FprEN 1838
(Main)Lighting applications - Emergency lighting for buildings
Lighting applications - Emergency lighting for buildings
This document specifies the luminous requirements for emergency lighting systems, including adaptive emergency escape lighting systems, electric emergency lighting, installed in premises or locations where such systems are required or needed and which are principally applicable to locations where the public or workers have access.
Angewandte Lichttechnik - Notbeleuchtung für bauliche Anlagen
Dieses Dokument legt die lichttechnischen Anforderungen für Notbeleuchtungsanlagen fest, einschließlich adaptiver Sicherheitsbeleuchtungsanlagen, elektrischer Notbeleuchtung, die in Räumlichkeiten oder an Orten installiert werden, an denen solche Systeme erforderlich sind oder benötigt werden, und die hauptsächlich für Orte bestimmt sind, zu denen die Öffentlichkeit oder Arbeitnehmer Zugang haben.
Éclairagisme - Éclairage de secours pour les bâtiments
This document specifies the luminous requirements for emergency lighting systems, including adaptive emergency escape lighting systems, electric emergency lighting, installed in premises or locations where such systems are required or needed and which are principally applicable to locations where the public or workers have access.
Razsvetljava - Zasilna razsvetljava
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
oSIST prEN 1838:2022
01-julij-2022
Razsvetljava - Zasilna razsvetljava
Lighting applications - Emergency lighting
Angewandte Lichttechnik - Notbeleuchtung
Éclairagisme - Éclairage de secours
Ta slovenski standard je istoveten z: prEN 1838
ICS:
91.160.10 Notranja razsvetljava Interior lighting
oSIST prEN 1838:2022 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
oSIST prEN 1838:2022
oSIST prEN 1838:2022
DRAFT
EUROPEAN STANDARD
prEN 1838
NORME EUROPÉENNE
EUROPÄISCHE NORM
May 2022
ICS 91.160.10 Will supersede EN 1838:2013
English Version
Lighting applications - Emergency lighting
Éclairagisme - Éclairage de secours Angewandte Lichttechnik - Notbeleuchtung
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee
CEN/TC 169.
If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations
which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC
Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and
United Kingdom.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are
aware and to provide supporting documentation.
Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without
notice and shall not be referred to as a European Standard.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2022 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 1838:2022 E
worldwide for CEN national Members.
oSIST prEN 1838:2022
prEN 1838:2022 (E)
Contents Page
European foreword . 4
Introduction . 5
1 Scope . 7
2 Normative references . 7
3 Terms and definitions . 7
4 Emergency escape lighting . 10
4.1 General. 10
4.2 Points of emphasis . 12
4.3 Requirements for specific areas . 13
4.3.1 Toilets and changing rooms . 13
4.3.2 Swimming pools . 13
4.3.3 Motor generator, control, switch and plant rooms . 14
4.4 Escape route lighting . 14
4.5 Open area (anti-panic) lighting . 16
4.6 Local area safety lighting . 16
4.7 High risk task area safety lighting . 17
4.8 Standby lighting . 17
5 Safety signs . 18
5.1 General. 18
Annex A (informative) Rated duration and activation times . 21
A.1 Introduction . 21
A.2 Rated duration . 21
A.3 Activation times . 22
Annex B (informative) On-site luminance and illuminance measurements . 23
B.1 Introduction . 23
B.2 General. 23
B.3 Illuminance and luminance meters. 24
B.4 Measurement of emergency lighting illuminance levels . 24
B.4.1 General considerations . 24
B.4.2 Method A . 25
B.4.3 Method B . 25
B.4.4 Method C . 26
B.4.5 Method D . 26
B.5 Illuminance measurements on site . 27
B.5.1 General. 27
oSIST prEN 1838:2022
prEN 1838:2022 (E)
B.5.2 Illuminance measurements of open area (anti panic) lighting, local area lighting and
high-risk task area lighting . 28
B.5.2.1 Initial verification . 28
B.5.2.2 Five-year verification . 28
B.5.3 Illuminance measurement of escape route lighting . 28
B.6 Emergency escape route safety signs . 29
B.6.1 Internally illuminated escape route safety signs . 29
B.6.1.1 Initial verification . 29
B.6.1.2 Five-year verification . 29
B.6.2 Externally illuminated escape route safety signs . 29
B.6.2.1 Initial verification . 29
B.6.2.2 Five-year verification . 30
B.7 Conformity assessment . 30
Annex C (informative) Local area safety lighting . 31
Annex D (informative) A–deviations . 32
Bibliography . 34
oSIST prEN 1838:2022
prEN 1838:2022 (E)
European foreword
This document (prEN 1838:2022) has been prepared by Technical Committee CEN/TC 169 “Light and
lighting”, the secretariat of which is held by DIN.
