Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware - Part 2: Fire resistance of hinged and pivoted steel doorsets

This Part of prEN 15269, which should be read in conjunction with prEN 15269-1, covers single and double leaf, hinged and pivoted, steel based doorsets.
This document prescribes the methodology for extending the application of test results obtained from test(s) conducted in accordance with EN 1634-1.
Subject to the completion of the appropriate test or tests selected from those identified in Clause 4 the extended application may cover all or some of the following non-exhaustive list:
- Integrity only (E), radiation (EW) or insulated (EI1 or EI2) classifications;
- door leaf;
- wall/ceiling fixed elements (frame/suspension system;
- glazing for door leaf;
- items of building hardware;
- decorative finishes;
- intumescent, smoke, draught or acoustic seals;
- alternative supporting construction(s).
- decorative finishes;
- intumescent, smoke, draught or acoustic seals;
alternative supporting construction(s).

Erweiterter Anwendungsbereich von Prüfergebnissen zur Feuerwiderstandsfähigkeit und/oder Rauchtigkeit von Feuerschutzabschlüssen und Fenstern einschließlich ihrer Baubeschläge - Teil 2: Feuerwiderstandsfähigkeit von Drehflügeltüreinheiten aus Stahl

Application élargie des résultats d'essais en matière de résistance au feu et/ou d'étanchéité à la fumée des blocs-portes, fermetures et fenêtre, y compris leurs éléments de quincaillerie - Partie 2: Résistance au feu des blocs-portes battants et pivotants en acier

La présente partie du prEN 15269, qu’il convient de lire conjointement avec le prEN 15269-1, couvre les blocs-portes en acier à un vantail ou deux vantaux, pivotants ou battants.
Le présent document prescrit la méthode d’extension de l’application des résultats d’essai obtenus suite aux essais menés conformément à l’EN 1634-1.
Soumise à la réalisation des essais appropriés sélectionnés parmi ceux identifiés dans l’article 4, l’application étendue peut couvrir tout ou partie de la liste non exhaustive ci-dessous :
-   classifications d’étanchéité au feu uniquement (E), de rayonnement (EW) ou d’isolation (EI1 ou EI2) ;
-   ouvrant ;
-   éléments fixes des murs/du plafond (châssis/système de suspension) ;
-   vitrage pour ouvrant ;
-   éléments de quincaillerie ;
-   finis décoratifs ;
-   joints intumescent, joints étanches à la fumée, joints étanches à l’air ou joints acoustiques ;
-   autre(s) construction(s) support(s).

Razširjena uporaba rezultatov preskusov požarne odpornosti in/ali dimotesnosti za vrata, zapore in okna, ki se odpirajo, vključno z njihovim okovjem - 2. del: Požarna odpornost jeklenih vrat s tečaji

General Information

Status
Not Published
Publication Date
24-Jul-2011
Withdrawal Date
24-Jan-2012
Current Stage
4098 - Decision to abandon - Enquiry
Start Date
13-Dec-2010
Completion Date
13-Dec-2010

Buy Standard

Draft
prEN 15269-2:2009
English language
94 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-julij-2009
5D]ãLUMHQDXSRUDEDUH]XOWDWRYSUHVNXVRYSRåDUQHRGSRUQRVWLLQDOLGLPRWHVQRVWL
]DYUDWD]DSRUHLQRNQDNLVHRGSLUDMRYNOMXþQR]QMLKRYLPRNRYMHPGHO
3RåDUQDRGSRUQRVWMHNOHQLKYUDWVWHþDML
Extended application of test results for fire resistance and/or smoke control for door,
shutter and openable window assemblies, including their elements of building hardware -
Part 2: Fire resistance of hinged and pivoted steel doorsets
Erweiterter Anwendungsbereich von Prüfergebnissen zur Feuerwiderstandsfähigkeit von
Feuerschutzabschlüssen - Teil 2: Drehflügeltüreinheiten aus Stahl
Application élargie des résultats d'essais en matière de résistance au feu et/ou
d'étanchéité à la fumée des blocs-portes, fermetures et fenêtre, y compris leurs éléments
de quincaillerie - Partie 2: Résistance au feu des blocs-portes battants et pivotants en
acier
Ta slovenski standard je istoveten z: prEN 15269-2
ICS:
13.220.50 Požarna odpornost Fire-resistance of building
gradbenih materialov in materials and elements
elementov
91.060.50 Vrata in okna Doors and windows
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD
DRAFT
NORME EUROPÉENNE
EUROPÄISCHE NORM
April 2009
ICS 13.220.50; 91.060.50
English Version
Extended application of test results for fire resistance and/or
smoke control for door, shutter and openable window
assemblies, including their elements of building hardware - Part
2: Fire resistance of hinged and pivoted steel doorsets
Application élargie des résultats d'essais en matière de
résistance au feu et/ou d'étanchéité à la fumée des blocs-
portes, fermetures et fenêtre, y compris leurs éléments de
quincaillerie - Partie 2: Résistance au feu des blocs-portes
battants et pivotants en acier
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee CEN/TC 127.
If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the
same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to
provide supporting documentation.
: This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and
Warning
shall not be referred to as a European Standard.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2009 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 15269-2:2009: E
worldwide for CEN national Members.

