Abstract

This document defines the general terms and the calculations used to determine the thermohydraulic performance of heat exchangers. It includes the general test procedure and related theories.
This document is intended to be used for acceptance-testing heat exchangers in test facilities such as laboratories, manufacturer test facilities and final installation site.
This document specifies three acceptance levels:
—   level 1 for minimum tolerances;
—   level 2 for nominal tolerances;
—   level 3 for maximum tolerances;
This document constitutes an application-specific standard in line with EN 305 and EN 306.

Status
Published
Publication Date
17-Aug-2026
Technical Committee
CEN/TC 110 - Heat exchangers
Current Stage
6060 - Definitive text made available (DAV) - Publishing
Start Date
28-Oct-2026
Due Date
18-Aug-2026
Completion Date
18-Aug-2026

Buy Documents

EN 18208:2026 is a CEN standard for liquid-to-liquid single-phase heat exchangers. It specifies the terms, calculation methods and test procedure used to determine thermohydraulic performance, mainly for acceptance testing in laboratories, manufacturer test facilities and at the final installation site. The document also sets three acceptance levels for minimum, nominal and maximum tolerances.

What does EN 18208:2026 specify?

EN 18208:2026 specifies how to define, measure and assess the thermohydraulic performance of liquid-to-liquid single-phase heat exchangers. It is an application-specific standard aligned with EN 305 and EN 306, so it sits within the broader European framework for heat-exchanger performance and measurement.

The scope covers acceptance testing and the calculations needed for performance evaluation. The underlying assumption is a Newtonian fluid in turbulent conditions, and the text allows adaptation for other liquids or conditions when the parties agree.

The document is organized into clauses 1 to 6, followed by three informative annexes.

AnnexWhat it covers
Annex ACalculation of thermal performance uncertainty k.A.F. according to the LMTD method
Annex BTest report template
Annex CExample of test

What are the key requirements of EN 18208:2026?

Performance is defined from rated conditions and basic heat-exchanger quantities

EN 18208:2026 requires thermohydraulic performance to be defined from rated conditions such as liquid type, flow rate, temperatures, pressures, physical properties, fouling state, auxiliary equipment and environmental constraints. In practice, this means the customer and manufacturer need to agree on the operating point before testing, otherwise the result cannot be judged fairly.

Clause 5 uses a set of derived quantities from EN 305, including pressure drops, heat transfer rate, overall heat transfer coefficient, heat transfer area, LMTD, NTU and thermal performance k.A.F. The document also distinguishes thermal resistance, cleanliness factor and fouling state, which matters because new exchangers are treated differently from exchangers already in service.

Thermal and hydraulic performance are both part of the assessment

EN 18208:2026 treats hydraulic performance as pressure drop and thermal performance as energy transfer across the exchanger. Clause 5.2 links the hydraulic part to Bernoulli-based pressure-loss calculation, while Clause 5.3 uses an energy balance to compare inlet and outlet conditions on both sides.

For thermal sizing and evaluation, the document recognizes two main calculation routes. The LMTD method is used when heat transfer surface is being determined from duty and temperatures, while the NTU method is used when outlet temperatures are being predicted from geometry. That matters because the reader must choose the method that matches the design or simulation task.

The document sets three acceptance levels for testing

EN 18208:2026 defines three acceptance levels: level 1 for minimum tolerances, level 2 for nominal tolerances and level 3 for maximum tolerances. The document maps these levels to typical test environments - laboratory or dedicated facility, factory with sensors and dedicated acquisition chain, and on-site measurements with operating sensors.

This level choice matters in practice because it drives the allowed uncertainty, the required sensor quality and the likely confidence in the result. For example, laboratory tests are expected to achieve the strictest level, while in situ testing is more tolerant but harder to measure accurately.

Test conditions, stability and instrumentation are tightly controlled

Clause 6 requires the test bench to match the intended installation as closely as possible, including auxiliary equipment and cleanliness. It also requires the exchanger to be identified, checked against design characteristics, filled with suitable liquids, sealed, purged of trapped air and fitted with calibrated instruments.

The test itself must reach steady-state and stay there long enough for valid averaging. The document also requires a quality check comparing primary-side and secondary-side heat transfer rates, plus a stability check that compares the two values against their combined uncertainty. In practice, this keeps a short or unstable test from being accepted as a true performance result.

