Type F and type B residual current operated circuit-breakers with and without integral overcurrent protection for household and similar uses (IEC 62423:2009, modified + corrigendum Dec. 2011)

The scope of IEC 61008-1 and IEC 61009-1 applies with the following additions. This standard specifies requirements and tests for Type F and Type B RCDs (Residual Current Devices). Requirements and tests given in this standard are in addition to the requirements of Type A residual current devices. This standard can only be used together with IEC 61008-1 and IEC 61009-1. Type F RCCBs (Residual Current Circuit Breaker) and Type F RCBOs (Residual current Circuit Breaker with Overcurrent protection) with rated frequency 50 Hz or 60 Hz are intended for installations when frequency inverters are supplied between phase and neutral or phase and earthed middle conductor and are able to provide protection in case of alternating residual sinusoidal at the rated frequency, pulsating direct residual currents and composite residual currents that may occur. Type B RCCBs and Type B RCBOs are able to provide protection in case of alternating residual sinusoidal currents up to 1 000 Hz, pulsating direct residual currents and smooth direct residual currents. RCDs according to this standard are not intended to be used in d.c. supply systems. Further requirements and tests for products to be used in situations where the residual current was not intended to be covered in IEC 61008-1 or IEC 61009-1 are under consideration. For the purpose of manufacturer’s declaration or verification of conformity, type tests should be carried out in test sequences in compliance with Annex A, Annex B, Annex C or Annex D of this standard. The complete test sequence for type test of Type F RCCBs and Type F RCBOs is given in Tables A.1 and B.1 respectively. The complete test sequence for type test of Type

Fehlerstrom-/Differenzstrom-Schutzschalter Typ F und Typ B mit und ohne eingebautem Überstromschutz für Hausinstallationen und für ähnliche Anwendungen (IEC 62423:2009, modified + corrigendum Dec. 2011) (IEC 62423:2009, modifiziert)

Interrupteurs automatiques à courant différentiel résiduel de type B et de type F avec et sans protection contre les surintensités incorporée pour usages domestiques et analogues ( (IEC 62423:2009, modified + corrigendum Dec. 2011)CEI 62423:2009, modifiée)

Les domaines d'application de la CEI 61008-1 et de la CEI 61009-1 s'appliquent avec les additions suivantes. La CEI 62423:2009 spécifie les exigences et les essais pour les DDR (dispositif de protection à courant différentiel résiduel) de Type B et de Type F. Les exigences et les essais donnés dans la présente norme complètent les exigences des dispositifs à courant différentiel résiduel de Type A. La présente norme ne peut être utilisée que conjointement à la CEI 61008-1 et à la CEI 61009-1. Les ID (interrupteur différentiel sans protection contre les surintensités incorporée) de Type F et les DD (interrupteur différentiel avec protection contre les surintensités incorporée) de Type F de fréquence assignée 50 Hz ou 60 Hz sont destinés à des installations dans lesquelles les convertisseurs de fréquence sont alimentés entre phase et neutre ou entre phase et conducteur milieu mis à la terre et sont aptes à assurer la protection en cas d'apparition de courant différentiel alternatif sinusoïdal à la fréquence assignée, de courant différentiel continu pulsé et de courant différentiel composé. Les ID de Type B et les DD de Type B sont aptes à assurer la protection en cas de courants différentiels résiduels alternatifs sinusoïdaux jusqu'à 1 000 Hz, de courants différentiels résiduels continus pulsés et de courants différentiels résiduels continus lissés. Cette deuxième édition annule et remplace la première édition publiée en 2007 dont elle constitue une révision technique. Les changements par rapport à la première édition sont les suivants:
- des exigences et essais ont été introduits pour le DDR de Type F;
- des exigences et essais ont été introduits pour le DDR à deux pôles de Type B;
- de nouvelles exigences et de nouveaux essais supplémentaires pour les DDR de Type B ont été introduits pour couvrir aussi les exigences et essais pour le Type F.

