Type B residual current operated circuit-breakers with and without integral overcurrent protection for household and similar uses (Type B RCCBs and Type B RCBOs)

The scope of IEC 61008-1 and IEC 61009-1 applies. This standard specifies requirements and tests for type B RCDs. Requirements and tests given in this standard are in addition to the requirements of type A residual current devices. Type B RCCBs and Type B RCBOs are able to provide protection in case of alternating residual sinusoidal currents up to 1 000 Hz, pulsating direct residual currents and smooth direct residual currents in case of three phase supply.

Typ B Fehlerstsrom-/Differenzstrom-Schutzschalter mit und ohne eingebautem Überstromschutz für Hausinstallationen und für ähnliche Anwendungen (Typ B RCCBs und Typ B RCBOs)

Interrupteurs automatiques à courant différentiel résiduel de Type B avec et sans protection contre les surintensités incorporée pour usages domestiques et analogues (ID et DD de Type B)

Les domaines d'application de la CEI 61008-1 et de la CEI 61009-1 s'appliquent. La présente norme spécifie les exigences et les essais pour les DDR de Type B. Les exigences et les essais donnés dans la présente norme complètent les exigences des dispositifs à courant différentiel résiduel de Type A. Les ID de Type B et les DD de Type B sont aptes à assurer la protection en cas de courants différentiels alternatifs sinusoïdaux jusqu'à 1 000 Hz, de courants différentiels continus pulsés et de courants différentiels continus lissés dans le cas d'une alimentation triphasée.

Odklopniki na preostali tok tipa B z vgrajeno nadtokovno zaščito in brez nje za gospodinjsko in podobno rabo (tip B RCCBs in tip B RCBOs) (IEC 62423:2007, spremenjen)

General Information

Status
Withdrawn
Publication Date
21-Oct-2009
Withdrawal Date
30-Jun-2012
Current Stage
9960 - Withdrawal effective - Withdrawal
Start Date
19-Jun-2017
Completion Date
19-Jun-2017

Relations

Buy Standard

Standard
EN 62423:2009
English language
43 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-december-2009
2GNORSQLNLQDSUHRVWDOLWRNWLSD%]YJUDMHQRQDGWRNRYQR]DãþLWRLQEUH]QMH]D
JRVSRGLQMVNRLQSRGREQRUDER WLS%5&&%VLQWLS%5&%2V  ,(&
VSUHPHQMHQ
Type B residual current operated circuit-breakers with and without integral overcurrent
protection for household and similar uses (Type B RCCBs and Type B RCBOs) (IEC
62423:2007, modified)
Typ B Fehlerstsrom-/Differenzstrom-Schutzschalter mit und ohne eingebautem
Überstromschutz für Hausinstallationen und für ähnliche Anwendungen (Typ B RCCBs
und Typ B RCBOs) (IEC 62423:2007, modifiziert)
Interrupteurs automatiques à courant différentiel résiduel de Type B avec et sans
protection contre les surintensités incorporée pour usages domestiques et analogues (ID
et DD de Type B) (CEI 62423:2007, modifiée)
Ta slovenski standard je istoveten z: EN 62423:2009
ICS:
29.120.50 9DURYDONHLQGUXJD Fuses and other overcurrent
PHGWRNRYQD]DãþLWD protection devices
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD
EN 62423
NORME EUROPÉENNE
October 2009
EUROPÄISCHE NORM
ICS 29.120; 29.120.50
English version
Type B residual current operated circuit-breakers
with and without integral overcurrent protection
for household and similar uses
(Type B RCCBs and Type B RCBOs)
(IEC 62423:2007, modified)
Interrupteurs automatiques  Typ B Fehlerstsrom-/Differenzstrom-
à courant différentiel résiduel de Type B Schutzschalter mit und ohne eingebautem
avec et sans protection contre Überstromschutz für Hausinstallationen
les surintensités incorporée und für ähnliche Anwendungen
pour usages domestiques et analogues (Typ B RCCBs und Typ B RCBOs)
(ID et DD de Type B) (IEC 62423:2007, modifiziert)
(CEI 62423:2007, modifiée)
This European Standard was approved by CENELEC on 2009-07-01. CENELEC members are bound to comply
with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and notified
to the Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the
Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: Avenue Marnix 17, B - 1000 Brussels