Uncertainty limits depend on the acceptance level

EN 18208:2026 gives overall uncertainty targets for flow, pressure, temperature, hydraulic performance and thermal performance. It also gives limits on the acceptable amplitude of fluctuations during testing, which is important when the test facility or process creates oscillating readings.

The document requires calibrated flowmeters, temperature sensors and pressure sensors, with calibration and uncertainty management consistent with the chosen acceptance level. This is practical guidance for test laboratories and manufacturers because the final performance claim depends on measurement quality, not just on the exchanger itself.

Results can be transposed to reference conditions

Clause 6 allows test results to be transposed when the test conditions differ from the reference conditions. Separate methods are given for new or replacement heat exchangers and for heat exchangers already in use, with thermal and hydraulic transposition treated separately.

For thermal transposition, the document uses model adjustment factors and references the Kern method, local heat-transfer coefficients, conduction resistance and fouling resistance. For hydraulic transposition, it uses a pressure-drop coefficient and recommends at least three points for a trend curve and extrapolation. This is important when a perfect match to site conditions is not possible.

The test report must capture the full evidence trail

Clause 6.4 requires a report with the date, observers, exchanger identity, liquids used, test procedure, test programme, calibration references, measurements and final results. Annex B then gives a report template.

In practice, this means the test is not only a calculation exercise. It must be documented well enough for the customer, manufacturer or verifier to review the conditions, uncertainties and conclusions later.

What terms does EN 18208:2026 define?

  • Liquid - any liquid used to transfer thermal energy, including a mixture of liquids in the same single phase.
  • Primary liquid - the hottest liquid, acting as the heat source.
  • Secondary liquid - the coolest liquid, acting as the heat sink.
  • Thermohydraulic performance of a heat exchanger - the performance expressed through temperatures, flow rates, pressures, pressure drops, heat transfer rate, heat transfer coefficient and fouling-related quantities.
  • Fouling - unwanted deposits that increase resistance to heat transfer.
  • Plugging - blockage of openings or channels that reduces transfer surface and increases pressure drop.
  • Design state (reference conditions) - the operating parameters used to determine the required minimum thermal performance.
  • Steady-state - the condition where the main variables remain constant over time within measurement limits.

Who uses EN 18208:2026?

EN 18208:2026 is used by manufacturers, customers, users, laboratories and verifiers working with liquid-to-liquid heat exchangers. It is relevant wherever a heat exchanger must be acceptance-tested, whether in a lab, in a factory or on site.

Manufacturers use it to prepare performance claims, define reference conditions and transpose test results to design conditions. Laboratories use it to set up the test bench, choose instruments, calculate uncertainty and issue the report. Customers and buyers use it to define acceptance criteria and decide whether a tested exchanger meets the required duty. Users of operating exchangers use it for periodic checks, fouling assessment and decisions about cleaning, plugging or replacement.

Which standards are used with EN 18208:2026?

  • EN 247 - supplies the common terminology for heat exchangers.
  • EN 305 - gives the performance definitions and the general test procedure framework that this document builds on.
  • EN 306 - provides methods for measuring the parameters needed to establish performance and estimate measurement uncertainty.
  • EN ISO 5167 (all parts) - supports flow measurement by pressure-differential devices in full circular conduits.
  • ISO/TR 12767 - gives guidance on the effect of departures from ISO 5167 specifications and operating conditions.
  • EN ISO/IEC 17025 - is used in Clause 6.2 for calibration practice and laboratory competence during testing.

What does the EN 18208:2026 document contain?

EN 18208:2026 contains the definitions, symbols and calculation methods needed to evaluate liquid-to-liquid single-phase heat exchangers. It includes performance quantities, rated-condition requirements, thermal and hydraulic calculation routes, and the acceptance logic for new and operating exchangers.

The document also contains figures for counter-current and co-current flow, tables for derived quantities, acceptance levels and uncertainty limits, and formulae for energy balance, pressure drop, LMTD, NTU and thermal efficiency. These parts are used for design checks, acceptance testing, transposition to reference conditions and uncertainty evaluation.