Odklopniki na preostali tok tipov F in B z vgrajeno nadtokovno zaščito ali brez nje za gospodinjsko in podobno rabo (IEC 62423:2009, spremenjen + popravek dec. 2011)

Na področje uporabe standardov IEC 61008-1 in IEC 61009-1 spadajo tudi naslednji dodatki. Ta standard navaja zahteve in preskuse za zaščitne naprave na preostali (residualni) tok (RCD) tipa F in B. Zahteve in preskusi, ki so podani v tem standardu, so dodatek k zahtevam za zaščitne naprave na preostali (residualni) tok tipa A. Ta standard se lahko uporablja samo skupaj s standardoma IEC 61008-1 in IEC 61009-1. Odklopniki RCCB (odklopniki na preostali (residualni) tok) tipa F in odklopniki RCBO (odklopniki na preostali (residualni) tok z vgrajeno nadtokovno zaščito) z naznačeno frekvenco 50 ali 60 Hz so namenjeni za naprave, kjer so frekvenčni razsmerniki napajani med faznim in nevtralnim ali med faznim in ozemljenim srednjim vodnikom in lahko omogočajo zaščito v primeru, da pride do izmeničnih sinusoidnih residualnih tokov na naznačeni frekvenci, enosmernih utripajočih residualnih tokov in sestavljenih residualnih tokov. Odklopniki RCCB tipa B in odklopniki RCBO tipa B omogočajo zaščito v primeru izmeničnih sinusoidnih residualnih tokov do 1 000 Hz, enosmernih utripajočih residualnih tokov in mehkih enosmernih residualnih tokov. Zaščitne naprave na preostali (residualni) tok v skladu s tem standardom niso namenjene uporabi v enosmerno napajanih sistemih. Nadaljnje zahteve in preskusi za izdelke, ki se uporabljajo v primerih, ko residualni tok ni namenjen obravnavi v standardih IEC 61008-1 in IEC 61009-1, so v obravnavi. Za potrebe izjave proizvajalca ali preverjanja skladnosti bi morali biti tipski preskusi izvedeni v zaporedjih, ki so v skladu z dodatki A, B, C ali D k temu standardu. Popolno zaporedje preskusov za tipski preskus odklopnikov RCCB tipa F in odklopnikov RCBO tipa F je podano v preglednicah A.1 in B.1. Popolno zaporedje preskusov za tipski preskus odklopnikov RCCB tipa B in odklopnikov RCBO tipa B je podano v preglednicah C.1 in D.1.

General Information

Status
Published
Publication Date
01-Jan-2013
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
18-Dec-2012
Due Date
22-Feb-2013
Completion Date
02-Jan-2013

Relations

Buy Standard

Standard
EN 62423:2013 - BARVE
English language
58 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 62423:2013
01-februar-2013
1DGRPHãþD
SIST EN 62423:2009
2GNORSQLNLQDSUHRVWDOLWRNWLSRY)LQ%]YJUDMHQRQDGWRNRYQR]DãþLWRDOLEUH]QMH
]DJRVSRGLQMVNRLQSRGREQRUDER ,(&VSUHPHQMHQSRSUDYHNGHF

Type F and type B residual current operated circuit-breakers with and without integral
overcurrent protection for household and similar uses (IEC 62423:2009, modified +
corrigendum Dec. 2011)
Fehlerstrom-/Differenzstrom-Schutzschalter Typ F und Typ B mit und ohne eingebautem
Überstromschutz für Hausinstallationen und für ähnliche Anwendungen (IEC
62423:2009, modified + corrigendum Dec. 2011) (IEC 62423:2009, modifiziert)
Interrupteurs automatiques à courant différentiel résiduel de type B et de type F avec et
sans protection contre les surintensités incorporée pour usages domestiques et
analogues ( (IEC 62423:2009, modified + corrigendum Dec. 2011)CEI 62423:2009,
modifiée)
Ta slovenski standard je istoveten z: EN 62423:2012
ICS:
29.120.50 9DURYDONHLQGUXJD Fuses and other overcurrent
PHGWRNRYQD]DãþLWD protection devices
SIST EN 62423:2013 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 62423:2013

---------------------- Page: 2 ----------------------

SIST EN 62423:2013

EUROPEAN STANDARD
EN 62423

NORME EUROPÉENNE
December 2012
EUROPÄISCHE NORM

ICS 29.120; 29.120.50 Supersedes EN 62423:2009


English version


Type F and type B residual current operated circuit-breakers with and
without integral overcurrent protection for household and similar uses
(IEC 62423:2009, modified + corrigendum Dec. 2011)


Interrupteurs automatiques à courant Fehlerstrom-/Differenzstrom-
différentiel résiduel de type B et de type F Schutzschalter Typ F und Typ B mit und
avec et sans protection contre les ohne eingebautem Überstromschutz für
surintensités incorporée pour usages Hausinstallationen und für ähnliche
domestiques et analogues Anwendungen
(CEI 62423:2009, modifiée + corrigendum (IEC 62423:2009, modifiziert +
déc. 2011) corrigendum Dez. 2011)





