Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware - Part 6: Fire resistance of sliding timber doorsets

This European Standard covers horizontally sliding doorsets and hatches (single and double) with timber based leaves and timber framed glazed leaves. It prescribes the methodology for extending the application of test results obtained from fire resistance test(s) conducted in accordance with EN 1634-1. This standard covers doorsets with internal structural elements which are comprised of timber.
Subject to the completion of the appropriate test or tests selected from those identified in Clause 4, the extended application can cover all or some of the following non-exhaustive list:
—   integrity (E), integrity/radiation (EW) or integrity/insulation (EI1 or EI2) classification;
—   glazed elements and framed glazed doorsets;
—   side, transom or overpanels;
—   doorframe;
—   suspension system;
—   items of building hardware;
—   decorative finishes;
—   intumescent, smoke, draught or acoustic seals;
—   alternative supporting construction(s).
The effect on the Classification ‘C’ for the doorsets following an extended application process is not addressed in this standard.

Erweiterter Anwendungsbereich von Prüfergebnissen zur Feuerwiderstandsfähigkeit und/oder Rauchdichtigkeit von Türen, Toren und Fenstern einschließlich ihrer Baubeschläge - Teil 6: Feuerwiderstandsfähigkeit von Schiebetüren aus Holz

Diese Europäische Norm gilt für (einflügelige und zweiflügelige) horizontale Schiebetüren und  klappen aus Holz¬werkstoffen und verglaste Holztüren. Sie beschreibt die Methodologie zur Erweiterung der Anwendung von Ergebnissen der Prüfung(en) der Feuerwiderstandsfähigkeit nach EN 1634 1. Diese Norm behandelt Türen mit einer tragenden Innenkonstruktion aus Holz.
In Abhängigkeit von der Durchführung der jeweiligen, aus den entsprechenden Beschreibungen in Abschnitt 4 ausgewählten Prüfung(en) kann der erweiterte Anwendungsbereich einige oder alle aus der folgenden, nicht ausschließlichen Liste abdecken:
   Klassifizierungen von nicht wärmegedämmten Elementen (E) sowie solchen mit Anforderungen an die Strahlung (EW) oder wärmegedämmten Elementen (EI1 oder EI2);
   verglaste Teilbereiche und verglaste Türen;
   Seitenteile, Oberteile mit oder ohne Kämpfer;
   Türzarge;
   Aufhängungssystem;
   Baubeschläge;
   dekorative Beschichtungen;
   dämmschichtbildende Dichtungen sowie Dichtungen zur Verhinderung von Rauchdurchtritt, Durchzug oder Schallübertragung;
   alternative Tragkonstruktion(en).
Die Auswirkung der Klassifizierung „C“ für Türen im Rahmen des Prozesses eines erweiterten Anwendungs¬bereichs ist nicht Gegenstand dieser Norm.

Application étendue des résultats d'essais en matière de résistance au feu et/ou d'étanchéité à la fumée des blocs-portes, blocs-fermetures et ouvrants de fenêtre, y compris leurs éléments de quincaillerie intégrés - Partie 6 : Résistance au feu des blocs-portes coulissants

La présente Norme européenne couvre les blocs-portes et trappes coulissants horizontalement (à un vantail ou deux vantaux) à vantaux à base de bois et à vantaux vitrés à ossature en bois. Elle prescrit la méthodologie permettant d'étendre l'application des résultats obtenus à partir d’un ou plusieurs essai(s) de résistance au feu effectué(s) conformément à l'EN 1634-1. La présente norme couvre les blocs-portes à éléments de structure internes composés de bois.
Sous réserve de la réalisation de l'essai ou des essais appropriés choisis parmi ceux identifiés à l'Article 4, l'application étendue peut couvrir tout ou partie de la liste non exhaustive suivante :
   classement de l'étanchéité au feu (E), de l'étanchéité au feu/rayonnements (EW) ou de l'étanchéité au feu/isolation thermique (EI1 ou EI2) ;
   éléments vitrés et blocs-portes vitrés ;
   panneaux latéraux, panneaux d'imposte ;
   dormant ;
   système de suspension ;
   éléments de quincaillerie de bâtiment ;
   finitions décoratives ;
   joints intumescents, joints d'étanchéité à la fumée, joints d'étanchéité à l'air ou joints acoustiques ;
   autre(s) construction(s) support.
L'effet sur le classement « C » des blocs-portes à la suite d'un processus d'application étendue n'est pas traité dans la présente norme.

