Standard Practice for Installing Clay Flue Lining

ABSTRACT
This practice covers the minimum requirements for installing clay flue lining for residential concrete or masonry chimneys. Footings shall be constructed of concrete or solid masonry and the foundation shall be placed with respect to adjacent structures to minimize the possibility of damage. Both the concrete footings and foundations shall conform to local building codes. Flue liners shall be installed using refractory mortar in such a manner as to minimize ledges or steps within the flue passageway and shall be surrounded by masonry on all sides with a separation not exceeding the flue liner wall thickness. Materials used for chimney construction shall comprise of the following: flue linings, refractory mortar, concrete block, brick, mortar, firebrick, and natural stone. Chimney connection shall be made by either a metal or clay thimble while the chimney caps shall be made of precast or cast-in-place concrete, metal, or stone caps. Combustible materials shall be permitted to abut the masonry chimney sidewalls; wherein, the minimum air space clearance between the interior or exterior masonry chimneys and the combustible materials shall be met.
SCOPE
1.1 This practice covers the minimum requirements for installing clay flue lining for residential concrete or masonry chimneys.  
1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.  
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
30-Nov-2015
Current Stage
Ref Project

Buy Standard

Standard
ASTM C1283-15 - Standard Practice for Installing Clay Flue Lining
English language
4 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
REDLINE ASTM C1283-15 - Standard Practice for Installing Clay Flue Lining
English language
4 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: C1283 − 15
Standard Practice for
1
Installing Clay Flue Lining
This standard is issued under the fixed designation C1283; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope C652 Specification for Hollow Brick (Hollow Masonry
Units Made From Clay or Shale)
1.1 This practice covers the minimum requirements for
C896 Terminology Relating to Clay Products
installing clay flue lining for residential concrete or masonry
chimneys.
3. Terminology
1.2 The values stated in inch-pound units are to be regarded
3.1 General—Terminology C896 should be used for clari-
as standard. The values given in parentheses are mathematical
fication of definitions in this practice.
conversions to SI units that are provided for information only
and are not considered standard.
3.2 Definitions of Terms Specific to This Standard:
1.3 This standard does not purport to address all of the 3.2.1 chimney connector—tubular unit or pipe used to
safety concerns, if any, associated with its use. It is the convey products of combustion from a heating or cooking
responsibility of the user of this standard to establish appro- appliance to the chimney.
priate safety and health practices and determine the applica-
3.2.2 flue—passageway within a chimney through which
bility of regulatory limitations prior to use.
products of combustion are conveyed.
3.2.3 flue liner—manufactured tubular nonloadbearing fired
2. Referenced Documents
clay unit, normally used for conveying hot gases in chimneys.
2
2.1 ASTM Standards:
3.2.4 masonry chimney—vertical structure constructed of
C24 Test Method for Pyrometric Cone Equivalent (PCE) of
brick, concrete, concrete masonry units, or stone, which
Fireclay and High Alumina Refractory Materials
contains one or more flues, and conveys products of combus-
C27 Classification of Fireclay and High-Alumina Refractory
tion from a heat source or cooking appliance.
Brick
C55 Specification for Concrete Building Brick
3.2.5 smoke chamber—section of a fireplace above the
C90 Specification for Loadbearing Concrete Masonry Units
throat and below the flue, which is an area of transition from
C99 Test Method for Modulus of Rupture of Dimension
the shape of the throat to the shape of the flue.
Stone
3.2.6 thimble—manufactured tubular nonloadbearing fired
C129 Specification for Nonloadbearing Concrete Masonry
clay unit normally used to connect the chimney connector from
Units
an appliance through the wall of the chimney to the flue.
C170 Test Method for Compressive Strength of Dimension
Stone
4. Footings and Foundations
C199 Test Method for Pier Test for Refractory Mortars
C216 Specification for Facing Brick (Solid Masonry Units
4.1 Footings for masonry chimneys shall be constructed of
Made from Clay or Shale)
concrete or solid masonry at least 12 in. (305 mm) thick, and
C270 Specification for Mortar for Unit Masonry
it shall extend at least 6 in. (150 mm) beyond the face of the
C315 Specification for Clay Flue Liners and Chimney Pots
foundation or support wall on all sides. Footings shall be
founded below frost depth on natural undisturbed earth or
engineeredfill.Inareasnotsubjectedtofreezing,footingsshall
1
This practice is under the jurisdiction of ASTM Committee C04 on Vitrified
be founded at least 12 in. (305 mm) below finished grade.
Clay Pipe and is the direct responsibility of Subcommittee C04.20 on Methods of
Test and Specifications. 4.2 The foundation shall be placed, with respect to adjacent
Current edition approved Dec. 1, 2015. Published December 2015. Originally
structures existing or anticipated, to minimize the possibility of
approved in 1994. Last previous edition approved in 2011 as C1283 – 11. DOI:
damage by construction operations or by transmission of
10.1520/C1283-15.
2
additional loads to the supporting soils.
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
4.3 Concrete footings and foundations shall conform to
Standards volume information, refer to the standard’s Document Summary page on
the ASTM website. local building codes.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
C1283 − 15
4.3.1 In the absence of a local building code, concrete with 5.8 When more than one flue is contained in a chimney, a
a minimum 28 day compressive strength of 3000 psi (21 MPa) separation shall be provided between adjacent flues. The
shall be used. separation shall be solid masonry wythes (partitions) not less
tha
...