This European Standard was approved by CENELEC on 2012-06-19. CENELEC members are bound to comply
with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the CEN-CENELEC Management Centre or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and notified
to the CEN-CENELEC Management Centre has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus,
the Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany,
Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland,
Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Management Centre: Avenue Marnix 17, B - 1000 Brussels


© 2012 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 62423:2012 E

---------------------- Page: 3 ----------------------

SIST EN 62423:2013
EN 62423:2012 - 2 -

Foreword

This document (EN 62423:2012) consists of the text of IEC 62423:2009 + corrigendum 2011 prepared
by IEC/TC 23E "Circuit-breakers and similar equipment for household use", together with the common
modifications prepared by CLC/TC 23E "Circuit breakers and similar devices for household and similar
applications".


The following dates are fixed:

(dop) 2013-06-19
• latest date by which this document has to be implemented
at national level by publication of an identical
national standard or by endorsement
(dow) 2017-06-19
• latest date by which the national standards conflicting
with this document have to be withdrawn

This document supersedes EN 62423:2009.

EN 62423:2012 includes the following significant technical changes with respect to EN 62423:2009:

– requirements and tests for Type F RCD have been introduced;
– requirements and tests for two-pole Type B RCD have been introduced;
– new additional requirements and tests for Type B RCDs have been introduced to cover
requirements and tests for Type F too.
This European Standard is to be read in conjunction with the following standards:
EN 61008-1:2012, Residual current operated circuit-breakers without integral overcurrent protection
for household and similar uses (RCCBs) – Part 1: General rules
EN 61009-1:2012, Residual current operated circuit-breakers with integral overcurrent protection for
household and similar uses (RCBOs) – Part 1: General rules

Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC [and/or CEN] shall not be held responsible for identifying any or all such
patent rights.

This document has been prepared under a mandate given to CENELEC by the European Commission
and the European Free Trade Association, and supports essential requirements of EU Directive(s).

For the relationship with EU Directive(s) see informative Annex ZZ, which is an integral part of this
document.

Endorsement notice
The text of the International Standard IEC 62423:2009 + corrigendum 2011 was approved by
CENELEC as a European Standard with agreed common modifications.

---------------------- Page: 4 ----------------------

SIST EN 62423:2013
- 3 - EN 62423:2012
COMMON MODIFICATIONS


Clause Common modification
Introduction Delete “with rated frequency 50 Hz or 60 Hz”.
1 Scope Replace the first two paragraphs by :
The scope of EN 61008-1 and EN 61008-2-1 or EN 61009-1 and EN 61009-2-
1 applies with the following additions.
"This standard specifies requirements and tests for Type F and Type B RCDs
(Residual current devices). Requirements and tests given in this standard are
in addition to the requirements of Type A residual current devices according
to EN 61008-2-1 or EN 61009-2-1. This standard can only be used together
with EN 61008-1 and EN 61009-1."
1 In third paragraph, delete “with rated frequency 50 Hz or 60 Hz”.
1 In sixth paragraph, replace “IEC” with “EN”.
1 Add a new paragraph after fourth paragraph:
"Type F and type B RCDs have high resistance against unwanted tripping
even if the surge voltage causes a flashover and a follow-on current occurs
and in case of inrush residual currents with a maximum duration of 10 ms
which can occur in case of switching ON electronic equipment or EMC-
filters."
1 Delete the seventh paragraph.
1 Modify note 2 by:
“Note 2 : deleted”
2 Replace the contents of Clause 2 with: “Normative references to
international publications are listed in Annex ZA.”
5.2.3 Delete the value "60 Hz" three times: in the title of 5.2.3, in the title of
Table 2 and in note 4 of Table 2.
9.2.1.1 Delete the third paragraph in 9.2.1.1.
9.2.1.2 b) Replace last paragraph by:
The maximum break time shall not exceed 0,3 s for general type RCDs and
for S-type RCDs the maximum break time shall not exceed 0,5 s.
9.2.1.7.1 Add a note after the first paragraph in 9.2.1.7.1 :
Note: The open circuit voltage of the DC source should be high enough to guarantee
stable smooth d.c. current (e.g. more than 24 V).
9.2.2 Delete the paragraph before the note.
Figure 2 Delete “or 60 Hz”.
Annexes A, B, See modified Annexes A to D at the end of the document (modifications in
C and D red).
Annex ZA See new Annex ZA at the end of this document.