Annex A provides the uncertainty approach for k.A.F. using the LMTD method. Annex B gives a report structure that supports test documentation and traceability. Annex C shows a worked example for thermal performance and pressure drop, including transposition from test conditions to reference conditions.

Buy Documents

Get Certified

Connect with accredited certification bodies for this standard

DNV

DNV is an independent assurance and risk management provider.

NA Norway Verified

Lloyd's Register

Lloyd's Register is a global professional services organisation specialising in engineering and technology.

UKAS United Kingdom Verified

DNV Energy Systems

Energy and renewable energy certification.

NA Norway Verified

Sponsored listings

Frequently Asked Questions

EN 18208:2026 is a standard published by the European Committee for Standardization (CEN). Its full title is "Liquid-to-liquid single-phase heat exchangers - Test procedure for determining performance". This standard covers: This document defines the general terms and the calculations used to determine the thermohydraulic performance of heat exchangers. It includes the general test procedure and related theories. This document is intended to be used for acceptance-testing heat exchangers in test facilities such as laboratories, manufacturer test facilities and final installation site. This document specifies three acceptance levels: — level 1 for minimum tolerances; — level 2 for nominal tolerances; — level 3 for maximum tolerances; This document constitutes an application-specific standard in line with EN 305 and EN 306.

This document defines the general terms and the calculations used to determine the thermohydraulic performance of heat exchangers. It includes the general test procedure and related theories. This document is intended to be used for acceptance-testing heat exchangers in test facilities such as laboratories, manufacturer test facilities and final installation site. This document specifies three acceptance levels: — level 1 for minimum tolerances; — level 2 for nominal tolerances; — level 3 for maximum tolerances; This document constitutes an application-specific standard in line with EN 305 and EN 306.

EN 18208:2026 is classified under the following ICS (International Classification for Standards) categories: 27.060.30 - Boilers and heat exchangers. The ICS classification helps identify the subject area and facilitates finding related standards.

EN 18208:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • Introduction
  • 1 Scope
  • 2 Normative references
  • 3 Terms and definitions
  • 3.1 liquid
  • 3.2 primary liquid
  • 3.3 secondary liquid
  • 3.4 mixture
  • 3.5 heat exchanger
  • 3.6 thermohydraulic performance of a heat exchanger
  • 3.7 heat exchanger categories
  • 3.8 heating
  • 3.9 cooling
  • 3.10 fouling
  • 3.11 plugging
  • 3.12 irreversible pressure drop
  • 3.13 typical inlet
  • 3.14 typical outlet
  • 3.15 pinch temperature
  • 3.16 customer
  • 3.17 maker
  • 3.18 verifier
  • 3.19 design state
  • 3.20 steady state
  • 3.21 required
  • 4 Symbols and abbreviations
  • 5 Performance of liquid-to-liquid heat exchangers
  • 5.1 Typical quantities
  • 5.2 Hydraulic performance
  • 5.3 Thermal performance
  • 6 Performance test description and requirements
  • 6.1 Test procedures
  • 6.2 Measurements and instrumentation
  • 6.3 Test analysis
  • 6.4 Test report
  • Annex A
  • Annex B
  • 1. General information
  • Annex C
  • Annex D
  • Bibliography

Introduction

This document is designed to support a series of European standards dedicated to heat exchangers. This document provides manufacturers and users with the information needed to present the thermohydraulic performance characteristics of a heat exchanger. These characteristics form the basis for evaluating the state of a heat exchanger, whether it is new/a replacement, or already in operation. This document also provides a performance-based acceptance test procedure for a liquid-to-liquid singlephase heat exchanger (sensor calibration, acknowledgement of uncertainties, standardization of physical properties of liquids) and the possible transpositions under various rated conditions. The customer's technical specification, referred to in this document, defines or adapts the level of tolerance. It also defines thermal performance acceptance criteria. Examples are provided in Annex C. Underlying assumption of this document is that the liquid is a Newtonian fluid in turbulent conditions. This document may be adapted for other liquids or conditions, as agreed by parties involved in the performance test.

