for Temperature and Humidity (continued)  
FIG. 1 Scale A.4.1 for Temperature and Humidity (continued)  
FIG. 2 Scale A.4.2 for Indoor Air Quality Conditions  
FIG. 2 Scale A.4.2 for Indoor Air Quality Conditions (continued)  
FIG. 3 Scale A.4.3 for Ventilation (Air Supply)  
FIG. 3 Scale A.4.3 for Ventilation (Air Supply) (continued)  
FIG. 3 Scale A.4.3 for Ventilation (Air Supply) (continued)  
FIG. 4 Scale A.4.4 for Local Adjustments by Occupants  
FIG. 4 Scale A.4.4 for Local Adjustments by Occupants (continued)  
FIG. 5 Scale A.4.5 for Ventilation with Openable Windows  
FIG. 5 Scale A.4.5 for Ventilation with Openable Windows (continued)  
FIG. 5 Scale A.4.5 for Ventilation with Openable Windows (continued)  
1.3 The paragraphs in the Facility Rating Scale (see Figs. 1-5) are indicative and not comprehensive. They are for quick scanning to estimate approximately, quickly, and economically how well a facility is likely to meet the needs of one or another type of occupant group over time. The paragraphs are not fo...

  • Standard
    14 pages
    English language
  • Standard
    14 pages
    English language

SIGNIFICANCE AND USE
4.1 Each Facility Rating Scale in this classification provides a means for estimating the level of serviceability of a building or facility for one topic of serviceability, and for comparing that level against the level of any other building or facility.  
4.2 This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.  
4.3 This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility, or within a group of office facilities.  
4.4 This classification can be used to estimate the following: (1) serviceability of an existing facility for uses other than its present use; (2) the serviceability (potential) of a facility that has been planned but not yet built; and (3) the serviceability (potential) of a facility for which a remodelling has been planned.  
4.5 The use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires special expertise in building engineering or technology and the use of instruments, tools, or measurements.  
4.6 This classification applies only to facilities that are building constructions or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)  
4.7 This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment nor for fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements for special facilities and technologies.  
1.2 Each pair of scales shown in Figs. 1-6 printed side-by-side on a page, are for classifying one topic of serviceability within that aspect of serviceability. Each paragraph in an Occupant Requirement Scale (see Figs. 1-6) summarizes one level of serviceability on that topic that occupants might require. The matching entry in the Facility Rating Scale (See Figs. 1-6) is a translation of the requirement into a description of certain features of a facility that, taken in combination, indicate that the facility is likely to meet that level of required serviceability.  
FIG. 1 Scale A.13.1 for Group or Shared Conference Center  
FIG. 2 Scale A.13.2 for Video Teleconference Facilities  
FIG. 3 Scale A.13.3 for Simultaneous Translation  
FIG. 4 Scale A.13.4 for Satellite and Microwave Links  
FIG. 5 Scale A.13.5 for Mainframe Computer Center  
FIG. 6 Scale A.13.6 for Telecommunications Center  
1.3 The entries in the Facility Rating Scale (See Figs. 1-6) are indicative and not comprehensive. They are for quick scanning, to estimate approximately, quickly, and economically, how well an office facility is likely to meet the needs of one or another type of occupant group over time. The entries are not for measuring, knowing, and evaluating how an office facility is performing.  
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.  
1.5 This classification indicates what would cause a facility to be rated at a certain level of serviceability, but it does not state how to conduct a serviceability rating nor how to assign a serviceability score. That information is found in Practice E1334. The scales in this classification are complementary to and compatible with Practice E1334. Each requires the o...

  • Standard
    8 pages
    English language
  • Standard
    8 pages
    English language

SIGNIFICANCE AND USE
4.1 Each Facility Rating Scale (see Figs. 1-3) in this classification provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability and to compare that level against the level of any other building or facility.  
4.2 This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.  
4.3 This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility or within a group of office facilities.  
4.4 This classification can be used to estimate the following:  
4.4.1 Serviceability of an existing facility for uses other than its present use.  
4.4.2 Serviceability (potential) of a facility that has been planned but not yet built.  
4.4.3 Serviceability (potential) of a facility for which remodeling has been planned.  
4.5 Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology and the use of instruments, tools, or measurements.  
4.6 This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)  
4.7 This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment nor for fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements for layout and building factors.  
1.2 Within that aspect of serviceability, each pair of scales, shown in Figs. 1-3, are for classifying one topic of serviceability. Each paragraph in an Occupant Requirement Scale (see Figs. 1-3) summarizes one level of serviceability on that topic, which occupants might require. The matching entry in the Facility Rating Scale (see Figs. 1-3) is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.
FIG. 1 Scale A.7.1 for Influence of HVAC on Layout  
FIG. 1 Scale A.7.1 for Influence of HVAC on Layout (continued)  
FIG. 2 Scale A.7.2 for the Influence of Sound and Visual Factors on Layout  
FIG. 2 Scale A.7.2 for the Influence of Sound and Visual Factors on Layout (continued)  
FIG. 3 Scale A.7.3 for the Influence of Building Loss Factors on Space Needs  
1.3 The entries in the Facility Rating Scale (see Figs. 1-3) are indicative and not comprehensive. They are for quick scanning to estimate approximately, quickly, and economically, how well an office facility is likely to meet the needs of one or another type of occupant group over time. The entries are not for measuring, knowing, or evaluating how an office facility is performing.  
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.  
1.5 This classification indicates what would cause a facility to be rated at a certain level of serviceability but does not state how to conduct a serviceability rating nor how to assign a serviceability score. That information is found in Practice E1334. The scales in this classification are complimentary to and compatible with Practice E1334. Each requires the ot...