---------------------- Page: 5 ----------------------

SIST EN 62423:2013
EN 62423:2012 - 4 -
Annex A
(normative)

Number of samples to be submitted and test sequences
to be applied for verification of conformity for type F RCCBs

Verification of conformity may be made
– by the manufacturer for the purpose of suppliers declaration (13.5.1 of ISO/IEC Guide 2);
– by an independent body for certification (13.5.2 of ISO/IEC Guide 2).
According to the terminology of ISO/IEC Guide 2 the term "certification" can be used for the
second case only.
The tests are made according to Table A.1 below, where the tests in each sequence are
carried out in the order indicated.
The sampling procedure is given in A.2 and A.3 of EN 61008-1:2012 .
Table A.1 – Test sequences for Type F RCCBs
Test Tests according to Additional tests Test (or Inspection)
sequence EN 61008-1 and according to this

EN 61008-2-1 standard
6 6 Marking
8.1.1 No General
No
8.1.2 Mechanism
No
9.3 Indelibility of marking
No
8.1.3 Clearance and creepage distances (external parts only)
No
9.15 Trip-free mechanism
No
Reliability of screws, current-carrying parts and
9.4
connections
A
No
9.5 Reliability of terminals for external conductors
No
9.6 Protection against electric shock
No
9.13.1
No
Resistance to heat
9.13.2
9.13.3
No
8.1.3 Clearances and creepage distances (internal parts)
No
9.14 Resistance to abnormal heat and to fire
No
9.7 Test of dielectric properties
No
9.8 Temperature rise
No
B 9.20 Resistance of insulation against impulse voltages
No
9.22.2 Reliability at 40 °C
No
9.23 Ageing of electronic components
No
C 9.10 Mechanical and electrical endurance
9.9 Residual operating characteristics
Verification of the correct operation in case of a steady
9.1.2
D increase of composite residual current
0

Verification of the correct operation in case of sudden
9.1.3
D
appearance of composite residual current
9.17 No Behaviour in the case of failure of the line voltage
D 9.1.5
1
Unwanted tripping
9.19
Behaviour in the case of surge currents

---------------------- Page: 6 ----------------------

SIST EN 62423:2013
- 5 - EN 62423:2012
9.1.6
…… Behaviour in the case of inrush residual currents
9.1.4
Correct operation for RCD powered on two poles only
9.1.7
9.21.4 Type A residual current devices
No
9.11.2.3 a) and b) Performance at I
∆m
No
9.16 Test device
No
9.12 Resistance to mechanical shock and impact
9.18 No Non-operating current under overcurrent conditions
No
D 9.11.2.3 c) Verification of the suitability in IT system
2
No
9.11.2.4 a) Coordination at I
nc
E
No
9.11.2.2 Performance at I
m
No
9.11.2.4 b) Coordination at I
m
F
No
9.11.2.4 c) Coordination at I
∆c
No
9.22.1 Reliability (climatic tests)
G
0
Verification of correct operation at low ambient air temperature
G 9.Z1 No
1
of RCCBs for use in the range of .-25 °C to +40 °C
No
EN 61543:1995, Table 4 Harmonics, interharmonics
-T1.1
Signalling voltage
EN 61543:1995, Table 4
a
Conducted unidirectional transients of the ms and µs time
H
-T1.2
scale
EN 61543:1995, Table
5 -T2.3
No Conducted oscillatory voltages or currents
EN 61543:1995, Table 5
Radiated high-frequency phenomena
-T2.1
Conducted unidirectional transients of the ns time scale
EN 61543:1995, Table 5
I (burst)
-T2.5
EN 61543:1995, Table
5 -T2.2
No
EN 61543:1995, Table
Conducted common mode disturbances in the frequency range
5 -T2.6
lower than 150 kHz
J
EN 61543:1995, Table
Electrostatic discharges
6 -T3.1
a
For devices containing a continuously operating oscillator, the test of CISPR 14-1 shall be carried out on the samples prior to the
tests of this sequence.