SIST EN 18208:2027 EN 18208:2026 (E)

1 Scope

This document defines the general terms and the calculations used to determine the thermohydraulic performance of heat exchangers. It includes the general test procedure and related theories. This document is intended to be used for acceptance-testing heat exchangers in test facilities such as laboratories, manufacturer test facilities and final installation site. This document specifies three acceptance levels:

  • level 1 for minimum tolerances;
  • level 2 for nominal tolerances;
  • level 3 for maximum tolerances; This document constitutes an application-specific standard in line with EN 305 and EN 306.

2 Normative references

The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 247, Heat exchangers — Terminology EN 305, Heat exchangers — Definitions of performance of heat exchangers and the general test procedure for establishing performance of all heat exchangers EN 306, Heat exchangers — Methods of measuring the parameters necessary for establishing the performance EN ISO 5167 (all parts), Measurement of fluid flow by means of pressure differential devices inserted in circular cross-section conduits running full ISO/TR 12767, Measurement of fluid flow by means of pressure differential devices — Guidelines on the effect of departure from the specifications and operating conditions given in ISO 5167

3 Terms and definitions

For the purposes of this document, the terms and definitions given in EN 247 and the following apply. ISO and IEC maintain terminology databases for use in standardization at the following addresses:

  • ISO Online browsing platform: available at https://www.iso.org/obp/
  • IEC Electropedia: available at https://www.electropedia.org/

3.1 liquid

any type of liquid, such as water, used to transfer thermal energy (heat) Note 1 to entry: There can be a combination of two or more types of liquids, all in the same phase state (singlephase liquid).

SIST EN 18208:2027 EN 18208:2026 (E)

3.2 primary liquid

hottest liquid, which serves as a heat source

3.3 secondary liquid

coolest liquid, which serves as a heat sink

3.4 mixture

liquid with two or more elements, all in the same phase state

3.5 heat exchanger

device designed to transfer heat between two physically separated liquids

3.6 thermohydraulic performance of a heat exchanger

heat exchanger thermohydraulic performance that can be established by measuring, or can be calculated using measured parameters, and is expressed according to one or more of the following elements:

  • temperature of primary/secondary liquid;
  • flow rate of primary/secondary liquid;
  • pressure of primary/secondary liquid;
  • temperature difference;
  • heat transfer coefficient;
  • heat transfer rate transferred by primary liquid / captured by secondary liquid;
  • pressure drops;
  • fouling factors.

Note 1 to entry: These elements are identified per EN 305 and may be established by measuring per EN 306.

3.7 heat exchanger categories

classification of heat exchanger types based on design criteria, physical criteria, or a mix of the two

3.8 heating

temperature increase of a secondary liquid that does not change its phase state

3.9 cooling

temperature decrease of a primary liquid that does not change its phase state

3.10 fouling

deposit of a layer of unwanted materials entailing/causing resistance to the heat transfer

SIST EN 18208:2027 EN 18208:2026 (E)

3.11 plugging

obstruction of one or more openings/channels in a heat exchanger where no primary or secondary liquid can circulate, resulting in a decrease in the transfer surface and an increase in pressure drops

3.12 irreversible pressure drop

decrease of static pressure between inlet and outlet not including change of level

3.13 typical inlet

inlet considered the most representative of each heat exchanger, chosen by the manufacturer or in accordance with the installation conditions

3.14 typical outlet

outlet considered the most representative of each heat exchanger, chosen by the manufacturer or in accordance with the conditions of use

3.15 pinch temperature

minimum difference between the primary liquid and secondary liquid temperatures

3.16 customer

user entity that purchases a good or service from a supplier Note 1 to entry: For test of used heat exchangers, the user is responsible of the fouling of the heat exchanger. (i.e. for cleaning it or defining the fouling resistance)

3.17 maker

manufacturer supplier entity that supplies goods to a user and guarantees the performance of the heat exchanger (sourcing, manufacture, production inspection, packaging, storage, transport) Note 1 to entry: For new heat exchangers, in the case of performance tests, they are also responsible for checking heat exchanger cleanliness (initial cleanliness report), preparing the heat exchanger and its immediate environment (e.g. anchoring, adapters, cradles, access scaffolding) and establishing the thermohydraulic criterion checking report (by transposition if the conditions differ from the reference conditions, per 6.3).