  • Standard
    10 pages
    English language
  • Standard
    10 pages
    English language

SIGNIFICANCE AND USE
5.1 This test method establishes water immersion, drying, and cleaning procedures to be used when determining whether building materials noted in 1.1 are flood damage resistant for applications that comply with the National Flood Insurance Program (NFIP) [44 CFR § 60.3(a)(3)].  
5.2 This test method exposes the test specimen to water immersion and drying conditions to simulate the effects of wetting and subsequent drying that occurs with a flood event. The wetting and drying exposure is followed by surface cleaning. This test method provides a measure of how test specimens may respond to water immersion, subsequent drying, and cleaning that occur with flood events.  
5.3 This test method is useful for determining water absorption characteristics of different test specimens in terms of percent increase in test specimen weight, their drying characteristics in terms of elapsed time to dry to equilibrium weight, and changes in physical appearance following water immersion and surface cleaning.  
5.4 This test method is useful in comparing the water absorption characteristics of different test specimens, their drying characteristics, and changes in physical appearance following water immersion and surface cleaning. This test method is also useful in comparing test specimen physical dimensions before water immersion, immediately following removal from water immersion, after drying, and after cleaning.  
5.5 The ability to directly compare test results will vary by many factors including test specimen size and whether test specimens are individual building materials or composite assemblies of building materials.
SCOPE
1.1 This test method is intended to apply to building materials used in construction below the base flood elevation (BFE) including, but not limited to: individual building materials and composite assemblies of building materials that constitute permanent integral parts of a finished building including walls, floors, ceilings, stairways, built-in partitions, finishes, cladding, and other similarly incorporated architectural and structural items.  
1.2 Requirements for evaluation of other hazards associated with flood damage including, but not limited to: debris impact, flood velocity, wave action, water pressure differential, scour, erosion, biological and chemical contaminants in floodwater, and other factors that would be adverse to continued use of the structure for its intended purpose including long-term occupant health impacts are outside of the scope of the methods presented herein.  
1.3 The water immersion, drying, and cleaning procedures specified in this test method establishes standard conditions for laboratory evaluation of test specimen response to water immersion, subsequent drying, and cleaning. The results of these tests are one factor in assessing the characteristics of building materials with regard to water immersion, drying, and ability to be cleaned. Application of these test results to predict these characteristics for actual building construction requires the evaluation of test conditions as compared to conditions of end-use.  
1.4 The water immersion and drying procedures shall not be construed as representative of water makeup, duration of immersion, or conditions of drying during an actual flood event because actual flood conditions vary with such factors as makeup of water, depth and duration of immersion, and ambient temperature and humidity.  
1.5 The cleaning procedures specified in this test method are intended to simulate surface cleaning that normally occurs after flooding.  
1.6 The cleaning procedures specified in this test method shall not be construed as superseding standards or manufacturer’s recommended methods for cleaning and restoration after flooding.  
1.7 A commentary to this test method is provided in Appendix X1.  
1.8 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mat...

  • Standard
    6 pages
    English language

ABSTRACT
This guide provides guidance on conducting seismic risk assessments for buildings. As such, this guide assists a User to assess a property’s potential for losses from earthquake occurrences. Hazards addressed in this guide include earthquake ground shaking, earthquake-caused site instability, including fault rupture, landslides and soil liquefaction, lateral spreading and settlement, and earthquake-caused off-site response impacting the property, including flooding from dam or dike failure, tsunamis and seiches. This guide is intended to reflect a commercially prudent and reasonable investigation for performance of seismic risk assessments. Seismic risk assessments may be performed for an individual building or a group of buildings. This guide provides suggested approaches for the performance of five different types of seismic risk assessments. Building stability, site stability, building damageability, contents damageability, business interruption, and application and temporal relevance of report. Each is intended to serve different financial and management needs of the User. An earthquake ground motion assessment should be conducted in conjuction with probable loss evaluations for building damageability and may have applications in some scenario loss studies, as well as building stability or site stability assessments. Seismic risk assessments may consider varying degrees of assessment of a building or buildings from Level 0 to Level 3.
SIGNIFICANCE AND USE
4.1 Uses—This Guide is intended for use on a voluntary basis by parties such as lenders, loan servicers, insurers and equity investors in real estate (Users) who wish to estimate possible earthquake losses to buildings. This guide outlines procedures for conducting a seismic risk assessment for a specific User considering the User's requirements for due diligence. The specific purpose of this guide is to provide Users with seismic risk assessment during the anticipated term for holding either the mortgage or the deed. A seismic risk assessment prepared in accordance with this guide should reference or state that the guidance in this document was used as a basis for the report and should also identify any deviations from the guidelines. This guide is intended to reflect a commercially prudent and reasonable investigation for performance of seismic risk assessments.  
4.1.1 Users—This Guide is designed to assist the User in developing information about the earthquake-related damage potential of a building, or groups of buildings.
4.1.1.1 Use of this guide may permit a User to satisfy, in part, their requirements for due diligence in assessing a building’s potential for losses associated with earthquakes for real estate transactions.  
4.1.2 Types of Investigations—This guide provides suggested approaches for the performance of five different types of assessments. Each is intended to serve different financial and management needs of the User. Several of these types of assessment specifically depend on characterization of the earthquake ground motion as given in Section 7.
4.1.2.1 Building Stability (BS)—Assessment of whether the building will maintain vertical load-carrying capacity in whole or in part during considered earthquake ground motions (see Section 8).
4.1.2.2 Site Stability (SS)—Assessment of the likelihood that the site will remain stable in earthquakes and is not subject to failure through faulting, soil liquefaction, landslide, or other site respo...
SCOPE
1.1 This guide provides guidance on conducting seismic risk assessments for buildings. As such, this guide assists a User to assess a property's potential for losses from earthquake occurrences.  
1.1.1 Hazards addressed in this guide include:
1.1.1.1 Earthquake ground shaking,
1.1.1.2 Earthquake-caused site instability, including fault rupture, landslides, soil liquefaction, lateral spreading and settlement, and
1.1.1.3 Earthquake-caused off-site response impacting ...