---------------------- Page: 7 ----------------------

SIST EN 62423:2013
EN 62423:2012 - 6 -
Annex B
(normative)

Number of samples to be submitted and test sequences
to be applied for verification of conformity for Type F RCBOs

Verification of conformity may be made
– by the manufacturer for the purpose of suppliers declaration (13.5.1 of ISO/IEC Guide 2);
– by an independent body for certification (13.5.2 of ISO/IEC Guide 2).
According to the terminology of ISO/IEC Guide 2 the term "certification" can be used for the
second case only.
The tests are made according to Table B.1 below, where the tests in each sequence are
carried out in the order indicated.
The sampling procedure is given in A.2 and A.3 of EN 61009-1:2012.
Table B.1 – Test sequences for Type F RCBOs
Test Tests according to Additional tests Test (or Inspection)
sequence EN 61009-1 and according to this

EN 61009-2-1 standard
6 6 Marking
8.1.1 No General
8.1.2 No Mechanism
9.3 No Indelibility of marking
8.1.3 No Clearance and creepage distances (external parts only)
8.1.6 No Non-interchangeability
9.11 No Trip-free mechanism
Reliability of screws, current-carrying parts and
A
9.4 No
connections
9.5 No Reliability of terminals for external conductors
9.6 No Protection against electric shock
9.14.1 No
Resistance to heat
9.14.2
No
9.14.3
8.1.3 No Clearances and creepage distances (internal parts)
9.15 No Resistance to abnormal heat and to fire
9.7 No Dielectric properties
9.8 No Temperature rise
B
9.20 No Resistance of insulation against impulse voltages
9.22.2 No Reliability at 40 °C
9.23 No Ageing of electronic components
9.10 No Mechanical and electrical endurance
C
1 9.12.11.2.1
Performance at reduced short-circuit currents
No
(and 9.12.12) (Verification of the RCBO after the short-circuit tests)
C
No
Short-circuit test for verifying the suitability of RCBOs for
9.12.11.2.2
use in IT systems
C
2
(and 9.12.12)
(Verification of the RCBO after the short-circuit tests)
Operating characteristics under residual current
D D 9.9.1
0
conditions

---------------------- Page: 8 ----------------------

SIST EN 62423:2013
- 7 - EN 62423:2012
Verification of the correct operation in case of a steady
9.1.2
increase of composite residual current

Verification of the correct operation in case of sudden
9.1.3
appearance of composite residual current
9.17 No Behaviour in the case of failure of the line voltage
9.1.5
Unwanted tripping
9.19

Behaviour in the case of surge currents.
9.1.6
… Behaviour in the case of inrush residual currents
D
1
9.1.4
Correct operation for RCD powered on two poles only
9.1.7
9.21.1 Type A residual current devices
No
9.12.13 Performance at I
∆m
No
9.16 Test device
No
9.9.2 Overcurrent operating characteristics
E No
0
Limiting value of overcurrent in case of a single-phase load
9.18
through a 3-pole or 4-pole RCBO
E
No
9.13 Resistance to mechanical shock and impact
E
1
No
9.12.11.3 (and 9.12.12) Short-circuit performance at 1 500 A
No
F 9.12.11.4 b) (and 9.12.12) Performance at service short-circuit capacity
0
No
F 9.12.11.4 c) (and 9.12.12.2) Performance at rated short-circuit capacity
F 1

No
9.12.11.4 d)
Performance at I
∆m
F
2
(and 9.12.12.2) (Verification of RCBO after short-circuit test)
No
9.22.1 Reliability (climatic tests)
G
0
G
Verification of correct operation at low ambient air temperature of
G1 9.Z1 No
RCBOs for use in the range of .-25 °C to +40 °C
No
IEC 61543:1995, Table 4 - Harmonics, interharmonics
T1.1
Signalling voltage

IEC 61543:1995, Table 4 -
Conducted unidirectional transients of the ms and µs time scale
a
H
T1.2
IEC 61543:1995, Table 5 -
T2.3
No
IEC 61543:1995, Table 5 - Conducted sine-wave voltages or currents
T2.1
Radiated high-frequency phenomena
IEC 61543:1995, Table 5 -
Fast Conducted unidirectional transients of the ns time
I
T2.5
scale (burst)
IEC 61543:1995, Table 5 -
T2.2
No
IEC 61543:1995, Table 5 - Conducted common mode disturbances in the frequency
T2.6 range lower than 150 kHz
J
Electrostatic discharges
IEC 61543:1995, Table 6 -
T3.1
a) For devices containing a continuously operating oscillator, the test of CISPR 14-1 shall be carried out on the samples
prior to the tests of this sequence.