This document is currently submitted to the CEN Enquiry.
This document will supersede EN 1838:2013.
oSIST prEN 1838:2022
prEN 1838:2022 (E)
Introduction
Emergency lighting is provided for use when the supply to the normal lighting fails and is therefore
powered from a source independent of that supplying the normal lighting. It may provide lighting for
both safety and operational tasks.
For the purposes of this document emergency lighting is regarded as a generic term of which there are a
number of specific forms, as shown in Table 1.
Table 1 — Specific forms of emergency lighting
Emergency lighting 4
Emergency escape lighting Standby
lighting 6
Escape route Open area
Local area High risk task
lighting (anti-panic) lighting area lighting
lighting
5.1 5.3 5.4
5.2
Safety signs including adaptive safety signs 7
Emergency lighting can also be provided by maintained luminaires and maintained escape route safety
signs when the normal lighting is available. Maintained luminaires and maintained exit and escape route
safety signs shall operate when the normal lighting is required and when the normal lighting fails. (Refer
to EN 50172 for further details on normal lighting failures.)
Forms of emergency lighting and their applications.
Emergency escape lighting is provided to enable safe exit from a location in the event of failure of the
normal supply. The objective of each form within this category is as follows.
The objective of escape route lighting is to assist the safe exit from a location for occupants by providing
appropriate visual conditions and direction finding on escape routes and in special locations, and to
ensure that fire-fighting and safety equipment can be readily located and used.
The objective of emergency lighting escape routes is to be readily located and used. A multi-purpose
luminaire that provides direction finding and escape route lighting may be used.
The objective of open area (anti-panic) lighting is to reduce the likelihood of panic and to enable safe
movement of occupants towards escape routes by providing appropriate visual conditions and direction
finding. The flow of light for escape routes or open areas should be downward to the working plane but
illumination should also be provided to any obstruction.
Safety Lighting provides illumination for the safety of people involved in a potentially hazardous process
or situation.
The objective of local area safety lighting is to protect occupants who are allowed to remain in a premise
in the event of a supply failure. It is based on a safety risk assessment dependent upon the activities likely
to be performed. Additional areas of coverage and levels of illumination higher than the provision for
emergency escape lighting may be required.
The objective of high-risk task area lighting is to contribute to the safety of people involved in a
potentially dangerous process or situation and to assist proper shut down procedures to be carried out
for the safety of other people in the location.
oSIST prEN 1838:2022
prEN 1838:2022 (E)
Standby Lighting is based on operational requirements. This standard gives the definition of the term
and describes the principles and requirements to be complied with in context with the emergency escape
lighting.
There are techniques such as adaptive emergency escape lighting (AEELS) that can be used as a
supplement to emergency escape lighting and, when applied to escape routes in addition to emergency
escape lighting, can enhance their effectiveness in an emergency. These techniques are not included in
this standard.
Much anxiety and confusion can be alleviated by strategically placed escape route safety signs indicating
the way out of a location. It is very important that exits are clearly signposted and are visible, whenever
the location is occupied.
oSIST prEN 1838:2022
prEN 1838:2022 (E)
1 Scope
This document specifies the luminous requirements for emergency lighting systems, including static and
non-static, high- and low-mounted electric emergency
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.