  • Guide
    18 pages
    English language
  • Guide
    18 pages
    English language

SIGNIFICANCE AND USE
5.1 This practice is intended for use as a voluntary standard by parties who wish to undertake the seismic risk assessment of properties. The goal is for users to objectively and reliably compare the financial risks of earthquake damage to buildings, or groups of buildings, on a consistent basis.  
5.2 This practice is designed to provide requirements for the evaluation of earthquake damage risk so that technical reports prepared for the evaluation and rating of seismic risk of a building(s) will be adequate for use by other entities. Potential users including, but are not be limited to, those making equity investments, lending, and financial transactions, including securitized mortgage lending by mortgage originators, loan servicers, underwriters, rating agencies, and purchasers of bonds secured by the real estate.  
5.3 The use of this practice may permit a user to satisfy, in part, their requirements for due diligence in assessing a property's potential for losses associated with earthquakes for real estate transactions.
SCOPE
1.1 This practice establishes standard-of-care for evaluation and classification of the financial risks from earthquake damage to real estate improvements for use in financial mortgage transactions and capital investment evaluation. As such, this practice permits a user to satisfy, in part, their real estate transaction due-diligence requirements with respect to assessing and characterizing a property’s potential losses from earthquakes. This practice is intended to address only physical damage to the property from site and building response.  
1.1.1 Hazards addressed in this practice include earthquake ground shaking, earthquake-caused site instability, including faulting, subsidence, settlement landslides and soil liquefaction, earthquake-caused tsunamis and seiches, and earthquake-caused flooding from dam or dike failures.  
1.1.2 Earthquake-caused fires and toxic materials releases are not hazards considered in this practice.  
1.1.3 This practice does not purport to provide for the preservation of life safety, or prevention of building damage associated with its use, or both.
1.1.3.1 This practice does not address requirements of any federal, state, or local laws and regulations of building construction or maintenance. Users are cautioned that current federal, state, and local laws and regulations may differ from those in effect at the times of construction or modification of the building(s), or both.
1.1.3.2 This practice does not address the contractual and legal obligations between prior and subsequent Users of seismic risk assessment reports or between providers who prepared the report and those who would like to use such prior reports.
1.1.3.3 This practice does not address the contractual and legal obligations between a provider and a user, and other parties, if any.  
1.1.4 It is the responsibility of the owner of the building(s) to establish appropriate life-safety and damage prevention practices and determine the applicability of current regulatory limitations prior to use.  
1.2 Considerations not included in the scope: the impacts of damage to contents, loss of income(s), rents, or other economic benefits of use of the property, or from legal judgments, fire sprinkler water-induced damage or fire.  
1.3 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.

  • Standard
    8 pages
    English language
  • Standard
    8 pages
    English language

SIGNIFICANCE AND USE
4.1 This practice can be applied to the requirements for facility serviceability of many functional occupant groups, provided that an appropriate set of requirement classifications for each type has been established.  
4.2 This practice can be applied to rating the facility serviceability of a building or building-related facility.  
4.3 This practice can be used to ascertain the requirements of a group or organization at the time when the group (1) needs to ascertain the serviceability of the facility it occupies; (2) is contemplating a move and needs to assess the relative capability of several existing facilities to perform as required, before deciding to rent, lease, or buy; (3) needs to compare its requirements to the serviceability of a facility that is being planned, or is designed but is not yet built; (4) is planning to remodel or rehabilitate the space it occupies and needs to establish the required level of serviceability that the remodeled or rehabilitated facility will have to meet.  
4.4 This practice is not affected by the complexity of the requirement for serviceability.  
4.5 This practice can be used by any individual with sufficient organizational, functional, and technical knowledge of buildings to act as an informed facilitator. The individual charged with the task of leading the process of establishing the functional requirements of an occupant group or organization needs basic facilitation and interviewing skills. The individual charged with rating the serviceability of a building needs sufficient knowledge of buildings to identify the features that are present.  
4.6 This practice provides a means of setting typical required serviceability levels for any serviceability topic, and of comparing the required levels of functionality for one occupant group or organization against levels set by others.  
4.7 This practice provides a means for organizations to set a profile of functional requirements for each type of occupant group within that...
SCOPE
1.1 This practice provides a definitive procedure for setting the level of requirements of the users (functionality) for the functional capability of a building or building-related facility.  
1.2 This practice provides a definitive procedure for rating the level of functional capability (serviceability) provided by an existing building or building-related facility, or to be provided according to the design for one.  
1.3 This practice provides a definitive procedure for creating or adapting a set of classifications for establishing the levels of functionality required of or the level of capability provided by a building or building-related facility.  
1.4 This practice can be used for setting the profile of requirements of an occupant group in an existing building or building-related facility, or of a group planning to move and looking at new accommodations to rent, buy, or build, and it can be used to assess the suitability of their present facilities.  
1.5 This practice can be used for setting the profile of requirements of an owner, facility manager, lender, or other investor.  
1.6 This practice does not specify what would cause a building to be rated at a given level. That information is found in classifications for specific topics of serviceability that contain a set of rating scales.  
1.7 This practice is not intended to be used for regulatory purposes.  
1.8 This practice contains the following information, in the sections indicated:    
Section  
Introduction  
1    
Scope  
1    
Referenced Documents  
2    
Terminology  
3    
Significance and Use  
4    
Essence of the Approach  
5    
Procedure for Setting the Profile of Required Functionality  
6    
Procedure for Setting the Profile of Functional Capability for a Building or for Building-Related Facilities  
7    
Rating the Plans or Proposals for a New Building or for a Remodel or Rehabilitation Project  
8    
Ke...

  • Standard
    17 pages
    English language
  • Standard
    17 pages
    English language

SIGNIFICANCE AND USE
4.1 Each Facility Rating Scale in this classification (see Figs. 1-6) provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability, and to compare that level against the level of any other building or facility.  
4.2 This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.  
4.3 This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility, or within a group of office facilities.  
4.4 This classification can be used to estimate the following:  
4.4.1 Serviceability of an existing facility for uses other than its present use.  
4.4.2 Serviceability (potential) of a facility that has been planned but not yet built.  
4.4.3 Serviceability (potential) of a facility for which a remodeling has been planned.  
4.5 Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology, and the use of instruments, tools, or measurements.  
4.6 This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)
SCOPE
1.1 This classification covers pairs of scales (see Figs. 1-6) for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements for structure and building envelope.
1.2 Within that aspect of serviceability, each pair of scales (see Figs. 1-6) are for classifying one topic of serviceability. Each paragraph in an Occupant Requirement Scale summarizes one level of serviceability on that topic, which occupants might require. The matching entry in the Facility Rating Scale is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.  
1.3 The entries in the Facility Rating Scale (see Figs. 1-6) are indicative and not comprehensive. They are for quick scanning, to estimate approximately, quickly, and economically, how well an office facility is likely to meet the needs of one or another type of occupant group, over time. The entries are not for measuring, knowing, or evaluating how an office facility is performing.  
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.  
1.5 This classification indicates what would cause a facility to be rated at a certain level of serviceability, but does not state how to conduct a serviceability rating nor how to assign a serviceability score. That information is found in Practice E1334. The scales in Figs. 1-6 are complimentary to and compatible with Practice E1334. Each requires the other.  
1.6 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.