---------------------- Page: 9 ----------------------

SIST EN 62423:2013
EN 62423:2012 - 8 -
Annex C
(normative)

Number of samples to be submitted and test sequences
to be applied for verification of conformity for Type B RCCBs

Verification of conformity may be made
– by the manufacturer for the purpose of suppliers declaration (13.5.1 of ISO/IEC Guide 2);
– by an independent body for certification (13.5.2 of ISO/IEC Guide 2).
According to the terminology of ISO/IEC Guide 2 the term "certification" can be used for the
second case only.
The tests are made according to Table C.1 below, where the tests in each sequence are
carried out in the order indicated.
The sampling procedure is given in A.2 and A.3 of EN 61008-1:2012.
Table C.1 – Test sequences for Type B RCCBs
Test Tests according to Additional tests Test (or inspection)
sequence EN 61008-1 and according to
EN 61008-2-1 this standard
6 6 Marking
8.1.1 No General
8.1.2 No Mechanism
9.3 No Indelibility of marking
8.1.3 No Clearance and creepage distances (external parts only)
9.15 No Trip-free mechanism
9.4 No Reliability of screws, current-carrying parts and connections
A
9.5 No Reliability of terminals for external conductors
9.6 No Protection against electric shock
Verification of the RCD after
9.13.1 9.2.4
test sequence
Resistance to heat
9.13.2
No
9.13.3
8.1.3 No Clearances and creepage distances (internal parts)
9.14 No Resistance to abnormal heat and to fire
9.7 No Test of dielectric properties
9.8 No Temperature rise
9.20 No Resistance of insulation against impulse voltages
B
9.22.2 No Reliability at 40 °C
9.23 No Ageing of electronic components
-- 9.2.4 Verification of the RCD after test sequence
9.10 No Mechanical and electrical endurance
C
-- 9.2.4 Verification of the RCD after test sequence
9.9 No Residual operating characteristics
Verification of the correct operation in case of a steady
9.1.2
D D0 increase of composite residual current
Verification of the correct operation in case of sudden
9.1.3
appearance of composite residual current

---------------------- Page: 10 ----------------------

SIST EN 62423:2013
- 9 - EN 62423:2012
Verification of the correct operation in case of residual
smooth direct current without load for ratings of I not tested
9.2.1.7.1 ∆n
in D
1
9.17 No Behaviour in the case of failure of the line voltage
9.19 9.1.5 Unwanted tripping
Behaviour in the case of surge currents
9.1.6 Behaviour in the case of inrush residual currents
9.1.4 Correct operation for RCD powered on two poles only
9.2.3 Correct operation for RCD powered on two poles only
a
9.21.1 9.1.7 Type A residual current devices
D
1
9.2.1 Type B residual current devices

9.2.2 Tests at temperature limits
No Performance at I
9.11.2.3 a) and b)
∆m
9.16 No Test device
9.12 No Resistance to mechanical shock and impact
9.18 No Non-operating current under overcurrent conditions
-- 9.2.4 Verification of the RCD after test sequence
9.11.2.3 c) No Verification of the suitability in IT system
D2
-- 9.2.4 Verification of the RCD after test sequence
No Coordination at I
9.11.2.4 a)
nc
E No Performance at I
9.11.2.2
m
-- 9.2.4 Verification of the RCD after test sequence
No Coordination at I
9.11.2.4 b)
m
F No Coordination at I
9.11.2.4 c)
∆c
-- 9.2.4 Verification of the RCD after test sequence
9.22.1 No Reliability (climatic tests)
G
0
-- 9.2.4 Verification of the RCD after test sequence
Verification of correct operation at low ambient air temperature of
9.Z1 No
RCCBs for use in the range of .-25 °C to +40 °C
G
1
9.2.4 Verification of the RCD after test sequence
No
EN 61543:1995, Harmonics, interharmonics
Table 4 -T1.1
Signalling voltage
EN 61543:1995,
b
Conducted unidirectional transients of the ms and µs time
H
Table 4 -T1.2
scale
EN 61543:1995,
Table 5 -T2.3
EN 61543:1995, No Conducted oscillatory voltages or currents
Table 5 -T2.1
Radiated high-frequency phenomena
EN 61543:1995,Table
Conducted unidirectional transients of the ns time scale
I
5 -T2.5
(burst)
EN 61543:1995,
Table 5 -T2.2
EN 61543:1995, No
Conducted common mode disturbances in the frequency range
Table 5 -T2.6
lower than 150 kHz
J
EN 61543:1995,
Electrostatic discharges
Table 6 –T3.1
a
For devices having different residual current detection systems, for which the test according to 9.21.1 was made
without supply voltage, an additional test according to 9.21.1.1 shall be made with a supply voltage of 1,1 U to verify
n
that there is no interference between the different systems. Only the lower limits of the tripping currents are verified.
b
For devices containing a continuously operating oscillator, the test of CISPR 14-1 shall be carried out on the samples
prior to the tests of this sequence.