This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: C1283 − 11 C1283 − 15
Standard Practice for
1
Installing Clay Flue Lining
This standard is issued under the fixed designation C1283; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This practice covers the minimum requirements for installing clay flue lining for residential concrete or masonry chimneys.
1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only and are not considered standard.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use.
2. Referenced Documents
2
2.1 ASTM Standards:
C24 Test Method for Pyrometric Cone Equivalent (PCE) of Fireclay and High Alumina Refractory Materials
C27 Classification of Fireclay and High-Alumina Refractory Brick
C55 Specification for Concrete Building Brick
C90 Specification for Loadbearing Concrete Masonry Units
C99 Test Method for Modulus of Rupture of Dimension Stone
C129 Specification for Nonloadbearing Concrete Masonry Units
C170 Test Method for Compressive Strength of Dimension Stone
C199 Test Method for Pier Test for Refractory Mortars
C216 Specification for Facing Brick (Solid Masonry Units Made from Clay or Shale)
C270 Specification for Mortar for Unit Masonry
C315 Specification for Clay Flue Liners and Chimney Pots
C652 Specification for Hollow Brick (Hollow Masonry Units Made From Clay or Shale)
C896 Terminology Relating to Clay Products
3. Terminology
3.1 General—Terminology C896 should be used for clarification of definitions in this practice.
3.2 Definitions of Terms Specific to This Standard:
3.2.1 chimney connector—tubular unit or pipe used to convey products of combustion from a heating or cooking appliance to
the chimney.
3.2.2 flue—passageway within a chimney through which products of combustion are conveyed.
3.2.3 flue liner—manufactured tubular nonloadbearing fired clay unit, normally used for conveying hot gases in chimneys.
3.2.4 masonry chimney—vertical structure constructed of brick, concrete, concrete masonry units, or stone, which contains one
or more flues, and conveys products of combustion from a heat source or cooking appliance.
3.2.5 smoke chamber—section of a fireplace above the throat and below the flue, which is an area of transition from the shape
of the throat to the shape of the flue.
1
This practice is under the jurisdiction of ASTM Committee C04 on Vitrified Clay Pipe and is the direct responsibility of Subcommittee C04.20 on Methods of Test and
Specifications.
Current edition approved Nov. 1, 2011Dec. 1, 2015. Published November 2011December 2015. Originally approved in 1994. Last previous edition approved in 20072011
as C1283 – 07a.C1283 – 11. DOI: 10.1520/C1283-11.10.1520/C1283-15.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
C1283 − 15
3.2.6 thimble—manufactured tubular nonloadbearing fired clay unit normally used to connect the chimney connector from an
appliance through the wall of the chimney to the flue.
4. Footings and Foundations
4.1 Footings for masonry chimneys shall be constructed of concrete or solid masonry at least 12 in. (305 mm) thick, and it shall
extend at least 6 in. (150 mm) beyond the face of the foundation or support wall on all sides. Footings shall be founded below
frost depth on natural undisturbed earth or engineered fill. In areas not subjected to freezing, footings shall be founded at least 12
in. (305 mm) below finished grade.
4.2 The foundation shall be placed, with respect to adjacent structures existing or anticipated, to minimize the possibility of
damage by construction operations or by transmission of additional loads to the supporting soils.
4.3 Concrete footings and foundations sha
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.