  • Standard
    11 pages
    English language
  • Standard
    11 pages
    English language

SCOPE
1.1 This terminology consists of terms and definitions pertaining to the description, measurement, prediction, improvement, and management of buildings and building-related facilities, and, in particular, terms related to the standards generated by ASTM Committee E06 on Performance of Buildings.  
1.2 The purpose of this terminology is to provide meanings and explanations of technical terms, written for both the technical expert and the non-expert user.  
1.3 This terminology is one of a group of special terminologies, subsidiary to the comprehensive Terminology E631.  
1.4 Terms are listed in alphabetical sequence. Compound terms appear in the natural spoken order. Where definitions herein are adopted from other sources, they are copied exactly. The source is identified at the right margin following the definition and is listed in Section 2. The equivalent term in French is listed in parentheses after the English term.

  • Standard
    6 pages
    English language

SIGNIFICANCE AND USE
This practice can be applied to the requirements for serviceability of many functional occupant groups, provided that an appropriate set of requirement classifications for each type has been established.
This practice can be used to ascertain the requirements of a group or organization at the time when the group (1) needs to ascertain the serviceability of the facility it occupies; (2) is contemplating a move and needs to assess the relative capability of several existing facilities to perform as required, before deciding to rent, lease, or buy; (3) needs to compare its requirements to the serviceability of a facility that is being planned, or is designed but is not yet built; (4) is planning to remodel or rehabilitate the space it occupies and needs to establish the required level of serviceability that the remodeled or rehabilitated facility will have to meet.
This practice is not affected by the complexity of the requirement for serviceability.
This practice can be used by any individual with sufficient organizational, functional, and technical knowledge to act as an informed facilitator. The individual charged with the task of leading the process of establishing the serviceability requirements of an occupant group or organization needs basic facilitation and interviewing skills.
This practice provides a means of setting typical required serviceability levels for any serviceability topic, and of comparing the required serviceability levels for one occupant group or organization against levels set by others.
This practice provides a means for organizations to set a profile of requirements for serviceability for each generic type of occupant group within that organization.
This practice enables an organization to compare an occupant's profile to a generic profile rapidly.
This practice provides a means for organizations to identify and validate exceptional needs of their occupants rapidly.
This practice provides a means of comparing the requirement ...
SCOPE
1.1 This practice is a definitive procedure for setting requirements for the serviceability of a building or building-related facility.
1.2 This practice is not intended to be used for regulatory purposes.
1.3 This practice can be used for setting the profile of serviceability requirements of an occupant group in an existing building or building-related facility or of a group planning to move and looking at new accommodations to rent, buy, or build.
1.4 This practice can be used for setting the profile of serviceability requirements of an owner, facility manager, lender, or other investor.
1.5 The process of creating or adapting a set of classifications for establishing the levels of serviceability required by an occupant group or organization is outside the scope of the practice.
1.6 This practice contains the following information, in the sections indicated:
Section   Introduction1  Scope1  Referenced Documents2  Terminology3  Summary of Practice4  Significance and Use5  Procedure6  Keywords7  Example of a Pair of Serviceability Scales for One TopicAppendix X1  Example of Part of a Pair of Matching Profiles Presented as Bar ChartsAppendix X2  Example of Titles of Serviceability Aspects, Topics, and FeaturesAppendix X3  Example of a List of Common Generic Types of FunctionAppendix X4

  • Standard
    9 pages
    English language

SIGNIFICANCE AND USE
Each facility rating scale in this classification provides a means for estimating the level of serviceability of a building or facility for one topic of serviceability, and for comparing that level against the level of any other building or facility.
This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.
This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility, or within a group of office facilities.
This classification can be used to estimate the following: (1) the serviceability of an existing facility for uses other than its present use; (2) the serviceability (potential) of a facility that has been planned but not yet built; and (3) the serviceability (potential) of a facility for which a remodeling has been planned.
The use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology and the use of instruments, tools, or measurements.
This classification applies only to facilities that are building constructions or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)
This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment or fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements to protect occupant assets.
1.2 Each pair of scales, shown in Figs. 1-8, printed side by side on a page, are for classifying one topic of serviceability within that aspect of serviceability. Each paragraph in an Occupant Requirement Scale (see Figs. 1-8) summarizes one level of serviceability on that topic that occupants might require. The matching entry in the Facility Rating Scale (see Figs. 1-8) is a translation of the requirement into a description of certain features of a facility that, taken in combination, indicate that the facility is likely to meet that level of required serviceability.
1.3 The entries in the Facility Rating Scale (see Figs. 1-8) are indicative and not comprehensive. They are for quick scanning, to estimate approximately, rapidly, and economically, how well an office facility is likely to meet the needs of one or another type of occupant group over time. The entries are not for measuring, knowing, and evaluating how an office facility is performing.
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.
1.5 This classification indicates what would cause a facility to be rated at a certain level of serviceability, but it does not state how to conduct a serviceability rating nor how to assign a serviceability score. That information is found in Practice E1334. The scales in this classification are complementary to and compatible with Practice E1334. Each requires the other.
FIG. 1 Scale A.8.1 for Control of Access from Building Public Zone to Occupant Reception Zone
FIG. 1Scale A.8.1 for Control of Access from Building Public Zone to Occupant Reception Zone (continued)
FIG. 2 Scale A.8.2 for Interior Zones of Security
FIG. 2Scale A.8.2 for Interior Zones of Security (continued)
FIG. 3 Scale A.8.3 for Vaults and Secure Rooms
...

