ASTM F1802-04(2010)
(Test Method)Standard Test Method for Performance Testing of Excess Flow Valves
Standard Test Method for Performance Testing of Excess Flow Valves
SIGNIFICANCE AND USE
This test method is intended to be used for the evaluation of EFVs manufactured for use on residential and small commercial thermoplastic natural gas service lines. Possible applications of the test include product design and quality control testing by a manufacturer and product acceptance testing by a natural gas utility.
The user of this test method should be aware that the flows and pressures measured in the test apparatus may not correlate well with those measured in a field installation. Therefore, the user should conduct sufficient tests to ensure that any specific EFV will carry out its intended function in the actual field installation used.
SCOPE
1.1 This test method covers a standardized method to determine the performance of excess flow valves (EFVs) designed to limit flow or stop flow in thermoplastic natural gas service lines.
1.2 All tests are intended to be performed using air as the test fluid. Unless otherwise stated, all flow rates are reported in standard cubic feet per hour of 0.6 relative density natural gas.
1.3 The test method recognizes two types of EFV. One type, an excess flow valve-bypass (EFVB), allows a small amount of gas to bleed through (bypass) after it has tripped, usually as a means of automatically resetting the device. The second type, an excess flow valve-non bypass (EFVNB), is intended to trip shut forming an essentially gas tight seal.
1.4 The performance characteristics covered in this test method include flow at trip point, pressure drop across the EFV, bypass flow rate of the EFVB or leak rate through the EFVNB after trip, and verification that the EFV can be reset.
1.4.1 Gas distribution systems may contain condensates and particulates such as organic matter, sand, dirt, and iron compounds. Field experience has shown that the operating characteristics of some EFVs may be affected by accumulations of these materials. The tests of Section 11 were developed to provide a simple, inexpensive, reproducible test that quantifies the effect, if any, of a uniform coating of kerosene and of kerosene contaminated with a specified amount of ferric oxide powder on an EFV's operating characteristics.
1.5 Excess flow valves covered by this test method will normally have the following characteristics: a pressure rating of up to 125 psig (0.86 MPa); a trip flow of between 200 and 2500 ft3/h (5.66 and 70.8 m3/h) at 10 psig (0.07 MPa); a minimum temperature rating of 0°F(–18°C), and a maximum temperature rating of 100°F (38°C).
1.6 The EFVs covered by this test method shall be constructed to fit piping systems no smaller than 1/2CTS and no larger than 11/4IPS, including both pipe and tubing sizes.
1.7 Tests will be performed at 67 ± 10°F (19.4 ± 5.5°C). Alternative optional test temperatures are 100 ± 10°F (37.7 ± 5.5°C) and 0 ± 10°F (–18 ± 5.5°C). All flow rates must be corrected to standard conditions.
1.8 This test method was written for EFVs installed in thermoplastic piping systems. However, it is expected that the test method may also be used for similar devices in other piping systems.
1.9 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.10 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific precautions, see Section 8.
General Information
Relations
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: F1802 − 04(Reapproved 2010)
Standard Test Method for
1
Performance Testing of Excess Flow Valves
This standard is issued under the fixed designation F1802; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
3 3
1. Scope 2500 ft /h (5.66 and 70.8 m /h) at 10 psig (0.07 MPa); a
minimum temperature rating of 0°F(–18°C), and a maximum
1.1 This test method covers a standardized method to
temperature rating of 100°F (38°C).
determine the performance of excess flow valves (EFVs)
designed to limit flow or stop flow in thermoplastic natural gas
1.6 The EFVs covered by this test method shall be con-
2
1
service lines.
structed to fit piping systems no smaller than ⁄2 CTS and no
1
larger than 1 ⁄4 IPS, including both pipe and tubing sizes.
1.2 All tests are intended to be performed using air as the
test fluid. Unless otherwise stated, all flow rates are reported in
1.7 Tests will be performed at 67 6 10°F (19.4 6 5.5°C).
standard cubic feet per hour of 0.6 relative density natural gas.
Alternative optional test temperatures are 100 6 10°F (37.7 6
1.3 The test method recognizes two types of EFV. One type, 5.5°C) and 0 6 10°F (–18 6 5.5°C). All flow rates must be
anexcessflowvalve-bypass(EFVB),allowsasmallamountof corrected to standard conditions.
gas to bleed through (bypass) after it has tripped, usually as a
1.8 This test method was written for EFVs installed in
means of automatically resetting the device. The second type,
thermoplastic piping systems. However, it is expected that the
an excess flow valve-non bypass (EFVNB), is intended to trip
test method may also be used for similar devices in other
shut forming an essentially gas tight seal.
piping systems.
1.4 The performance characteristics covered in this test
1.9 The values stated in inch-pound units are to be regarded
method include flow at trip point, pressure drop across the
as standard. The values given in parentheses are mathematical
EFV, bypass flow rate of the EFVB or leak rate through the
conversions to SI units that are provided for information only
EFVNB after trip, and verification that the EFV can be reset.
and are not considered standard.
1.4.1 Gas distribution systems may contain condensates and
particulates such as organic matter, sand, dirt, and iron com-
1.10 This standard does not purport to address all of the
pounds. Field experience has shown that the operating charac-
safety concerns, if any, associated with its use. It is the
teristics of some EFVs may be affected by accumulations of
responsibility of the user of this standard to establish appro-
these materials. The tests of Section 11 were developed to
priate safety and health practices and determine the applica-
provide a simple, inexpensive, reproducible test that quantifies
bility of regulatory limitations prior to use. For specific
the effect, if any, of a uniform coating of kerosene and of
precautions, see Section 8.
kerosene contaminated with a specified amount of ferric oxide
powder on an EFV’s operating characteristics.
2. Referenced Documents
1.5 Excess flow valves covered by this test method will 3
2.1 ASTM Standards:
normally have the following characteristics: a pressure rating
D1600 TerminologyforAbbreviatedTermsRelatingtoPlas-
of up to 125 psig (0.86 MPa); a trip flow of between 200 and
tics
F412 Terminology Relating to Plastic Piping Systems
2.2 ANSI Standard:
1
This test method is under the jurisdiction of ASTM Committee F17 on Plastic
4
B31.8 Gas Transmission and Distribution Piping Systems
Piping Systems and is the direct responsibility of Subcommittee F17.40 on Test
Methods.
Current edition approved Aug. 1, 2010. Published November 2010. Originally
approved in 1995 as PS 13–95. Last previous edition approved in 2004 as
3
F1804–04. DOI: 10.1520/F1802-04R10. For referenced ASTM standards, visit the ASTM website, www.astm.org, or
2
This contamination test procedure may be utilized to determine the effect, if contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
any, of contaminants from a specific gas distribution system on the operational Standards volume information, refer to the standard’s Document Summary page on
characteristics of an EFV under consideration for use in that system. Condensates, the ASTM website.
4
oils and particulates removed from that distribution system could be substituted for Available fromAmerican National Standards Institute (ANSI), 25 W. 43rd St.,
keroseneandironoxide.Resultsobtainedfromusingreagentsorcontaminantsother 4th Floor, New York, NY 10036.Available from American National Standards
than those specified in this te
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.