IEC 61000-2-4:2002/COR1:2014
(Corrigendum)Corrigendum 1 - Electromagnetic compatibility (EMC) - Part 2-4: Environment - Compatibility levels in industrial plants for low-frequency conducted disturbances
Corrigendum 1 - Electromagnetic compatibility (EMC) - Part 2-4: Environment - Compatibility levels in industrial plants for low-frequency conducted disturbances
Corrigendum 1 - Compatibilité électromagnétique - Partie 2-4: Environnement - Niveaux de compatibilité dans les installations industrielles pour les perturbations conduites à basse fréquence
General Information
Relations
Buy Standard
Standards Content (Sample)
IEC 61000-2-4 IEC 61000-2-4
(Second edition – 2002) (Deuxième édition – 2002)
Electromagnetic compatibility (EMC) Compatibilité électromagnétique (CEM) –
Part 2-4: Environment – Compatibility levels in Partie 2-4: Environnement – Niveaux de
industrial plants for low-frequency conducted compatibilité dans les installations industrielles
disturbances pour les perturbations conduites à basse
fréquence
CO RRI G E NDUM 1
This correction to the third column of Tableau 3
...
This May Also Interest You
IEC 61000-2-4:2024 is related to conducted disturbances in the frequency range from 0 kHz to 150 kHz. It gives compatibility levels in differential mode (L-L and L-N) for industrial locations, with a nominal voltage up to 35 kV and a nominal frequency of 50 Hz or 60 Hz.
NOTE 1 Industrial locations are defined in 3.1.8.
Power distribution systems on ships, aircraft, offshore platforms and railways are not included.
NOTE 2 See also Annex E. The compatibility levels specified in this document apply at the in-plant point of coupling (IPC). The level of the low-frequency disturbances at the terminals of equipment receiving its supply from the IPC is generally assumed to be similar to the disturbance level at the IPC itself. However, in some situations this is not the case, particularly when a long feeder is dedicated to the supply of a particular load, or when a disturbance is generated or amplified within the installation of which the equipment forms a part.
Compatibility levels are specified for the types of low-frequency electromagnetic disturbances expected at any in-plant point of coupling (IPC) within industrial locations, for guidance in the definition of:
a) limits for disturbance emissions in industrial power distribution systems (including the planning levels defined in 3.1.5);
NOTE 3 A very wide range of conditions is possible in the electromagnetic environments of industrial networks. These are approximated in this document by the three classes described in Clause 4. However, it is the responsibility of the operator of such a network to take account of the particular electromagnetic and economic conditions, including equipment characteristics, in setting the above-mentioned limits.
b) immunity levels for the equipment within these systems.
The disturbance phenomena considered are:
- voltage deviations;
- voltage dips and short interruptions;
- voltage imbalance;
- power-frequency variations;
- harmonics up to order 40;
- interharmonics up to the 40th harmonic;
- voltage components above the 40th harmonic up to 150 kHz;
- DC component;
- transient overvoltages.
The compatibility levels are given for different classes of environment determined by the characteristics of the supply network and loads.
NOTE 4 Compatibility levels at the point of common coupling (PCC) on public networks are specified in IEC 61000‑2‑2 for low-voltage networks and IEC 61000‑2‑12 for medium-voltage networks. IEC TR 61000‑3‑6 and IEC TR 61000‑3‑7 describe the approach of power distribution system operators to the limitation of emissions from installations and large loads.
This third edition cancels and replaces the second edition published in 2002. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition:
a) introduction of new classes 2a, 2b and 2L (former class 2);
b) modification of existing compatibility levels for class 3;
c) addition of compatibility levels in the frequency range 2 kHz to 150 kHz;
d) addition of compatibility levels using a new quantity: partial weighted harmonic distortion (PWHD).
- Standard150 pagesEnglish languagesale 15% off
- Standard96 pagesEnglish and French languagesale 15% off
IEC 61000-4-7:2002+A1:2008 applies to instrumentation intended for measuring spectral components in the frequency range up to 9 kHz which are superimposed on the fundamental of the power supply systems at 50 Hz and 60 Hz. For practical considerations, this standard distinguishes between harmonics, interharmonics and other components above the harmonic frequency range, up to 9 kHz. Defines the measurement instrumentation intended for testing individual items of equipment in accordance with emission limits given in certain standards (for example, harmonic current limits as given in IEC 61000-3-2) as well as for the measurement of harmonic currents and voltages in actual supply systems. The contents of the corrigendum of July 2004 have been included in this copy. This consolidated version consists of the second edition (2002) and its amendment 1 (2008). Therefore, no need to order amendment in addition to this publication.