Razširjena uporaba rezultatov preskusov požarne odpornosti in/ali dimotesnosti za vrata, zaporne elemente in okna, ki se odpirajo, vključno z njihovim okovjem - 6. del: Požarna odpornost lesenih drsnih vrat

General Information

Status
Not Published
Publication Date
28-May-2017
Withdrawal Date
28-Nov-2017
Current Stage
4098 - Decision to abandon - Enquiry
Completion Date
11-Oct-2017

Buy Standard

Draft
prEN 15269-6:2016
English language
76 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-januar-2016
5D]ãLUMHQDXSRUDEDUH]XOWDWRYSUHVNXVRYSRåDUQHRGSRUQRVWLLQDOLGLPRWHVQRVWL
]DYUDWD]DSRUQHHOHPHQWHLQRNQDNLVHRGSLUDMRYNOMXþQR]QMLKRYLPRNRYMHP
GHO3RåDUQDRGSRUQRVWOHVHQLKGUVQLKYUDW
Extended application of test results for fire resistance and/or smoke control for door,
shutter and openable window assemblies, including their elements of building hardware -
Part 6: Fire resistance of sliding timber doorsets
Erweiterter Anwendungsbereich von Prüfergebnissen zur Feuerwiderstandsfähigkeit
und/oder Rauchdichtigkeit von Türen, Toren und Fenstern einschließlich ihrer
Baubeschläge - Teil 6: Feuerwiderstandsfähigkeit von Schiebetüren aus Holz
Application étendue des résultats d'essais en matière de résistance au feu et/ou
d'étanchéité à la fumée des blocs-portes, blocs-fermetures et ouvrants de fenêtre, y
compris leurs éléments de quincaillerie intégrés - Partie 6 : Résistance au feu des blocs-
portes coulissants
Ta slovenski standard je istoveten z: prEN 15269-6
ICS:
13.220.50 Požarna odpornost Fire-resistance of building
gradbenih materialov in materials and elements
elementov
91.060.50 Vrata in okna Doors and windows
91.190 Stavbna oprema Building accessories
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

DRAFT
EUROPEAN STANDARD
NORME EUROPÉENNE
EUROPÄISCHE NORM
October 2015
ICS 13.220.50; 91.060.50
English Version
Extended application of test results for fire resistance
and/or smoke control for door, shutter and openable
window assemblies, including their elements of building
hardware - Part 6: Fire resistance of sliding timber
doorsets
Application étendue des résultats d'essais en matière Erweiterter Anwendungsbereich von Prüfergebnissen
de résistance au feu et/ou d'étanchéité à la fumée des zur Feuerwiderstandsfähigkeit und/oder
blocs-portes, blocs-fermetures et ouvrants de fenêtre, y Rauchdichtigkeit von Türen, Toren und Fenstern
compris leurs éléments de quincaillerie intégrés - einschließlich ihrer Baubeschläge - Teil 6:
Partie 6 : Résistance au feu des blocs-portes coulissants Feuerwiderstandsfähigkeit von Schiebetüren aus Holz
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee
CEN/TC 127.
If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations
which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC
Management Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and
United Kingdom.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are
aware and to provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without
notice and shall not be referred to as a European Standard.

EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2015 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 15269-6:2015 E
worldwide for CEN national Members.

Contents Page
European foreword . 3
1 Scope . 4
2 Normative references . 4
3 Terms and definitions . 5
4 Determination of the field of extended application . 5
4.1 General . 5
4.2 How to use the extended application rules in Annex A . 6
4.3 Procedure for maximum field of extended application . 6
4.4 Analysis of test results . 7
5 Extended application report . 7
6 Classification report . 7
Annex A (normative) Construction parameter variations . 8
A.1 General . 8
A.2 Construction parameter variations . 10
A.3 Figures . 65
Bibliography . 76