---------------------- Page: 11 ----------------------

SIST EN 62423:2013
EN 62423:2012 - 10 -
Annex D
(normative)

Number of samples to be submitted and test sequences
to be applied for verification of conformity for Type B RCBOs

Verification of conformity may be made
– by the manufacturer for the purpose of suppliers declaration (13.5.1 of ISO/IEC Guide 2);
– by an independent body for certification (13.5.2 of ISO/IEC Guide 2).
According to the terminology of ISO/IEC Guide 2 the term "certification" can be used for the
second case only.
The tests are made according to Table D.1 below, where the tests in each sequence are
carried out in the order indicated.
The sampling procedure is given in A.2 to A.5 of EN 61009-1:2012.

Table D.1 – Test sequences for Type B RCBOs
Test Tests according to Additional tests Test (or Inspection)
sequence EN 61009-1 and according to

EN 61009-2-1 this standard
6 6 Marking
8.1.1 No General
8.1.2 No Mechanism
9.3 No Indelibility of marking
8.1.3 No Clearance and creepage distances (external parts only)
8.1.6 No Non-interchangeability
9.11 No Trip-free mechanism
9.4 No Reliability of screws, current-carrying parts and connections
A
9.5 No Reliability of terminals for external conductors
9.6 No Protection against electric shock
Verification of the RCD
9.14.1 9.2.4
after test sequence
Resistance to heat
9.14.2
No
9.14.3
8.1.3 No Clearances and creepage distances (internal parts)
9.15 No Resistance to abnormal heat and to fire
9.7 No Dielectric properties
9.8 No Temperature rise
9.20 No Resistance of insulation against impulse voltages
B
9.22.2 No Reliability at 40 °C
9.23 No Ageing of electronic components
-- 9.2.4 Verification of the RCD after test sequence
9.10 No Mechanical and electrical endurance
-- 9.2.4 Verification of the RCD after test sequence
C C
1
9.12.11.2.1 Performance at reduced short-circuit currents
No
(and 9.12.12) (Verification of the RCBO after the short-circuit tests)

---------------------- Page: 12 ----------------------

SIST EN 62423:2013
- 11 - EN 62423:2012
Short-circuit test for verifying the suitability of RCBOs for use
9.12.11.2.2
in IT systems
C No
2
(and 9.12.12)
(Verification of the RCBO after the short-circuit tests)
9.9.1 No Operating characteristics under residual current conditions
Verification of the correct operation in case of a steady
9.1.2
increase of composite residual current
Verification of the correct operation in case of sudden
D 9.1.3
0
appearance of composite residual current
Verification of the correct operation in case of residual
smooth direct current without load for ratings of I not tested
9.2.1.7.1 ∆n
in D
1
9.17 No Behaviour in the case of failure of the line voltage
9.19 9.1.5 Behaviour in the case of surge currents
D
9.1.6 Behaviour in the case of inrush residual currents
9.1.4 Correct operation for RCD powered on two poles only
9.2.3 Correct operation for RCD powered on two poles only
a
9.21.1 9.1.7 Type A residual current devices
D
1
9.2.1 Type B residual current devices