  • Standard
    15 pages
    English language

SIGNIFICANCE AND USE
Each Facility Rating Scale (see Figs. 1-6) in this classification provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability and to compare that level against the level of any other building or facility.
This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.
This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility, or within a group of office facilities.
This classification can be used to estimate the following:
Serviceability of an existing facility for uses other than its present use.
Serviceability (potential) of a facility that has been planned but not yet built.
Serviceability (potential) of a facility for which remodeling has been planned.
Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology and the use of instruments, tools, or measurements.
This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)
This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment nor for fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements in support of recruiting and keeping quality employees.
1.2 Within that aspect of serviceability, each pair of scales, shown in Figs. 1-6, are for classifying one topic of serviceability. Each paragraph in an Occupant Requirement Scale (see Figs. 1-6) summarizes one level of serviceability on that topic, which occupants might require. The matching entry in the Facility Rating Scale (see Figs. 1-6) is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.
1.3 The entries in the Facility Rating Scale (see Figs. 1-6) are indicative and not comprehensive. They are for quick scanning to estimate approximately, quickly, and economically, how well an office facility is likely to meet the needs of one or another type of occupant group over time. The entries are not for measuring, knowing, or evaluating how an office facility is performing.
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.
1.5 This classification indicates what would cause a facility to be rated at a certain level of serviceability but does not state how to conduct a serviceability rating nor how to assign a serviceability score. That information is found in Practice E1334. The scales in this classification are complimentary to and compatible with Practice E1334. Each requires the other.
FIG. 1 Scale A.12.1 for Food
FIG. 1 Scale A.12.1 for Food (continued)
FIG. 2 Scale A.12.2 for Shops
FIG. 3 Scale A.12.3 for Daycare
FIG. 4 Scale A.12.4 for Exercise Room
FIG. 5 Scale A.12.5 for Bicycle Racks for Staff
FIG. 6 Scale A.12.6 for Seating Away from Work Areas
FIG. 6 Scale A.12.6 for Seating Away from Work Areas (continued)

  • Standard
    9 pages
    English language

SIGNIFICANCE AND USE
Each Facility Rating Scale (see Figs. 1-5) in this classification provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability and to compare that level against the level of any other building or facility.
This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.
This classification can be used to estimate the following:
Serviceability of an existing facility for uses other than its present use.
Serviceability (potential) of a facility that has been planned but not yet built.
Serviceability (potential) of a facility for which remodeling has been planned.
Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology and the use of instruments, tools, or measurements.
This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)
This classification is not intended for, and is not suitable for, use for regulatory purposes nor for fire hazard assessment nor for fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements for cleanliness.
1.2 Within that aspect of serviceability, each pair of scales, shown in Figs. 1-5, are for classifying one topic of serviceability. Each paragraph in an Occupant Requirement Scale (see Figs. 1-5) summarizes one level of serviceability on that topic, which occupants might require. The matching entry in the Facility Rating Scale (see Figs. 1-5) is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.
1.3 The entries in the Facility Rating Scale (see Figs. 1-5) are indicative and not comprehensive. They are for quick scanning and rating a facility and not for evaluating or diagnosing it.
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.
1.5 This classification indicates what would cause a facility to be rated at a certain level of serviceability but does not state how to conduct a serviceability rating nor how to assign a serviceability score. That information is found in Practice E1334. The scales in this classification are complimentary to and compatible with Practice E1334. Each requires the other.
FIG. 1 Scale B.4.1 for Exterior and Public Areas
FIG. 1 Scale B.4.1 for Exterior and Public Areas (continued)
FIG. 2 Scale B.4.2 for Office Areas (Interior)
FIG. 3 Scale B.4.3 for Toilets and Washrooms
FIG. 4 Scale B.4.4 for Special Cleaning
FIG. 5 Scale B.4.5 for Waste Disposal for Building
FIG. 5 Scale B.4.5 for Waste Disposal for Building (continued)

  • Standard
    8 pages
    English language

SIGNIFICANCE AND USE
Each Facility Rating Scale (see Figs. 1-4) in this classification provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability and to compare that level against the level of any other building or facility.
This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.
This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility, or within a group of office facilities.
This classification can be used to estimate the following:
Serviceability of an existing facility for uses other than its present use.
Serviceability (potential) of a facility that has been planned but not yet built.
Serviceability (potential) of a facility for which a remodeling has been planned.
Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology and the use of instruments, tools, or measurements.
This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)
This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment nor for fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements to enable work groups or project groups to function effectively and productively.
1.2 Within that aspect of serviceability, each pair of scales, shown in Figs. 1-4, are for classifying one topic of serviceability. Each paragraph in an Occupant Requirement Scale (see Figs. 1-4) summarizes one level of serviceability on that topic, which occupants might require. The matching entry in the Facility Rating Scale (see Figs. 1-4) is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.
1.3 The entries in the Facility Rating Scale (see Figs. 1-4) are indicative and not comprehensive. They are for quick scanning to estimate approximately, quickly, and economically, how well an office facility is likely to meet the needs of one or another type of occupant group over time. The entries are not for measuring, knowing, or evaluating how an office facility is performing.
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.
1.5 This classification indicates what would cause a facility to be rated at a certain level of serviceability but does not state how to conduct a serviceability rating nor how to assign a serviceability score. That information is found in Practice E1334. The scales in this classification are complimentary to and compatible with Practice E1334. Each requires the other.
FIG. 1 Scale A.2.1 for Meeting and Conference Rooms
FIG. 1Scale A.2.1 for Meeting and Conference Rooms (continued)
FIG. 1Scale A.2.1 for Meeting and Conference Rooms (continued)
FIG. 2 Scale A.2.2 for Informal Meetings and Interaction
FIG. 2Scale A.2.2 for Informal Meetings and Interaction (continued)
FIG. 3 Scale A.2.3 for Group Layout and Ter...

  • Standard
    12 pages
    English language

SIGNIFICANCE AND USE
Each facility rating scale in this classification (see Figs. 1-8) provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability, and to compare that level against the level of any other building or facility.
This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such aslocation, structure, mechanical systems, age, and building shape.
This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility, or within a group of office facilities.
This classification can be used to estimate the following:
Serviceability of an existing facility for uses other than its present use.
Serviceability (potential) of a facility that has been planned but not yet built.
Serviceability (potential) of a facility for which a remodeling has been planned.
Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology, and the use of instruments, tools, or measurements.
This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)
This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment nor fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales (see Figs. 1-8) for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements for manageability.
1.2 Within that aspect of serviceability, each pair of scales (see Figs. 1-8) are for classifying one topic of serviceability. Each paragraph in an Occupant Requirement Scale summarizes one level of serviceability on that topic, which occupants might require. The matching entry in the facility rating scale is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.
1.3 The entries in the Facility Rating Scale (see Figs. 1-8) are indicative and not comprehensive. They are for quick scanning, to estimate approximately, quickly, and economically, how well an office facility is likely to meet the needs of one or another type of occupant group, over time. The entries are not for measuring, knowing, or evaluating how an office facility is performing.
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.
1.5 This classification indicates what would cause a facility to be rated at a certain level of serviceability, but does not state how to conduct a serviceability rating nor how to assign a serviceability score. That information is found in Practice E1334. The scales in Figs. 1-8 are complimentary to and compatible with Practice E1334. Each requires the other.  
TABLE 1 Anticipated Remaining Service LifeA  CountBRemaining Useful Life at Least: Equal to 3 = Building envelope: seals, joints = 10 years or more  4 = Roofing and flashing = 15 years or more  5 = HVAC prime movers and main systems = 20 years or more  3 = HVAC secondary distrib., for example, small fans = 10 years or more  4 = HVAC controls = 10 years or more  3 = Elevators and escalators = 20 years or more  4 = Ceiling systems, including fixtures = 15 yea...