3.18 verifier

laboratory entity that verifies the equipment performance through one or more tests and ensures the exchanger test measurements (calibration, test bench assembly, bench cleanliness check, sensor installation, liquid analysis report, acquisition chain, test bench/heat exchanger adapters connection, performance test, uncertainty calculations), including measurement uncertainties

SIST EN 18208:2027 EN 18208:2026 (E)

3.19 design state

reference conditions heat exchanger operating parameters that will determine the minimum k.A.F. coefficient required to satisfy the customer's criterion Note 1 to entry: This state is determined by the manufacturer based on the operating situations required by the customer (mass flow rates and liquid temperatures, heat transfer rate to be transferred, etc.)

3.20 steady state

condition where the average value of all main variables of the heat exchanger (temperature, pressure, flow rate) remains constant over time, and fluctuations are in the same order of magnitude of the measuring sensor, given that external conditions and inputs are unchanging Note 1 to entry: Steady-state criteria are expressed in 6.1.3.

3.21 required

thermohydraulic rated conditions according to customer requirements

4 Symbols and abbreviations

For the purposes of this document, the symbols, abbreviations and subscripts given in Table 1 apply. Table 1 — Symbols, abbreviations, subscripts and units Symbol Denomination Unit

A Reference heat transfer surface area m C Hydraulic test factor — DP C Thermal test factor — e C Cleanliness factor — foul C Constant pressure specific heat capacity J/(kg °C) p F LMTD correction factor —

g Acceleration of gravity m/s h Specific enthalpy J/kg

k Overall heat transfer coefficient W/(m °C) k·A·F Heat exchanger thermal performance W/°C LMTD Log mean temperature difference °C NTU Number of thermal transfer units — p Pressure Pa q Mass flow kg/s m q c Heat capacity flow rate W/°C m p

R Resistance (thermal) (m °C)/W

S Liquid flow section m

SIST EN 18208:2027 EN 18208:2026 (E) Symbol Denomination Unit SM Excess surface heat transfer coefficient % T Celsius temperature °C U Absolute uncertainty — v Velocity m/s x Overall heat transfer coefficient margin % y Heat flow ratio — z Height m

α Convective heat transfer coefficient W/(m °C) ε Thermal efficiency — ζ Pressure drop coefficient — λ Thermal conductivity W/(m °C) µ Dynamic viscosity at liquid average temperature kg/(m.s) µ Dynamic viscosity at temperature of wall in contact with liquid kg/(m.s) w Φ Heat transfer rate W

ρ Density kg/m σ Experimental standard deviation — Δ Difference — Absolute — abs Clean — clean Fouled/fouling — foul Mass — m max Maximum — Material in contact with liquid — mat Minimum — min Numerical — num Operational — op Relative — rel Design reference — required Test — test Transposed/transposition — transpo Primary side —

Secondary side —

Inlet conditions, primary side —

Outlet conditions, primary side —

SIST EN 18208:2027 EN 18208:2026 (E) Symbol Denomination Unit Inlet conditions, secondary side —

Outlet conditions, secondary side —

NOTE The LMTD correction factor F depends on the type of heat exchanger and the flow configuration. This factor is equal to or less than 1 (5.3.5.2).

5 Performance of liquid-to-liquid heat exchangers

5.1 Typical quantities

5.1.1 Derived quantities

When this document serves as the basis for establishing performance characteristics, the parts contained in EN 305 shall be used (see Table 2).

Table 2 — Quantity used to establish performance characteristics Quantity Designation Subclause Fouling thermal resistance R 5.1.2.5 foul Excess surface heat transfer coefficient SM 5.1.2.5 Cleanliness factor C 5.1.2.5 foul Pressure drops (hydraulic performance) Δp 5.2 Heat transfer rate Φ 5.3.2 Overall heat transfer coefficient k 5.3.3 Heat transfer area A 5.3.4 Logarithmic mean temperature difference LMTD 5.3.5.2 Thermal performance k.A.F 5.3.5.2.3 Number of thermal transfer units NTU 5.3.5.2.4 Thermal efficiency ε 5.3.5.3.2

5.1.2 Rated conditions
5.1.2.1 General

The thermohydraulic performance of a heat exchanger shall be defined for rated conditions by:

  • type of liquid;
  • flow rate (primary and second liquid mass flow rate);
  • temperature (at primary and secondary liquid inlet and/or outlet);
  • total pressure (at primary and secondary liquid inlet and/or outlet);
  • pressure drops (of primary and secondary liquids);

SIST EN 18208:2027 EN 18208:2026 (E) - physical properties of liquid (density, enthalpy and/or specific heat capacity, thermal conductivity, dynamic viscosity) and chemical composition of liquids involved (calculated at primary and secondary mean temperature); - physical properties of material used at the average temperature of the material; - fouling state of heat transfer surfaces; - auxiliary equipment requirements (e.g. purges, level controls, pumps); - environmental constraints (e.g. ambient temperature, humidity, contamination); - operating frequency (for regenerative heat exchangers).

NOTE The physical and thermodynamic properties of the liquids use international standards such as IAPWS IF95/97 for standard water and IAPWS 08 for seawater. In the absence of an international standard, an appropriate thermodynamic model to estimate the physical properties of the liquids can be proposed. Fouling kinetics, whether asymptotic (soft, fragile deposits such as particulate fouling) or not (hard, adhesive deposits such as scale), shall be taken in account at the design phase. For the single-phase liquid system of a heat exchanger, multiplying the specific heat capacity by the temperature difference on the primary and/or secondary side may be equivalent to the specific enthalpy difference of the liquid in J/kg. It shall be checked according to the fluid properties and the difference between both methods shall be less than aimed uncertainties to use heat capacity method. EXAMPLE For liquid water, if the temperature is above 250°C, it is better to use the enthalpy balance.

5.1.2.2 Flow

Flow should be viewed as the mass flow rate q relative to the normal entry or outlet. m

5.1.2.3 Temperature

The average inlet temperature shall refer to the heat exchanger inlet. The average outlet temperature shall refer to the heat exchanger outlet.

5.1.2.4 Pressure

The total inlet pressure shall be expressed as the average absolute total pressure relative to the inlet. The total outlet pressure shall be expressed as the average absolute total pressure relative to the outlet.

5.1.2.5 Fouling

The fouling thermal resistance (R and R ) of each side of the heat transfer wall is expressed as the foul1 foul2 composite value R . Fouling can also be expressed in terms of the percentage difference on the overall foul heat transfer coefficient (k).

Fouling shall be calculated using the mean values obtained through the operating test data in accordance with the following formulae:

SIST EN 18208:2027 EN 18208:2026 (E) - For fouling resistance, see Formula (1):

11 1 (1) R =−= foul kk k op clean foul - For variations in heat transfer surface (deviation of value k), see Formula (2):

kk− clean op SM= 100 (2) k op - For cleanliness factor (Cfoul), see Formula (3):

k op C = (3) foul k clean where

R is the total fouling resistance, in m °C/W; foul

k is the overall heat transfer coefficient in operation, in W/m °C; op

k is the overall heat transfer coefficient under cleanliness conditions, in W/m °C; clean

k is the inverse of R , in W/m °C; foul foul SM is the excess surface heat transfer coefficient; C is the cleanliness factor.

foul NOTE 1 The cleanliness factor is not constant and depends on test conditions. It is preferable to use the concept of fouling resistance, which is intrinsic to the heat exchanger and does not depend on test conditions. NOTE 2 In the case of new/replacement heat exchangers, the cleanliness factor is equal to 1.

5.2 Hydraulic performance

According to Bernoulli's theorem, the formula is written in the general form between inlet and outlet of a single flow in a facility; see Formula (4):

2 2 ∆p ρ ⋅ v−ρ ⋅ v+−g ρρ⋅⋅z z+ p − p (4)

inlet inlet outlet outlet inlet inlet outlet outlet inlet outlet

where

ρ is the density of the liquid, in kg/m ; v is the velocity of the liquid between points (inlet) and (outlet), in m/s;

g is the acceleration of gravity, in m/s (generally equal to 9,81); z is the height of points (inlet) and (outlet), in m; p is the static pressure of points (inlet) and (outlet), in Pa; Δp is all the mechanical energy losses or pressure drops (regular and singular) between points (inlet) and (outlet), in Pa.

q m Velocity v of the liquid is calculated using mass flow rate q , density ρ and flow section S, with v= . m ρS

SIST EN 18208:2027 EN 18208:2026 (E)

5.3 Thermal performance

5.3.1 Energy balance

The energy balance allows the total energy at the heat exchanger inlet to be compared with the total energy at its outlet, as shown in Figure 1.