Contents Page
Foreword . 3
Introduction . 3
1 Scope. 4
2 Normative references . 4
3 Definitions . 5
4 Determination of the field of extended application . 5
4.1 General . 5
4.2 Procedure for evaluation . 5
4.3 Procedure for maximum field of extended application . 6
4.4 Interpretation of test results . 7
5 Extended application report . 7
6 Classification report . 7
Annex A (normative) Construction Parameter Variations . 8
Annex B (normative) Test Protocols for Doorsets Incorporating Side, Transom and Flush
Over Panels. Tables and figures in Annex B relate to Section E of Annex A . 50
Annex C (informative) Figures Relating to Annex A . 58
Bibliography . 94

Foreword
This document (prEN 15269-2:2009) has been prepared by Technical Committee CEN/TC 127 “Fire
safety in buildings”, the secretariat of which is held by BSI.
This document is currently submitted to the CEN Enquiry.
This document has been prepared under a mandate given to CEN by the European Commission and
the European Free Trade Association, and supports essential requirements of 89/106/EEC.
Introduction
This document is one of a series of standards listed below and intended to be used for the purpose of
producing an extended application report based on the evaluation of one or more fire resistance
and/or smoke control tests. These standards may also be used to identify the best selection of test
specimens required to cover a wide range of product variations.
The prEN 15269 series of standards currently consists of:
prEN 15269, Extended application of test results for fire resistance and/or smoke control for door,
shutter and openable window assemblies, including their elements of building hardware
Part 1: General requirements
Part 2: Fire resistance of hinged and pivoted steel doorsets
Part 3: Fire resistance of hinged and pivoted timber doorsets and openable timber framed windows
Part 4: Fire resistance of hinged and pivoted glass doorsets
Part 5: Fire resistance of hinged and pivoted, metal framed, glazed doorsets and openable windows
Part 6: Fire resistance of sliding timber doorsets
Part 7: Fire resistance of sliding steel doorsets
Part 8: Fire resistance of horizontally folding timber doorsets
Part 9: Fire resistance of horizontally folding steel doorsets
Part 10: Fire resistance of steel rolling shutters
Part 11: Fire resistance of fabric curtains
Part 20: Smoke control for hinged and pivoted timber and steel doorsets
Before there can be any consideration for extended application the doorset should have been tested
in accordance with EN 1634-1 to achieve a test result which could generate a classification in
accordance with EN 13501-2 at least equal to the classification subsequently required from extended
application considerations.
A review of the doorset construction parameters can indicate that one or more characteristics may be
improved by a particular parameter variation. All evaluations should be made on the basis of retaining
the fire resistance classifications obtainable from testing to EN 1634-1, including those lower than the
test duration. However, this should never lead to an increased classification for any specific fire
performance parameter beyond that achieved during any one test unless specifically identified in the
relevant Construction Parameter Variation tables within this series of standards.
The effect on the durability of self closing of the doorsets following an extended application process is
not addressed in this series of standards.
1 Scope
This Part of prEN 15269, which should be read in conjunction with prEN 15269-1, covers single and
double leaf, hinged and pivoted, steel based doorsets.
This document prescribes the methodology for extending the application of test results obtained from
test(s) conducted in accordance with EN 1634-1.
Subject to the completion of the appropriate test or tests selected from those identified in Clause 4 the
extended application may cover all or some of the following non-exhaustive list:
 Integrity only (E), radiation (EW) or insulated (EI or EI ) classifications;
1 2
 door leaf;
 wall/ceiling fixed elements (frame/suspension system;
 glazing for door leaf;
 items of building hardware;
 decorative finishes;
 intumescent, smoke, draught or acoustic seals;
 alternative supporting construction(s).
2 Normative references
This European Standard incorporates by dated or undated reference, provisions from other