  • Standard
    15 pages
    English language

SIGNIFICANCE AND USE
Each Facility Rating Scale (see Figs. 1-6) in this classification provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability and to compare that level against the level of any other building or facility.
This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.
This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility, or within a group of office facilities.
This classification can be used to estimate the following:
Serviceability of an existing facility for uses other than its present use.
Serviceability (potential) of a facility that has been planned but not yet built.
Serviceability (potential) of a facility for which remodeling has been planned.
Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology and the use of instruments, tools, or measurements.
This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)
This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment nor for fire risk assessment.
SCOPE
1.1 This classification contains pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements for locating the building and finding the way inside the building.
1.2 Within that aspect of serviceability, each pair of scales, shown in Figs. 1-6, are for classifying one topic of serviceability. Each paragraph in an Occupant Requirement Scale (see Figs. 1-6) summarizes one level of serviceability on that topic, which occupants might require. The matching entry in the Facility Rating Scale (see Figs. 1-6) is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.
1.3 The entries in the Facility Rating Scale (see Figs. 1-6) are indicative and not comprehensive. They are for quick scanning to estimate approximately, quickly, and economically, how well an office facility is likely to meet the needs of one or another type of occupant group over time. The entries are not for measuring, knowing, or evaluating how an office facility is performing.
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.
1.5 This classification indicates what would cause a facility to be rated at a certain level of serviceability but does not state how to conduct a serviceability rating nor how to assign a serviceability score. That information is found in Practice E2334. The scales in this classification are complimentary to and compatible with Practice E2334. Each requires the other.
FIG. 1 Scale A.14.1 for Public Transportation (Urban Sites)
FIG. 2 Scale A.14.2 for Staff Visits to Other Offices
FIG. 3 Scale A.14.3 for Vehicular Entry and Parking
FIG. 3Scale A.14.3 for Vehicular Entry and Parking  (continued)
FIG. 4 Scale A.14.4 for Wayfinding to Building and Lobby
FIG. 4Scale A.14.4 for Wayfinding to Building and Lobby (continued)
F...

  • Standard
    12 pages
    English language

SIGNIFICANCE AND USE
Each Facility Rating Scale (see Figs. 1-7) in this classification provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability and to compare that level against the level of any other building or facility.
This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.
This classification can be used to estimate the amount of variance of serviceability from target or from requirement for a single office facility or within a group of office facilities.
This classification can be used to estimate the following:
Serviceability of an existing facility for uses other than its present use.
Serviceability (potential) of a facility that has been planned but not yet built.
Serviceability (potential) of a facility for which remodeling has been planned.
Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology and the use of instruments, tools, or measurements.
This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)
This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment nor for fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements for image to the public and occupants.
1.2 Within that aspect of serviceability, each pair of scales, shown in Figs. 1-7, are for classifying one topic of serviceability. Each paragraph in an Occupant Requirement Scale (see Figs. 1-7) summarizes one level of serviceability on that topic, which occupants might require. The matching entry in the Facility Rating Scale (see Figs. 1-7) is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.
1.3 The entries in the Facility Rating Scale (see Figs. 1-7) are indicative and not comprehensive. They are for quick scanning to estimate approximately, quickly, and economically, how well an office facility is likely to meet the needs of one or another type of occupant group over time. The entries are not for measuring, knowing, or evaluating how an office facility is performing.
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.
1.5 This classification indicates what would cause a facility to be rated at a certain level of serviceability but does not state how to conduct a serviceability rating nor how to assign a serviceability score. That information is found in Practice E1334. The scales in this classification are complimentary to and compatible with Practice E1334. Each requires the other.
FIG. 1 Scale A.11.1 for Exterior Appearance
FIG. 1Scale A.11.1 for Exterior Appearance (continued)
FIG. 2 Scale A.11.2 for Public Lobby of Building
FIG. 2Scale A.11.2 for Public Lobby of Building (continued)
FIG. 3 Scale A.11.3 for Public Spaces Within the Building
FIG. 3Scale A.11.3 for Public Spaces Within the Building (continued)
FIG. 4 Scale A.11.4 for Appearance and Spaciousness of...

  • Standard
    14 pages
    English language

SIGNIFICANCE AND USE
Each Facility Rating Scale (see Figs. 2-7) in this classification provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability and to compare that level against the level of any other building or facility.
This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.
This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility, or within a group of office facilities.
This classification can be used to estimate the following:
Serviceability of an existing facility for uses other than its present use.
Serviceability (potential) of a facility that has been planned but not yet built.
Serviceability (potential) of a facility for which remodeling has been planned.
Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology and the use of instruments, tools, or measurements.
This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)
This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment nor for fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements for protection of a building or site.
1.2 Within that aspect of serviceability, each pair of scales, shown in Figs. 2-7, are for classifying one topic of serviceability. Each paragraph in an Occupant Requirement Scale (see Figs. 2-7) summarizes one level of serviceability on that topic, which occupants might require. The matching entry in the Facility Rating Scale (see Figs. 2-7) is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.
1.3 The entries in the Facility Rating Scale (see Figs. 2-7) are indicative and not comprehensive. They are for quick scanning to estimate approximately, quickly, and economically, how well an office facility is likely to meet the needs of one or another type of occupant group over time. The entries are not for measuring, knowing, or evaluating how an office facility is performing.
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.
1.5 This classification indicates what would cause a facility to be rated at a certain level of serviceability but does not state how to conduct a serviceability rating nor how to assign a serviceability score. That information is found in Practice E1334. The scales in this classification are complimentary to and compatible with Practice E1334. Each requires the other.
FIG. 1 Zones of Physical Security
FIG. 2 Scale A.9.1 for Protection Around Building
FIG. 2Scale A.9.1 for Protection Around Building (continued)
FIG. 3 Scale A.9.2 for Protection from Unauthorized Access to Site and Parking
FIG. 3Scale A.9.2 for Protection from Unauthorized Access to Site and Parking (continued)
FIG. 4 Scale A.9.3 for Protective Surveillance of Site
FIG. 4Scale A.9.3 for Protective Surv...