This balance should be included in the test reports conducted on the heat exchangers to check the measured results.

Figure 1 — Energy balance In steady state, the enthalpy variation on the primary liquid side shall be equal to the enthalpy variation on the secondary liquid side assuming no heat losses to the environment nor heat sources inside the component. In general, the power (mechanical or electrical) supplied within the limits of the measurements, and the heat transfer (heat gains or losses) between the heat exchanger and its environment, should be considered.

Based on Figure 1, this relationship can be written in the theoretical form given in Formula (5):

q hh−+ΦΦ− q hh−−+Φ Φ (5)

m1 11 12 p1 loss1 m2 22 21 p2 loss2 where q is the mass flow rate of the primary liquid, in kg/s; m1 q is the mass flow rate of the secondary liquid, in kg/s; m2 h is the specific enthalpy of the primary liquid, at the inlet, in J/kg;

h is the specific enthalpy of the primary liquid, at the outlet, in J/kg;

h is the specific enthalpy of the secondary liquid, at the inlet, in J/kg;

h is the specific enthalpy of the secondary liquid, at the outlet, in J/kg;

Φ is the heat dissipation due to the head losses, primary side, in W; p1 Φ is the heat dissipation due to the head losses, secondary side, in W; p2 Φ are the heat losses (gains), primary side, in W; loss1 are the heat losses (gains), secondary side, in W.

Φ loss2

SIST EN 18208:2027 EN 18208:2026 (E) Generally, the previous formula is simplified as follows because heat losses to surroundings and head losses thermal impact are negligible, see Formula (6):

q hh−= q hh− (6)

m1 11 12 m2 22 21

5.3.2 Heat transfer rate

The heat transfer rate of a single-phase heat exchanger (i.e. when the two liquids remain in liquid state) is characterized by the following formulae: see Formula (7) for primary side and Formula (8) for secondary side.

φφq××c TT− + (7)

1 m1 p1 11 12 loss1 φφq××c TT− + (8)

2 m2 p2 22 21 loss2 where ϕ is the heat transfer rate, in W and is positive; qm is the mass flow rate, in kg/s; c is the specific heat capacity at constant pressure, in J/kg °C; p T is the temperature, in °C; or is the subscript relative to the heat exchanger primary circuit or secondary circuit; 1 2 ϕ is the heat loss or gain due to the surrounding environment, in W. loss In this relationship, the heat exchanger heat balance describes the fact that the heat transferred by the primary liquid is equal to the heat captured by the secondary liquid, adjusted for heat losses or gains to/from the surrounding environment.

When the enthalpy function of the fluid is known, it shall be used to determine heat transfer rate as it is more accurate than the heat capacity at average temperature.

5.3.3 Heat transfer coefficients

The heat transfer can be characterized by various types of heat transfer coefficients that express the heat transfer rate per heat transfer surface area unit and per temperature difference unit. The heat transfer coefficients shall be given separately for primary and secondary flows and aggregated in an overall heat transfer coefficient. The overall heat transfer coefficient combines the effects of convection and conduction between the two flows and the heat transfer surface of the heat exchanger, and fouling.

The conditions for establishing the heat transfer coefficient — for example the conditions for establishing the heat transfer surface area and the temperature difference — shall be described. In this document, the overall heat transfer coefficient should be used. This coefficient is calculated based on the log mean temperature difference (5.3.5.2) and the total heat transfer surface area in contact with either liquid, by adding fins or any other type of additional surface. Under normal operating conditions, the calculated values of the overall heat transfer coefficient might need to be adjusted using the fouling coefficients from each side of the heat transfer wall, as shown in 5.1.2.5. The value of the overall heat transfer shall be specified at the time of purchase.

SIST EN 18208:2027 EN 18208:2026 (E)

5.3.4 Heat transfer surface

The part of the surface of the heat exchanger channel walls that is involved in the heat transfer process is called the heat transfer surface.

...