European foreword
This document (prEN 15269-6:2015) has been prepared by Technical Committee CEN/TC 127
“Fire safety in buildings”, the secretariat of which is held by BSI.
This document is currently submitted to the CEN Enquiry.
This document has been prepared under a mandate given to CEN by the European Commission
and the European Free Trade Association.
EN 15269-6 is part of a series entitled “Extended application of test results for fire resistance
and/or smoke control for door, shutter and openable window assemblies, including their
elements of building hardware” which consists of the following parts:
— Part 1: General requirements
— Part 2: Fire resistance of hinged and pivoted steel doorsets
— Part 3: Fire resistance of hinged and pivoted timber doorsets and openable timber framed
windows
— Part 5: Fire resistance of hinged and pivoted, metal framed, glazed doorsets and openable
windows
— Part 6: Fire resistance of sliding timber doorsets
— Part 7: Fire resistance of sliding steel doorsets
— Part 10: Fire resistance of steel rolling shutter assemblies
— Part 11: Fire resistance of operable fabric curtains
— Part 20: Smoke control for hinged and pivoted timber and steel doorsets
1 Scope
This European Standard covers horizontally sliding doorsets and hatches (single and double)
with timber based leaves and timber framed glazed leaves. It prescribes the methodology for
extending the application of test results obtained from fire resistance test(s) conducted in
accordance with EN 1634-1. This standard covers doorsets with internal structural elements
which are comprised of timber.
Subject to the completion of the appropriate test or tests selected from those identified in
Clause 4, the extended application can cover all or some of the following non-exhaustive list:
— integrity (E), integrity/radiation (EW) or integrity/insulation (EI or EI ) classification;
1 2
— glazed elements and framed glazed doorsets;
— side, transom or overpanels;
— doorframe;
— suspension system;
— items of building hardware;
— decorative finishes;
— intumescent, smoke, draught or acoustic seals;
— alternative supporting construction(s).
The effect on the Classification ‘C’ for the doorsets following an extended application process is
not addressed in this standard.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and
are indispensable for its application. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments)
applies.
EN 1363-1, Fire resistance tests - Part 1: General Requirements
EN 1634-1, Fire resistance and smoke control tests for door and shutter assemblies, openable
windows and elements of building hardware - Part 1: Fire resistance test for door and shutter
assemblies and openable windows
EN 1634-2, Fire resistance and smoke control tests for door, shutter and openable window
assemblies and elements of building hardware - Part 2: Fire resistance characterisation test for
elements of building hardware
EN 12519, Windows and pedestrian doors - Terminology
EN 13501-2, Fire classification of construction products and building elements - Part 2:
Classification using test data from fire resistance tests excluding ventilation services
EN ISO 13943, Fire safety - Vocabulary (ISO 13943)
EN 15254-4, Extended application of results from fire resistance tests - Non-loadbearing walls -
Part 4: Glazed constructions
EN 15269-1:2010, Extended application of test results for fire resistance and/or smoke control for
door, shutter and openable window assemblies, including their elements of building hardware -
Part 1: General requirements
EN 15269-3, Extended application of test results for fire resistance and/or smoke control for door,
shutter and openable window assemblies, including their elements of building hardware - Part 3:
Fire resistance of hinged and pivoted timber doorsets and openable timber framed windows
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 1363-1, EN 12519,
EN ISO 13943, EN 1634-1, EN 1634-2 and EN 15269-1 together with the following apply.
3.1
core
material fitted centrally within the thickness of a door leaf
Note 1 to entry: It may consist of a single sheet of material or a combination either of sheets of the same
material or layers of different materials.
3.2
leaf symmetry
construction of a door leaf, without consideration of any leaf edge rebates, viewed either side of
an imaginary plane drawn centrally in the thickness of the leaf
Note 1 to entry: A symmetrical door leaf will be identical either side of this imaginary plane, whilst an
asymmetrical door leaf will differ.
3.3
facing (and decorative facing)
outer layer of material on the leaf or panel normally only used for decorative, not structural,
purposes
3.4
subfacing
layer (or layers) of material between the core and the facing in the leaf or panel normally used
for structural purposes
3.5
lipping
material on the door edge, limited to a thickness of 12 mm
Note 1 to entry: A 'Lipping' of more than 12 mm thickness is deemed to be a leaf framing element.
Lippings of less than 3 mm thick are deemed to be a veneer.
4 Determination of the field of extended application
4.1 General
4.1.1 Before there can be any consideration for extended application, a representative doorset
shall have been tested in accordance with EN 1634-1 to achieve a test result which could
generate a classification in accordance with EN 13501-2 at least equal to the classification
subsequently required from extended application considerations.
4.1.2 A review of the doorset construction parameters can indicate that one or more
characteristics may be improved by a particular parameter variation. All evaluations shall be
made on the basis of retaining the classifications obtainable from testing to EN 1634-1,
including those lower than the test duration. However, this shall never lead to an increased
classification for any specific parameter beyond that achieved during any one test unless
specifically identified in the relevant Construction Parameter Variation tables.
4.1.3 If, when following the extended application procedure, any part of the classified product
cannot be covered by the extended application rules then that part shall be omitted from the
subsequent extended application report and classification report.
4.2 How to use the extended application rules in Annex A
4.2.1 Identify the variations from the original test specimen(s) which are required to be
covered by an extended application report.
4.2.2 Locate the variations in the appropriate parameter variation by reference to columns
(1) and (2) of Table A.2.
4.2.3 Review the type of classification to be retained from column (3) of Table A.2 and
establish from the contents of column (4) of Table A.2 whether any extended application is
available beyond the direct application rules in EN 1634-1 without the need for further testing.
4.2.4 Where this is deemed to be possible it can be recorded in the extended application
report together with any appropriate restrictions and the stated rules from column (4) of
Table A.2.
4.2.5 Where the variations required can only be achieved from additional testing, the
additional test can be made on a similar specimen type i.e. a doorset of the same or more
onerous configuration where the construction is fundamentally the same as tested but with the
required outstanding parameter. Alternatively, column
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.