Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware - Part 7: Fire resistance for steel sliding doorsets

This European Standard, which should be read in conjunction with prEN 15269-1, covers the following types of steel based doorsets: horizontally sliding doorsets (single and double), telescopic doorsets (single and double) and single vertically sliding doorsets.
This document prescribes the methodology for extending the application of test results obtained from test(s) conducted in accordance with EN 1634-1.
Subject to the completion of the appropriate test or tests selected from those identified in Clause 4 the extended application may cover all or some of the following non-exhaustive list:
- integrity only (E), radiation (EW) or insulated (EI1 or EI2) classifications;
- door leaf;
- wall/ceiling fixed elements (frame/suspension system);
- glazing for door leaf;
- items of building hardware;
- decorative finishes;
- intumescent, smoke, draught or acoustic seals;
- alternative supporting construction(s).

Erweiterter Anwendungsbereich von Prüfergebnissen zur Feuerwiderstandsfähigkeit und/oder Rauchdichtigkeit von Türen, Toren und Fenstern einschließlich ihrer Baubeschläge - Teil 7: Feuerwiderstandsfähigkeit von Schiebetoren aus Stahl

Diese Europäische Norm gilt in Verbindung mit prEN 15269 1 und deckt die folgenden Arten von Stahltoren ab: horizontal öffnende Schiebetore (ein- oder zweiflügelig), Teleskoptore (ein- oder zweiflügelig) und von einer Seite aus vertikal öffnende Schiebetore.
Dieses Dokument legt die Methodologie zur Erweiterung der Anwendung von Ergebnissen aus Prüfungen nach EN 1634 1 fest.
In Abhängigkeit von der Durchführung der entsprechenden Prüfung oder Prüfungen, die aus den in Abschnitt 4 aufgeführten auszuwählen sind, kann der erweiterte Anwendungsbereich einige oder alle der nachstehend aufgeführten Bereiche abdecken, wobei diese Liste nicht vollständig ist:
-   Klassifizierung von nicht wärmegedämmten Abschlüssen (E), sowie solchen mit Anforderungen an die Strahlung (EW) oder wärmegedämmten Abschlüssen (EI1 oder EI2);
-   Türflügel;
-   an der Wand/Decke befestigte Elemente (Zarge/Aufhängungssysteme);
-   verglaste Teilbereiche;
-   Baubeschläge;
-   dekorative Beschichtungen;
-   dämmschichtbildende Dichtungen, sowie Dichtungen zur Behinderung von Rauchdurchtritt (Rauchschutz-dichtungen), Durchzug oder der Schallübertragung (Schallschutzdichtungen);
-   alternative Tragkonstruktionen.

Application élargie des résultats d'essai en matières de résistance au feu et d'étanchéité à la fumée des blocs-portes, blocs-fermetures et ouvrants de fenêtres, y compris les éléments intégrés de quincaillerie de bâtiment - Partie 7: Résistance au feu des blocs-portes coulissants en acier

La présente Norme européenne, qu'il convient de lire conjointement avec le prEN 15269-1, couvre les types
suivants de blocs-portes en acier : blocs-portes coulissant horizontalement (à simple vantail ou double
vantail), blocs-portes télescopiques (à simple vantail ou double vantail) et blocs-portes coulissant
verticalement à simple vantail.
Le présent document prescrit la méthodologie d'extension de l'application des résultats d'essai obtenus suite
aux essais réalisés conformément à l'EN 1634-1.
Sous réserve de la réalisation de l'essai ou des essais appropriés sélectionnés parmi ceux identifiés à
l'Article 4, l'application élargie peut couvrir tout ou partie de la liste suivante non exhaustive :
- classement d'étanchéité au feu uniquement (E), de rayonnement (EW) ou d'isolation thermique (EI1 ou
EI2) ;
- vantail ;
- éléments fixés au mur/plafond (ossature/système de suspension) ;
- vitrage de vantail ;
- éléments de quincaillerie de bâtiment ;
- finitions décoratives ;
- joints intumescents, d'étanchéité à la fumée, d'étanchéité à l'air ou acoustique ;
- autre(s) construction(s) support.

Razširjena uporaba rezultatov preskusov požarne odpornosti in nadzora dima za vrata, zaporne elemente ter okna, ki se odpirajo, vključno z vgrajenimi elementi gradbenega okovja - 7. del: Požarna odpornost za jeklena drsna vrata

Ta evropski standard, ki se mora obravnavati v povezavi s prEN 15269-1, vključuje naslednje vrste vrat na osnovi jekla: vodoravna drsna vrata (enojna in dvojna), teleskopska vrata (enojna in dvojna) in enojna navpična drsna vrata. Ta dokument predpisuje metodologijo za razširitev uporabe rezultatov preskusa, pridobljenih s preskusi, opravljenimi v skladu z EN 1634-1. Razširjena uporaba lahko v skladu z opravljenim ustreznim preskusom ali preskusi, izbranimi med tistimi, opredeljenimi v Klavzuli 4, vključuje vse ali del navedenega v naslednjem neizčrpnem seznamu: razvrstitev le glede na integriteto (E), sevanje (EW) ali izolirana razvrstitev (EI1 ali EI2); vratno krilo; fiksni elementi na steni/stropu (ogrodje/sistem za obešanje); zasteklitev vratnih kril; izdelki gradbene strojne opreme; okrasni zaključki; intumescenčna, dimna, vetrovna ali akustična tesnila; alternativne podporne konstrukcije.