9.2.2 Tests at temperature limits
No Performance at I
9.12.13
∆m
9.16 No Test device
-- 9.2.4 Verification of the RCD after test sequence
9.9.2 No Overcurrent operating characteristics
E
0
No Limiting value of overcurrent in case of a single-phase load
9.18
through a 3-pole or 4-pole RCBO
9.13 No Resistance to mechanical shock and impact
E
1
9.12.11.3 (and 9.12.12) No Short-circuit performance at 1 500 A
9.12.11.4 b)
No
F Performance at service short-circuit capacity
0
(and 9.12.12)
9.12.11.4 c)
No
F Performance at rated short-circuit capacity
1
(and 9.12.12.2)
No
9.12.11.4 d) Performance at I
∆m
F
2
(and 9.12.12.2) (Verification of RCBO after short-circuit test)
9.22.1 No Reliability (climatic tests)
G
0
-- 9.2.4 Verification of the RCD after test sequence
Verification of correct operation at low ambient air temperature of
9.Z1 No
RCBOs for use in the range of .-25 °C to +40 °C
G
1
9.2.4 Verification of the RCD after test sequence
EN 61543:1995, Table 4 No
-T1.1
Harmonics, interharmonics
Signalling voltage
b EN 61543:1995, Table 4
H
-T1.2
Conducted unidirectional transients of the ms and µs time
scale
EN 61543:1995 Table
5 -T2.3
No
EN 61543:1995, Table 5 Conducted oscillatory voltages or currents
-T2.1 Radiated high-frequency phenomena
EN 61543:1995, Table 5 Conducted unidirectional transients of the ns time scale
I
(burst)
-T2.5
EN 61543:1995, Table
5 -T2.2
EN 61543:1995, Table No Conducted common mode disturbances in the frequency range
5 -T2.6 lower than 150 kHz
J
EN 61543:1995, Table
Electrostatic discharges
6 –T3.1

---------------------- Page: 13 ----------------------

SIST EN 62423:2013
EN 62423:2012 - 12 -
a
For devices having different residual current detection systems, for which the test according to 9.21.1 was made
without supply voltage, an additional test according to 9.21.1.1 shall be made with a supply voltage of 1,1 U to verify
n
that there is no interference between the different systems. Only the lower limits of the tripping currents are verified.
b
For devices containing a continuously operating oscillator, the test of CISPR 14-1 shall be carried out on the samples
prior to the tests of this sequence.

---------------------- Page: 14 ----------------------

SIST EN 62423:2013
- 13 - EN 62423:2012
Annex ZA
(normative)

Normative references to international publications
with their corresponding European publications

The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any amendments) applies.

NOTE  When an international publication has been modified by common modifications, indicated by (mod), the relevant EN/HD
applies.

Publication Year Title EN/HD Year

CISPR 14-1 2005 Electromagnetic compatibility - EN 55014-1 2006
+ corr. January 2009 Requirements for household appliances,
electric tools and similar apparatus -
Part 1: Emission


IEC/TS 60479-1 - Effects of current on human beings and - -
livestock -
Part 1: General aspects


IEC/TS 60479-2 - Effects of current on human beings and - -
livestock -
Part 2: Special aspects


IEC 61008 Series Residual current operated circuit-breakers EN 61008 Series
without integral overcurrent protection for
household and similar uses (RCCB's)


IEC 61009 Series Residual current operated circuit-breakers EN 61009 Series
with integral overcurrent protection for
household and similar uses (RCBO's)


IEC 61543 1995 Residual current-operated protective devices EN 61543 1995
(RCDs) for household and similar use - + corr. December 1997
Electromagnetic compatibility + A12 2005

---------------------- Page: 15 ----------------------

SIST EN 62423:2013
EN 62423:2012 - 14 -
Annex ZB
(normative)

Special national conditions

Special national condition: National characteristic or practice that cannot be changed even over a
long period, e.g. climatic conditions, electrical earthing conditions.

NOTE  If it affects harmonization, it forms part of the European Standard / Harmonization Document.

For the countries in which the relevant special national conditions apply these provisions are
normative, for other countries they are informative.

Clause Special national condition
The Netherlands
Scope Add the following:
This standard together with these requirements apply for 2 pole type B RCD for use in TN
and TT distribution systems for protection of line and neutral circuits (L-N).
Modify note 2 reading: additional requirements for 1 pole devices for use in TN-S or TN-
C-S systems and 2 pole devices (L-L) for use between phases are under consideration
3.2
Modify as follows
3.2 residual current devices for which tripping is ensured as for type A according to
EN 61008-1 or EN 61009-1, as applicable, and in addition for the following residual
currents:
3.2.1 Type B residual current devices with 3 or 4 poles
Existing text
3.2.2 Type B residual current devices with 2 poles
Residual current devices for which tripping is ensured as for RCD type A according
EN 61008-1 or EN 61009-1, as applicable , and in addition:
- for residual sinusoidal alternating currents up to 1 000 Hz,
- for residual pulsating direct currents,
- for residual alternating currents superimposed on a smooth direct current,
- for residual pulsating rectified d.c which results from 2 phases,
- for residual d.c currents that may result from inverter circuits.
NOTE The above 5th dash refers to fault conditions in micro generato
...