SCOPE
1.1 This specification covers fibrous glass insulation used as a thermal and sound absorbing liner for interior surfaces of ducts, plenums, and other air handling equipment that handle air up to 250°F (121°C).
1.2 The values stated in inch-pound units are the standard. The SI values in parentheses are for information only.
This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
General Information
Relations
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: C 1071 – 05
Standard Specification for
Fibrous Glass Duct Lining Insulation (Thermal and Sound
1
Absorbing Material)
This standard is issued under the fixed designation C 1071; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the Department of Defense.
1. Scope C 665 Specification for Mineral-Fiber Blanket Thermal In-
sulation for Light Frame Construction and Manufactured
1.1 This specification covers fibrous glass insulation used as
Housing
a thermal and sound absorbing liner for interior surfaces of
C 1104/C 1104M Test Method for Determining the Water
ducts, plenums, and other air handling equipment that handle
Vapor Sorption of Unfaced Mineral Fiber Insulation
air up to 250°F (121°C).
C 1114 TestMethodforSteady-StateThermalTransmission
1.2 The values stated in inch-pound units are the standard.
Properties by Means of the Thin-Heater Apparatus
The SI values in parentheses are for information only.
C 1304 Test Method for Assessing the Odor Emission of
1.3 This standard does not purport to address all of the
Thermal Insulation Materials
safety concerns, if any, associated with its use. It is the
C 1338 Test Method for Determining Fungi Resistance of
responsibility of the user of this standard to establish appro-
Insulation Materials and Facings
priate safety and health practices and determine the applica-
E84 Test Method for Surface Burning Characteristics of
bility of regulatory limitations prior to use.
Building Materials
2. Referenced Documents E 795 Practices for Mounting Test Specimens During
2
Sound Absorption Tests
2.1 ASTM Standards:
E 2231 Practice for Specimen Preparation and Mounting of
C 167 Test Methods for Thickness and Density of Blanket
Pipe and Duct Insulation Materials to Assess Surface
or Batt Thermal Insulations
Burning Characteristics
C 168 Terminology Relating to Thermal Insulation
G21 Practice for Determining Resistance of Synthetic
C 177 Test Method for Steady-State Heat Flux Measure-
Polymer Materials to Fungi
ments and Thermal Transmission Properties by Means of
G22 Practice for Determining Resistance of Plastics to
the Guarded-Hot-Plate Apparatus
Bacteria
C 390 Practice for Sampling and Acceptance of Preformed
2.2 Other Standards:
Thermal Insulation Lots
3
NAIMA Fibrous Glass Duct Liner Standard
C411 Test Method for Hot-Surface Performance of High-
4
SMACNA HVAC Duct Construction Standards
Temperature Thermal Insulation
UL723 Test for Surface Burning Characteristics of Building
C 423 Test Method for Sound Absorption and Sound Ab-
5
Materials
sorption Coefficients by the Reverberation Room Method
NFPA 255 Method of Test of Surface Burning Characteris-
C 518 Test Method for Steady-State Heat Flux Measure-
6
tics of Building Materials
ments and Thermal Transmission Properties by Means of
NFPA 259 Test Method for Potential Heat of Building
the Heat Flow Meter Apparatus
6
Materials
1
This specification is under the jurisdiction of ASTM Committee C16 on
3
Thermal Insulation and is the direct responsibility of Subcommittee C16.23 on Available from North American Insulation Manufacturers Association, 44
Blanket and Loose Fill Insulation. Canal Center Plaza, Suite 310, Alexandria, VA 22314.
4
Current edition approved April 1, 2005. Published April 2005. Originally Available from Sheet Metal and Air Conditioning Contractors National
approved in 1986. Last previous edition approved in 2000 as C 1071 – 00. Association, Inc., 4201 Lafayette Center Drive, Chantilly, VA 22021-1209.
2 5
For referenced ASTM standards, visit the ASTM website, www.astm.org, or Available from Underwriters Laboratories Inc., 333 Pfingsten Road, North-
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM brook, Illinois 60062–2096.
6
Standards volume information, refer to the standard’s Document Summary page on Available from National Fire ProtectionAssociation, 1 Batterymarch Park, PO
the ASTM website. Box 9101, Quincy, MA 02269–9101.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1
---------------------- Page: 1 ----------------------
C1071–05
CAN/ULC-S102-M88 Method of Test for Surface Burning 7.5 Erosion Resistance—When tested in accordance with
7
Characteristics of Building Materials and Assemblies 12.7, the insulation shall not break away, crack, peel, flake off,
or show evidence of delamination or continued erosion when
3. Terminology
air is passed through typical duct sections at a velocity
specified in 12.7.
3.1 For definitions of terms used in this
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.