© 2009 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 62423:2009 E
Foreword
The text of the International Standard IEC 62423:2007, prepared by SC 23E, Circuit-breakers and
similar equipment for household use, of IEC TC 23, Electrical accessories, together with the common
modifications prepared by the Technical Committee CENELEC TC 23E, Circuit breakers and similar
devices for household and similar applications, was submitted to the Unique Acceptance Procedure
and was approved by CENELEC as EN 62423 on 2009-07-01.
The following dates were fixed:
– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2010-07-01
– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2012-07-01
This European Standard has been prepared under a mandate given to CENELEC by the European
Commission and the European Free Trade Association and covers essential requirements of
EC Directive 2004/108/EC. See Annex ZZ.
Clauses, subclauses, notes, tables and figures which are additional to those in IEC 62423 are
prefixed “Z”.
Annexes ZA, ZB and ZZ have been added by CENELEC.
__________
- 3 - EN 62423:2009
Endorsement notice
The text of the International Standard IEC 62423:2007 was approved by CENELEC as a European
Standard with agreed common modifications as given below.
COMMON MODIFICATIONS
Contents Add:
9.Z1 Electromagnetic compatibility (EMC)
Annex ZA Normative references to international publications
with their corresponding European publications
Annex ZB Special national conditions
Annex ZZ Coverage of Essential Requirements of EC Directives
Table Z1 Tests to be applied for EMC
Table A.Z1
Table A.Z2 Number of samples for full test procedure
Table A.Z3 Number of samples for simplified test procedure
Table B.Z1
Table B.Z2 Number of samples for full test procedure
Table B.Z3 Number of samples for simplified test procedure
1 Scope
Replace the first two paragraphs by the following new paragraphs:
The scope of EN 61008-1 and EN 61008-2-1 or EN 61009-1 and EN 61009-2-1 applies.
This standard specifies requirements and tests for type B RCDs. Requirements and
tests given in this standard are in addition to the requirements of type A residual current
devices according to EN 61008-2-1 or EN 61009-2-1. Type B RCCBs and type B RCBOs
are able to provide protection in case of alternating residual sinusoidal currents up to
1 000 Hz, pulsating direct residual currents and smooth direct residual currents in case
of three phase supply.
Delete the fifth paragraph.
Replace note 2 by the following new note:

NOTE 2 Requirements for 2 poles devices are under consideration.
5 Characteristics
5.3 Delete the value "60 Hz" three times: in the title of 5.3, in the title of Table 2 and in
note 4 of Table 2.
9 Tests
9.2 Delete the third paragraph.

9.Z1 Add the new following subclause:
9.Z1 Electromagnetic compatibility (EMC)
EMC tests shall be performed according to EN 61543 as follows:
– Tests listed in the following table are covered by EN 61008-1 or EN 61009-1 as
applicable and have not to be repeated:
Table Z1 – Tests to be applied for EMC
Reference to Tables 4
Electromagnetic phenomena Tests of EN 61008-1 Tests of EN 61009-1
and 5 of EN 61543
T 1.3 Voltage amplitude variations 9.9.5 and 9.17 9.9.1.5 and 9.17
T 1.4 Voltage unbalance 9.9.5 and 9.17 9.9.1.5 and 9.17
T 1.5 Power frequency variations 9.2 9.2
T 1.8 Magnetic fields 9.11 and 9.18 9.12 and 9.18
T 2.4 Current oscillatory transients 9.19 9.19

– The remaining tests in Tables 4, 5 and 6 of EN 61543 shall be done according to

the test sequences Z1, Z2 and Z3 listed in Annex A or B of this standard.
For devices containing a continuously operating oscillator, the test of EN 55014 (series)
shall be carried out on the samples prior to the tests of EN 61543.
Annex A Number of samples to be submitted and test sequences to be applied
for verification of conformity for type B RCCBs
Modify the note before A.1 into a requirement.

