Standard Guide for Installation of Flexible Closed Cell Preformed Insulation in Tube and Sheet Form

SIGNIFICANCE AND USE
This guide applies to flexible closed cell insulation tubing and sheet materials manufactured according to Specification C534 and Specification C1427. This standard is intended to provide a basic guide for installing these types of materials.
Confirm application use temperature is consistent with specified use temperature for material as defined in ASTM Specifications unless otherwise agreed upon with the manufacturer. There are different grades for each of the insulation types referred to in this guide, material and grade installed should be that specified.
This guide is not intended to cover all aspects associated with installation for all applications, consult the National, Commercial Industrial Insulation Standards (MICA Manual) or the specific product manufacturer for recommendations, or both. (See ASHRAE Handbook (Fundamentals – Chapter 26) and ASHRAE Handbook (Refrigeration – Chapter 33)
SCOPE
1.1 This guide covers recommended installation techniques for flexible closed cell pre-formed insulation in tube or sheet form. This guide is applicable to materials manufactured in accordance with Specification C534 (Elastomeric based insulation) or Specification C1427 (polyolefin based insulation). The materials covered in this guide encompass a service temperature of -297°F to 300°F ( -183°C to 150 °C) as indicated in the material specifications referenced above. Many of the recommendations made are specific to below ambient applications only.
1.2 The purpose of this guide is to optimize the thermal performance and longevity of installed closed cell flexible insulation systems. By following this guide, the owner, and designer can expect to achieve the energy savings expected and prevention of condensation under the specified design conditions. This document is limited to installation procedures and does not encompass system design.
1.3 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
31-Aug-2011
Technical Committee
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Guide
ASTM C1710-11 - Standard Guide for Installation of Flexible Closed Cell Preformed Insulation in Tube and Sheet Form
English language
9 pages
sale 15% off
Preview
sale 15% off
Preview
Guide
REDLINE ASTM C1710-11 - Standard Guide for Installation of Flexible Closed Cell Preformed Insulation in Tube and Sheet Form
English language
9 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: C1710 − 11
StandardGuide for
Installation of Flexible Closed Cell Preformed Insulation in
1
Tube and Sheet Form
This standard is issued under the fixed designation C1710; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope C534 Specification for Preformed Flexible Elastomeric Cel-
lular Thermal Insulation in Sheet and Tubular Form
1.1 This guide covers recommended installation techniques
C585 Practice for Inner and Outer Diameters of Thermal
for flexible closed cell pre-formed insulation in tube or sheet
Insulation for Nominal Sizes of Pipe and Tubing
form. This guide is applicable to materials manufactured in
C1427 Specification for Extruded Preformed Flexible Cel-
accordance with Specification C534 (Elastomeric based insu-
lular Polyolefin Thermal Insulation in Sheet and Tubular
lation) or Specification C1427 (polyolefin based insulation).
Form
The materials covered in this guide encompass a service
2.2 Other Standards:
temperature of -297°F to 300°F ( -183°C to 150 °C) as
National Commerical, Industrial Insulation Standards
indicatedinthematerialspecificationsreferencedabove.Many
3
(MICA Manual)
of the recommendations made are specific to below ambient
4
ASHRAE Handbook (Fundamentals – Chapter 26)
applications only.
4
ASHRAE Handbook (Refrigeration – Chapter 33)
1.2 The purpose of this guide is to optimize the thermal
3. Terminology
performance and longevity of installed closed cell flexible
insulation systems. By following this guide, the owner, and
3.1 Definitions—C168shallbeconsideredasapplyingtothe
designercanexpecttoachievetheenergysavingsexpectedand
terms in this specification.
prevention of condensation under the specified design condi-
3.2 Definitions of Terms Specific to This Standard:
tions. This document is limited to installation procedures and
3.2.1 seams—Longitudinal or horizontal cross-sections
does not encompass system design.
where insulation meets and must be adhered to itself or other
1.3 The values stated in inch-pound units are to be regarded
system components.
as standard. The values given in parentheses are mathematical
3.2.2 butt joints—Cross-sections where two pieces of tubu-
conversions to SI units that are provided for information only
lar or sheet insulation must be adhered to itself or other system
and are not considered standard.
components.
1.4 This standard does not purport to address all of the
3.2.3 vapor (water) stops—Locations / methods to prevent
safety concerns, if any, associated with its use. It is the
waterorwatervaporfromtravelingintoordownatubularpipe
responsibility of the user of this standard to establish appro-
section.
priate safety and health practices and determine the applica-
3.2.4 sleeving/multi layering—Applying another layer of
bility of regulatory limitations prior to use.
insulation over the first layer. This process is used when the
insulation thickness required is greater than that which is
2. Referenced Documents
commercially available. This technique is also employed when
2
2.1 ASTM Standards:
proper installation practice requires multiple layers and or
C168 Terminology Relating to Thermal Insulation
staggered joint application, even if a single layer thickness is
available.