  • Standard
    14 pages
    English language

SIGNIFICANCE AND USE
Each Facility Rating Scale (see Figs. 1-4) in this classification provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability and to compare that level against the level of any other building or facility.
This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.
This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility, or within a group of office facilities.
This classification can be used to estimate the following:
Serviceability of an existing facility for uses other than its present use.
Serviceability (potential) of a facility that has been planned but not yet built.
Serviceability (potential) of a facility for which remodeling has been planned.
Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology and the use of instruments, tools, or measurements.
This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)
This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment nor for fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements to be able to do normal office tasks outside scheduled hours.
1.2 Within that aspect of serviceability, each pair of scales, shown in Figs. 1-4, are for classifying one topic of serviceability. Each paragraph in an Occupant Requirement Scale (see Figs. 1-4) summarizes one level of serviceability on that topic, which occupants might require. The matching entry in the Facility Rating Scale (see Figs. 1-4) is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.
1.3 The entries in the Facility Rating Scale (see Figs. 1-4) are indicative and not comprehensive. They are for quick scanning to estimate approximately, quickly, and economically, how well an office facility is likely to meet the needs of one or another type of occupant group over time. The entries are not for measuring, knowing, or evaluating how an office facility is performing.
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.
1.5 This classification indicates what would cause a facility to be rated at a certain level of serviceability, but does not state how to conduct a serviceability rating nor how to assign a serviceability score. That information is found in Practice E1334. The scales in this classification are complimentary to and compatible with Practice E1334. Each requires the other.
FIG. 1 Scale A.10.1 for Operation Outside Normal Hours
FIG. 1Scale A.10.1 for Operation Outside Normal Hours (continued)
FIG. 2 Scale A.10.2 for Support After Hours
FIG. 2Scale A.10.2 for Support After Hours (continued)
FIG. 3 Scale A.10.3 for Temporary Loss of External Services
FIG. 3Scale A.10.3 for Temporary Loss of External Services (continued)
FIG. 4 Scale...

  • Standard
    10 pages
    English language

SIGNIFICANCE AND USE
Each Facility Rating Scale in this classification provides a means for estimating the level of serviceability of a building or facility for one topic of serviceability, and for comparing that level against the level of any other building or facility.
This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.
This classification can be used to estimate the amount of variance of serviceability from target or from requirement for a single office facility or within a group of office facilities.
This classification can be used to estimate the following: (1) the serviceability of an existing facility for uses other than its present use; (2) the serviceability (potential) of a facility that has been planned but not yet built; and (3) the serviceability (potential) of a facility for which a remodelling has been planned.
The use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires special expertise in building engineering or technology and the use of instruments, tools, or measurements.
This classification applies only to facilities that are building constructions or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)
This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment or fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements to accommodate changes in working method, and frequent relocations of staff, and realignment of workstations.
1.2 Each pair of scales shown in Figs. 1-5, printed side by side on a page, are for classifying one topic of serviceability within that aspect of serviceability. Each paragraph in an Occupant Requirement Scale (see Figs. 1-5) summarizes one level of serviceability on that topic that occupants might require. The matching entry in the Facility Rating Scale (see) is a translation of the requirement into a description of certain features of a facility that, taken in combination, indicate that the facility is likely to meet that level of required serviceability.
1.3 The entries in the Facility Rating Scale (see Figs. 1-5) are indicative and not comprehensive. They are for quick scanning, to estimate approximately, quickly, and economically how well an office facility is likely to meet the needs of one or another type of occupant group over time. The entries are not for measuring, knowing, and evaluating how an office facility is performing.
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.
1.5 This classification indicates what would cause a facility to be rated at a certain level of serviceability, but it does not state how to conduct a serviceability rating or how to assign a serviceability score. That information is found in Practice E1334. The scales in this classification are complementary to and compatible with Practice E1334. Each requires the other.
FIG. 1 Scale A.6.1 for Disruption Due to Physical Change
FIG. 1Scale A.6.1 for Disruption Due to Physical Change (continued)
FIG. 2 Scale A.6.2 for Illumination, HVAC, and Sprinklers
FIG. 2Scale A.6.2 for Illumination, HVAC, and Sprinklers (continued)
FIG. 3 Scale A.6.3 for Minor Changes to L...

  • Standard
    11 pages
    English language

SIGNIFICANCE AND USE
Each Occupant Requirement Scale (see Figs. 1-5) in this classification provides a means to set the required level of serviceability of a building or facility for one topic of serviceability and to compare that level against any level of any other occupant, or of any building or facility.
Each Facility Rating Scale (see Figs. 1-5) in this classification provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability and to compare that level against any level of requirement of any occupant, or of any other building or facility.
This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.
This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility, or within a group of office facilities.
This classification can be used to estimate the following:
Serviceability of an existing facility for uses other than its present use.
Serviceability (potential) of a facility that has been planned but not yet built.
Serviceability (potential) of a facility for which remodeling has been planned.
Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology, and the use of instruments, tools, or measurements.
This classification applies only to facilities that are building constructions, or part thereof. (While classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification. See discussion under definition 3.1.1.)
This classification is not intended for, and is not suitable for, use for regulatory purposes nor for f...
SCOPE
1.1 This classification contains pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements for suitable thermal environment and indoor air conditions.
1.2 Within this aspect of serviceability, each pair of scales, shown in Figs. 1-5 , is for classifying one topic of serviceability. Each paragraph in an Occupant Requirement Scale (see Figs. 1-5) summarizes one level of requirement for serviceability on that topic, which occupants might require. The matching paragraph in the Facility Rating Scale (see Figs. 1-5) is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.
1.3 The paragraphs in the Facility Rating Scale (see Figs. 1-5) are indicative and not comprehensive. They are for quick scanning to estimate approximately, quickly, and economically how well a facility is likely to meet the needs of one or another type of occupant group over time. The paragraphs are not for measuring, knowing, or evaluating how an office facility is performing.
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which schematic or preliminary drawings and outline specifications have been prepared.
1.5 This standard indicates what would cause a facility to be rated (classified) at a certain level of serviceability but does not state how to conduct a serviceability rating or how to assign a serviceability score. That information is found in Practice E1334. The scales in this classification are complimentary to and compatible with Practice E1334. Each requires the other.
1.6 This standard indicates what would caus...