Table A.1 Replace the second column heading by the following:
Tests according to EN 61008-1 and EN 61008-2-1
Delete in sequence D the row referred to 9.17.
a
Modify footnote reference into *.
Add the following new test sequences D and H:

D 9.11.2.3 c) Verification of the suitability in IT system
H 9.24 Verification of correct operation at low ambient air
temperature of RCCBs for use in the range of -25 °C
to +40 °C
a
Replace footnote by the following new footnote *:

* An additional test according to 9.21.1.1 shall be made with a supply voltage of 1,1 U . Only the lower
n
limits of the tripping currents are verified.
Delete the last sentence after Table A.1.

- 5 - EN 62423:2009
Add the following new Tables A.Z1, A.Z2 and A.Z3.

Table A.Z1
Test Tests according to EN 61543 Test (or Inspection)
sequence
Harmonics, interharmonics
EN 61543 Table 4 – T1.1
EN 61543 Table 4 – T1.2 Signalling voltage
a
Z1
EN 61543 Table 5 – T2.3 Conducted unidirectional transients of the ms

and µs time scale
EN 61543 Table 5 – T2.1 and T2.5 Conducted oscillatory voltages or currents
Z2
EN 61543 Table 5 – T2.2 Conducted unidirectional transients of the ns
time scale (burst)
EN 61543 Table 5 – T2.6 Conducted common mode disturbances in the
frequency range lower than 150 kHz
Z3
EN 61543 Table 6 – T3.1 Electrostatic discharges
a
For devices containing a continuously operating oscillator, the test of EN 55014 series shall be carried out
on the samples prior to the tests of this sequence.