4. Summary of Guide
1
This guide is under the jurisdiction of ASTM Committee C16 on Thermal
Insulation and is the direct responsibility of Subcommittee C16.40 on Insulation
4.1 Properinsulationthicknessshallbeinstalledasspecified
Systems.
and not compromised. The integrity of the insulation system
Current edition approved Sept. 1, 2011. Published October 2011. Originally
approved in 2009. Last previous edition approved in 2009 as C1710–09.
3
DOI:10.1520/C1710–11. AvailablefromMICA(MidwestInsulationContractorsAssociation)16712Elm
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or Circle, Omaha, NE 68130. http://www.micainsulation.org.
4
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Available from American Society of Heating, Refrigerating, and Air-
Standards volume information, refer to the standard’s Document Summary page on Conditioning Engineers, Inc. (ASHRAE), 1791 Tullie Circle, NE, Atlanta, GA
the ASTM website. 30329, http://www.ashrae.org.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
C1710 − 11
shall be maintained throughout the application. Never pull or insulation envelope. Never stretch insulation to fit. Specified
stretch insulation, always push or over-size insulation. dimensi
...

This document is not anASTM standard and is intended only to provide the user of anASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation:C1710–09 Designation:C1710–11
Standard Guide for
Installation of Flexible Closed Cell Preformed Insulation in
1
Tube and Sheet Form
This standard is issued under the fixed designation C1710; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This guide covers recommended installation techniques for flexible closed cell pre-formed insulation in tube or sheet form.
This guide is applicable to materials manufactured in accordance with Specification C534 (Elastomeric based insulation) or
Specification C1427 (polyolefin based insulation). The materials covered in this guide encompass a service temperature of -297°F
to 300°F ( -183°C to 150 °C) as indicated in the material specifications referenced above. Many of the recommendations made
are specific to below ambient applications only.
1.2 The purpose of this guide is to optimize the thermal performance and longevity of installed closed cell flexible insulation
systems. By following this guide, the owner, and designer can expect to achieve the energy savings expected and prevention of
condensation under the specified design conditions. This document is limited to installation procedures and does not encompass
system design.
1.3 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only and are not considered standard.
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use.
2. Referenced Documents
2
2.1 ASTM Standards:
C168 Terminology Relating to Thermal Insulation
C534 Specification for Preformed Flexible Elastomeric Cellular Thermal Insulation in Sheet and Tubular Form
C585 Practice for Inner and Outer Diameters of Thermal Insulation for Nominal Sizes of Pipe and Tubing
C1427 Specification for Extruded Preformed Flexible Cellular Polyolefin Thermal Insulation in Sheet and Tubular Form
2.2 Other Standards:
3
National Commerical, Industrial Insulation Standards (MICA Manual)
4
ASHRAE Handbook (Fundamentals – Chapter 26)
4
ASHRAE Handbook (Refrigeration – Chapter 33)
3. Terminology
3.1 Definitions:
C168 shall be considered as applying to the terms in this specification.
3.2 Definitions of Terms Specific to This Standard:
3.2.1 seams—Longitudinal or horizontal cross-sections where insulation meets and must be adhered to itself or other system
components.
3.2.2 butt joints—Cross-sections where two pieces of tubular or sheet insulation must be adhered to itself or other system
components.
1
This practiceguide is under the jurisdiction of ASTM Committee C16 on Thermal Insulation and is the direct responsibility of Subcommittee C16.40 on Insulation
Systems.
Current edition approved Nov. 1, 2009. Published December 2009. DOI:10.1520/C1710–09.
Current edition approved Sept. 1, 2011. Published October 2011. Originally approved in 2009. Last previous edition approved in 2009 as C1710–09. DOI:10.1520/
C1710–11.
2
For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
3
Available from MICA (Midwest Insulation Contractors Association) 16712 Elm Circle, Omaha, NE 68130. http://www.micainsulation.org.
4
Available from American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. (ASHRAE), 1791 Tullie Circle, NE, Atlanta, GA 30329,
http://www.ashrae.org.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
C1710–11
3.2.3 vapor (water) stops—Locations / methods to prevent water or water vapor from traveling into or down a tubular pipe
section.
3.2.4 sleeving/multi layering—Applying another layer of insulation over the first layer.This process is used when the insulation
thickness required is greater than that which is commercially available. This technique is also employed when proper installation
practice requires multiple
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.