  • Standard
    14 pages
    English language

SIGNIFICANCE AND USE
Each Facility Rating Scale (see Fig. 1 through Fig. 6) in this classification provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability and to compare that level against the level of any other building or facility.
This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.
This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility, or within a group of office facilities.
This classification can be used to estimate the following:
Serviceability of an existing facility for uses other than its present use.
Serviceability (potential) of a facility that has been planned but not yet built.
Serviceability (potential) of a facility for which remodeling has been planned.
Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology and the use of instruments, tools, or measurements.
This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)
This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment nor for fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements for performance to support typical office work.
1.2 Within that aspect of serviceability, each pair of scales, shown in Fig. 1 through Fig. 6, are for classifying one topic of serviceability. Each paragraph in an Occupant Requirement Scale (see Fig. 1 through Fig. 6) summarizes one level of serviceability on that topic, which occupants might require. The matching entry in the Facility Rating Scale (see Fig. 1 through Fig. 6) is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.
1.3 The entries in the Facility Rating Scale (see Fig. 1 through Fig. 6) are indicative and not comprehensive. They are for quick scanning to estimate approximately, quickly, and economically, how well an office facility is likely to meet the needs of one or another type of occupant group over time. The entries are not for measuring, knowing, or evaluating how an office facility is performing.
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.
1.5 This classification indicates what would cause a facility to be rated at a certain level of serviceability but does not state how to conduct a serviceability rating nor how to assign a serviceability score. That information is found in Practice E1334. The scales in this classification are complimentary to and compatible with Practice E1334. Each requires the other.
FIG. 1 Scale A.1.1 for Photocopying
FIG. 1Scale A.1.1 for Photocopying (continued)
FIG. 1Scale A.1.1 for Photocopying  (continued)
FIG. 2 Scale A.1.2 for Training Rooms, General
FIG. 2Scale A.1.2 for Training Rooms, General (continued)
FIG. 2Scale A.1.2 for Training Rooms, General (continued)
FIG. 3 Scale A.1.3 for ...

  • Standard
    16 pages
    English language

SIGNIFICANCE AND USE
Each Facility Rating Scale (see Figs. 1-3) in this classification provides a means to estimate the level of serviceability of a building or facility for one topic of serviceability and to compare that level against the level of any other building or facility.
This classification can be used for comparing how well different buildings or facilities meet a particular requirement for serviceability. It is applicable despite differences such as location, structure, mechanical systems, age, and building shape.
This classification can be used to estimate the amount of variance of serviceability from target or from requirement, for a single office facility or within a group of office facilities.
This classification can be used to estimate the following:
Serviceability of an existing facility for uses other than its present use.
Serviceability (potential) of a facility that has been planned but not yet built.
Serviceability (potential) of a facility for which remodeling has been planned.
Use of this classification does not result in building evaluation or diagnosis. Building evaluation or diagnosis generally requires a special expertise in building engineering or technology and the use of instruments, tools, or measurements.
This classification applies only to facilities that are building constructions, or parts thereof. (While this classification may be useful in rating the serviceability of facilities that are not building constructions, such facilities are outside the scope of this classification.)
This classification is not intended for, and is not suitable for, use for regulatory purposes, nor for fire hazard assessment nor for fire risk assessment.
SCOPE
1.1 This classification covers pairs of scales for classifying an aspect of the serviceability of an office facility, that is, the capability of an office facility to meet certain possible requirements for layout and building factors.
1.2 Within that aspect of serviceability, each pair of scales, shown in Figs. 1-3, are for classifying one topic of serviceability. Each paragraph in an Occupant Requirement Scale (see Figs. 1-3) summarizes one level of serviceability on that topic, which occupants might require. The matching entry in the Facility Rating Scale (see Figs. 1-3) is a translation of the requirement into a description of certain features of a facility which, taken in combination, indicate that the facility is likely to meet that level of required serviceability.
1.3 The entries in the Facility Rating Scale (see Figs. 1-3) are indicative and not comprehensive. They are for quick scanning to estimate approximately, quickly, and economically, how well an office facility is likely to meet the needs of one or another type of occupant group over time. The entries are not for measuring, knowing, or evaluating how an office facility is performing.
1.4 This classification can be used to estimate the level of serviceability of an existing facility. It can also be used to estimate the serviceability of a facility that has been planned but not yet built, such as one for which single-line drawings and outline specifications have been prepared.
1.5 This classification indicates what would cause a facility to be rated at a certain level of serviceability but does not state how to conduct a serviceability rating nor how to assign a serviceability score. That information is found in Practice E1334. The scales in this classification are complimentary to and compatible with Practice E1334. Each requires the other.
FIG. 1 Scale A.7.1 for Influence of HVAC on Layout
FIG. 1Scale A.7.1 for Influence of HVAC on Layout (continued)
FIG. 2 Scale A.7.2 for the Influence of Sound and Visual Factors on Layout
FIG. 2Scale A.7.2 for the Influence of Sound and Visual Factors on Layout (continued)
FIG. 3 Scale A.7.3 for the Influence of Building Loss Factors on Space Needs

  • Standard
    10 pages
    English language

Frequently Asked Questions

E06.25 is a Technical Committee within ASTM International. It is named "Whole Buildings and Facilities". This committee has published 124 standards.

E06.25 develops ASTM standards in the area of Information technology. Currently, there are 124 published standards from this technical committee.

ASTM is a standardization organization that develops and publishes standards to support industry, commerce, and regulatory requirements.

A Technical Committee (TC) in ASTM is a group of experts responsible for developing international standards in a specific technical area. TCs are composed of national member body delegates and work through consensus to create standards that meet global industry needs. Each TC may have subcommittees (SCs) and working groups (WGs) for specialized topics.