General Information

Status
Published
Publication Date
03-Nov-2009
Withdrawal Date
30-May-2010
Current Stage
9060 - Closure of 2 Year Review Enquiry - Review Enquiry
Start Date
03-Jun-2024
Completion Date
03-Jun-2024

Buy Standard

Standard
EN 15269-7:2010
English language
79 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.DWDErweiterter Anwendungsbereich von Prüfergebnissen zur Feuerwiderstandsfähigkeit und/oder Rauchdichtigkeit von Feuerschutzabschlüssen und Fenstern einschließlich ihrer Baubeschläge - Teil 7: Feuerwiderstandsfähigkeit von Schiebetoren aus StahlApplication élargie des résultats d'essai en matière de résistance au feu et d'étanchéité à la fumée des blocs-portes, blocs-fermetures et ouvrants de fenêtres, y compris les éléments intégrés de quincaillerie de bâtiment - Partie 7: Résistance au feu des blocs-portes coulissants en acierExtended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware - Part 7: Fire resistance for steel sliding doorsets91.060.50Vrata in oknaDoors and windows13.220.50Požarna odpornost gradbenih materialov in elementovFire-resistance of building materials and elementsICS:Ta slovenski standard je istoveten z:EN 15269-7:2009SIST EN 15269-7:2010en,de01-februar-2010SIST EN 15269-7:2010SLOVENSKI
STANDARD
EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 15269-7
November 2009 ICS 13.220.50; 91.060.50 English Version
Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware - Part 7: Fire resistance for steel sliding doorsets
Application élargie des résultats d'essai en matière de résistance au feu et d'étanchéité à la fumée des blocs-portes, blocs-fermetures et ouvrants de fenêtres, y compris les éléments intégrés de quincaillerie de bâtiment - Partie 7: Résistance au feu des blocs-portes coulissants en acier Erweiterter Anwendungsbereich von Prüfergebnissen zur Feuerwiderstandsfähigkeit und/oder Rauchdichtigkeit von Türen, Toren und Fenstern einschließlich ihrer Baubeschläge - Teil 7: Feuerwiderstandsfähigkeit von Schiebetoren aus Stahl This European Standard was approved by CEN on 22 September 2009.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre:
Avenue Marnix 17,
B-1000 Brussels © 2009 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 15269-7:2009: ESIST EN 15269-7:2010

EN 15269, Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware  Part 7: Fire resistance for steel sliding doorsets  Part 20: Smoke control for hinged and pivoted steel, timber and metal framed glazed doorsets
Before there can be any consideration for extended application the doorset should have been tested in accordance with EN 1634-1 to achieve a test result which could generate a classification in accordance with EN 13501-2 at least equal to the classification subsequently required from extended application considerations. A review of the doorset construction parameters can indicate that one or more characteristics may be improved by a particular parameter variation. All evaluations should be made on the basis of retaining the fire resistance classifications obtainable from testing to EN 1634-1, including those lower than the test duration. However, this should never lead to an increased classification for any specific fire or smoke performance parameter beyond that achieved during any one test unless specifically identified in the relevant Construction Parameter Variation tables within this series of standards. The effect on the durability of self closing of the doorsets following an extended application process is not addressed in this series of standards. SIST EN 15269-7:2010

EN 13501-2:2007, Fire classification of construction products and building elements — Part 2: Classification using data from fire resistance tests, excluding ventilation services
EN 15254-4:2008, Extended application of results from fire resistance tests — Non-loadbearing walls — Part 4: Glazed constructions prEN 15269-1:2007, Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware — Part 1: General requirements SIST EN 15269-7:2010

EN ISO 13943:2000, EN 1634-1:2008, EN 1634-2:2008 and prEN 15269-1:2007 together with the following apply. 3.1 full scale test test of a full size doorset in accordance with EN 1634-1 3.2 leaf/element/panel different parts of a doorset as indicated in Figures 1 and 2 below
123 Key 1
panel 2
leaf 3
element Figure 1 — Double leaf telescopic door SIST EN 15269-7:2010

Key 1
panel 2
leaf Figure 2 — Double leaf sliding door 4 Determination of the field of extended application
4.1 General 4.1.1 Before there can be any consideration for extended application the doorset shall have been tested and classified in accordance with EN 1634-1 and EN 13501-2 respectively in order to establish a classification for the doorset. 4.1.2 A review of the doorset construction parameters can indicate that one or more characteristics may be improved by a particular parameter variation. All evaluations shall be made on the basis of retaining the classifications obtainable from testing to EN 1634-1, including those lower than the test duration. However, this shall never lead to an increased classification for any specific parameter beyond that achieved during any one test unless specifically identified in the relevant Construction Parameter Variation tables. 4.1.3 All evaluations shall be made on the basis of retaining the classification obtained from testing to EN 1634-1. 4.1.4 If, by following the ensuing procedure, any part of the classification cannot be achieved by extended application rules that part of classification shall be omitted from the subsequent extended application report and classification report. 4.2 Procedure for evaluation 4.2.1 Identify the variations from the original test specimen(s) which are required to be covered by an extended application report. 4.2.2 Locate the variations in the appropriate parameter variation by reference to columns (1) and (2) of Table A.1. 4.2.3 Review the type of classification to be retained from column (3) of Table A.1 and establish from the contents of column (4) of Table A.1 whether any extended application is available without the need for further testing. 4.2.4 Where this is deemed to be possible this can be recorded in the extended application report together with any appropriate restrictions and the stated rules from column (4) in Table A.1. 4.2.5 Where the variations required can only be achieved from additional testing according to column (5) in Table A.1, the additional test can be made on a similar specimen type to the original test SIST EN 15269-7:2010

4.3.1 It is possible to provide a limited field of ext
...