publications. These normative references are cited at the appropriate places in the text and the
publications are listed hereafter. For dated references, subsequent amendments to or revisions of any
of these publications apply to this European Standard only when incorporated in it by amendment or
revision. For undated references the latest edition of the publication referred to applies.
EN 1634-1, Fire resistance and smoke control tests for door, shutter and openable window
assemblies and elements of building hardware - Part 1: Fire resistance tests for doors, shutters and
openable windows
EN 1634-2, Fire resistance and smoke control tests for door, shutter and openable window
assemblies and elements of building hardware - Part 2: Fire resistance characterisation test for
elements of building hardware
EN 13501-2, Fire classification of construction products and building elements — Part 2: Classification
using data from fire resistance tests, excluding ventilation services
3 Terms and definitions
For the purposes of this Part or EN 15269, the terms and definitions given in EN1363-1, EN ISO
13943, EN 1634-1, prEN 1634-2 and prEN 15269-1 together with the following apply:
3.1 full scale test
test of a full size doorset in accordance with EN 1634-1
3.2 small scale test
test on elements of building hardware in accordance with prEN 1634-2 and where the decision
process, given in prEN 1634-2, permits its use. This is abbreviated as SS in annex C
3.3 effective rebate depth
dimension of the door leaf thickness of overlapping adjacent edges of door leaf relative to the door
frame, transom or side panel or flush overpanel. At the meeting edges and for rebated leaves the
dimension shall be the depth of the largest rebate or the rebate where the intumescent seal is fitted
3.4 panel
component of a door leaf separated from other elements by joints which break through the total door
thickness. A door leaf can consist of one or more panels.
4 Determination of the field of extended application
4.1 General
4.1.1 Before there can be any consideration for extended application, the doorset must have been
tested and classified in accordance with EN1634-1 and EN 13501-2 respectively in order to establish
a classification for the doorset.
4.1.2 A review of the doorset construction parameters can indicate that one or more characteristics
may be improved by a particular parameter variation. All evaluations shall be made on the basis of
retaining the classifications obtainable from testing to EN1634-1, including those lower than the test
duration. However, this shall never lead to an increased classification for any specific parameter
beyond that achieved during any one test unless specifically identified in the relevant Construction
Parameter Variation tables.
4.1.3 All evaluations shall be made on the basis of retaining the classification obtained from testing
to EN1634-1.
4.1.4 If, by following the ensuing procedure, any part of the classification cannot be achieved by
extended application rules, that part of classification shall be omitted from the subsequent extended
application report and classification report.
4.2 Procedure for evaluation
4.2.1 Identify the variations from the original test specimen(s) which are required to be covered by
an extended application report.
4.2.2 Locate the variations in the appropriate parameter variation by reference to columns (1) and
(2) of Annex A.
4.2.3 Review the type of classification to be retained from column (3) and establish from the
contents of column (4) whether any extended application is available beyond the direct application
rules in EN 1634-1 without the need for further testing.
4.2.4 Where this is deemed to be possible this can be recorded in the extended application report
together with any appropriate restrictions and the stated rules from column (4).
4.2.5 Where the variations required can only be achieved from additional testing according to
column (5), the additional test can be made on a similar specimen type to the original test against
which the extended application is sought. Alternatively, column (5) identifies an option for alternative
testing and relevant test parameters.
4.3 Procedure for maximum field of extended application
4.3.1 It is possible to provide a limited field extended of application from the results of a
...

Questions, Comments and Discussion