Table A.Z2 – Number of samples for full test procedure

Test sequence Number of samples Minimum number of Maximum number of
samples which shall samples for repeated
a b c
pass the tests tests
A 1 1 –
B 3 2 3
d
C 3 2 3
d
D 3 2 3
D2 3 2 3
d
E 3 2 3
d
F 3 2 3
d
F 3 2 3
G 3 2 3
H 3 2 3
e
Z1 3 2 3
e
Z2 3 2 3
e
Z3 3 2 3
a
In total a maximum of three test sequences may be repeated.
b
It is assumed that a sample which has not passed a test has not met the requirements due to
workmanship or assembly defects which are not representative of the design.
c
In the case of repeated tests, all test results must be acceptable.
d
Except for tests of 9.12.10, 9.12.11.2, 9.12.11.3, 9.12.11.4, and 9.12.13, as appropriate, which all
samples shall pass.
e
On request of the manufacturer the same set of samples may be subjected to more than one of these test
sequences.
Table A.Z3 – Number of samples for simplified test procedure
a
Test Number of samples according to number of poles
sequence
b c
2 poles 3 poles 4 poles
max. rating I max. rating I max. rating I
n n n
A 1 1 1
min. rating I min. rating I min. rating I
∆n ∆n ∆n
max. rating I max. rating I max. rating I
n n n
B 3 3 3
min. rating I min. rating I min. rating I
∆n ∆n ∆n
max. rating I max. rating I max. rating I
n n n
C 3 3 3
min. rating I min. rating I min. rating I
∆n ∆n ∆n
max. rating I max. rating I max. rating I
n n n
D0 + D1 3 3 3
min. rating I min. rating I min. rating I
∆n ∆n ∆n
for all other ratings
D 1
of I
∆n
max. rating I max. rating I max. rating I
n n n
D 3 3 3
min. rating I min. rating I min. rating I
∆n ∆n ∆n
max. rating I max. rating I max. rating I
n n n
E 3 3 3
min. rating I min. rating I min. rating I
∆n ∆n ∆n
max. rating I max. rating I max. rating I
n n n
3 3 3
min. rating I min. rating I min. rating I
∆n ∆n ∆n
F
min. rating I min. rating I min. rating I
d n d n d n
3 3 3
max. rating I max. rating I max. rating I
∆n ∆n ∆n
max. rating I max. rating I max. rating I
n n n
3 3 3
min. rating I min. rating I min. rating I
∆n ∆n ∆n
G
min. rating I min. rating I min. rating I
d n d n d n
3 3 3
max. rating I max. rating I max. rating I
∆n ∆n ∆n
max. rating I max. rating I max. rating I
n n n
3 3 3
min. rating I min. rating I min. rating I
∆n ∆n ∆n
H
min. rating I min. rating I min. rating I
d n d n d n
3 3 3
max. rating I max. rating I max. rating I
∆n ∆n ∆n
any rating I any rating I any rating I
e n n n
Z1 3 3 3
min. rating I min. rating I min. rating I
∆n ∆n ∆n
any rating I any rating I any rating I
e n n n
Z2 3 3 3
min. rating I min. rating I min. rating I
∆n ∆n ∆n
e any rating I any rating I any rating I
n n n
Z3 3 3 3
min. rating I min. rating I min. rating I
∆n ∆n ∆n
a
If a test is to be repeated according to the minimum performance criteria of A.2, a new set of samples is
used for the relevant test. In the repeated test all test results must be acceptable.
b
If only 3-pole or 4-pole RCCBs are submitted, this column shall also apply to a set of samples with the
smallest number of poles.
c
This column is omitted when 4-pole RCCBs have been tested.
d
If only one value of I is submitted, these sets of samples are not required.
∆n
e
If a range of RCCBs of the same fundamental design are submitted, only the samples with the maximum
number of poles need to be tested.

- 7 - EN 62423:2009
Annex B Number of samples to be submitted and test sequences to be applied
for verification of conformity for type B RCCOs
Modify the note before B.1 into a requirement.
Table B.1 Replace the second column heading by the following:
Tests according to EN 61009-1 and EN 61009-2-1
Replace the test sequences C and C by the following:
1 2
9.10 Mechanical and electrical endurance
-- 9.3 Verification of the RCD after test sequence
C
9.12.11.2.Z1 Performance at reduced short-circuit currents

(and 9.12.12) (Verification of the RCBO after short-circuit tests)
9.12.11.2.Z2 Short-circuit test for verifying the suitability of RCBOs
C  for use in IT systems
(and 9.12.12) (Verification of the RCBO after short-circuit tests)

Delete in sequence D the rows referred to 9.17 and 9.12.13.

a
Modify footnote reference into *.

a
Replace footnote by the following new footnote *:

* An additional test according to 9.21.1.1 shall be made with a supply voltage of 1,1 Un. Only the lower
limits of the tripping currents are verified.
Delete the last sentence after Table B.1.

Add the following new Tables B.Z1, B.Z2 and B.Z3.

Table B.Z1
Test Tests according to EN 61543 Test (or Inspection)
sequence
Harmonics, interharmonics
EN 61543 Table 4 – T1.1
a EN 61543 Table 4 – T1.2 Signalling voltage
Z1
EN 61543 Table 5 – T2.3 Conducted unidirectional transients of the ms

and µs time scale
EN 61543 Table 5 – T2.1 and T2.5 Conducted oscillatory voltages or currents
Z2
EN 61543 Table 5 – T2.2 Conducted unidirectional transients of the ns
time scale (burst)
EN 61543 Table 5 – T2.6 Conducted common mode disturbances in the
frequency range lower than 150 kHz
Z3
EN 61543 Table 6 – T3.1 Electrostatic discharges
a
For devices containing a continuously operating oscillator, the test of EN 55014 series shall be carried out
on
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.