- Standard82 pagesEnglish and French languagesale 15% off
Applies to instrumentation intended for measuring spectral components in the frequency range up to 9 kHz which are superimposed on the fundamental of the power supply systems at 50 Hz and 60 Hz. For practical considerations, this standard distinguishes between harmonics, interharmonics and other components above the harmonic frequency range, up to 9 kHz. Defines the measurement instrumentation intended for testing individual items of equipment in accordance with emission limits given in certain standards (for example, harmonic current limits as given in IEC 61000-3-2) as well as for the measurement of harmonic currents and voltages in actual supply systems. The contents of the corrigendum of July 2004 have been included in this copy.
- Standard36 pagesEnglish languagesale 15% off
- Standard36 pagesFrench languagesale 15% off
- Standard71 pagesEnglish and French languagesale 15% off
- Standard82 pagesEnglish and French languagesale 15% off
- Standard46 pagesEnglish and French languagesale 15% off
- Standard10 pagesEnglish and French languagesale 15% off
IEC 61000-2-4:2002 is concerned with conducted disturbances in the frequency range from 0 kHz to 9 kHz. It gives numerical compatibility levels for industrial and non-public power distribution systems at nominal voltages up to 35 kV and a nominal frequency of 50 Hz or 60 Hz. Compatibility levels are specified for electromagnetic disturbances of the types which can be expected at any in-plant point of coupling within industrial plants or other non-public networks, for guidance in a) limits to be set for disturbance emission into industrial power supply systems; b) the choice of immunity levels for the equipment within these systems. The contents of the corrigendum of July 2014 have been included in this copy.
- Standard75 pagesEnglish and French languagesale 15% off
IEC 61000-2-4:2024 is related to conducted disturbances in the frequency range from 0 kHz to 150 kHz. It gives compatibility levels in differential mode (L-L and L-N) for industrial locations, with a nominal voltage up to 35 kV and a nominal frequency of 50 Hz or 60 Hz.
NOTE 1 Industrial locations are defined in 3.1.8.
Power distribution systems on ships, aircraft, offshore platforms and railways are not included.
NOTE 2 See also Annex E. The compatibility levels specified in this document apply at the in-plant point of coupling (IPC). The level of the low-frequency disturbances at the terminals of equipment receiving its supply from the IPC is generally assumed to be similar to the disturbance level at the IPC itself. However, in some situations this is not the case, particularly when a long feeder is dedicated to the supply of a particular load, or when a disturbance is generated or amplified within the installation of which the equipment forms a part.
Compatibility levels are specified for the types of low-frequency electromagnetic disturbances expected at any in-plant point of coupling (IPC) within industrial locations, for guidance in the definition of:
a) limits for disturbance emissions in industrial power distribution systems (including the planning levels defined in 3.1.5);
NOTE 3 A very wide range of conditions is possible in the electromagnetic environments of industrial networks. These are approximated in this document by the three classes described in Clause 4. However, it is the responsibility of the operator of such a network to take account of the particular electromagnetic and economic conditions, including equipment characteristics, in setting the above-mentioned limits.
b) immunity levels for the equipment within these systems.
The disturbance phenomena considered are:
- voltage deviations;
- voltage dips and short interruptions;
- voltage imbalance;
- power-frequency variations;
- harmonics up to order 40;
- interharmonics up to the 40th harmonic;
- voltage components above the 40th harmonic up to 150 kHz;
- DC component;
- transient overvoltages.
The compatibility levels are given for different classes of environment determined by the characteristics of the supply network and loads.
NOTE 4 Compatibility levels at the point of common coupling (PCC) on public networks are specified in IEC 61000‑2‑2 for low-voltage networks and IEC 61000‑2‑12 for medium-voltage networks. IEC TR 61000‑3‑6 and IEC TR 61000‑3‑7 describe the approach of power distribution system operators to the limitation of emissions from installations and large loads.
This third edition cancels and replaces the second edition published in 2002. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition:
a) introduction of new classes 2a, 2b and 2L (former class 2);
b) modification of existing compatibility levels for class 3;
c) addition of compatibility levels in the frequency range 2 kHz to 150 kHz;
d) addition of compatibility levels using a new quantity: partial weighted harmonic distortion (PWHD).
- Standard150 pagesEnglish languagesale 15% off
- Standard96 pagesEnglish and French languagesale 15% off
- Standard18 pagesEnglish and French languagesale 15% off
- Standard22 pagesEnglish and French languagesale 15% off
CISPR 36:2020 defines limits for 3 m measurement distance and methods of measurement that are designed to provide protection for off-board receivers (at 10 m distance) in the frequency range of 150 kHz to 30 MHz when used in the residential environment.
NOTE Protection of receivers used on board the same vehicle as the disturbance source(s) is covered by CISPR 25.
This document applies to the emission of electromagnetic energy which might cause interference to radio reception and which is emitted from electric and hybrid electric vehicles propelled by an internal traction battery (see 3.2 and 3.3) when operated on the road. This document applies to vehicles that have a traction battery voltage between 100 V and 1 000 V.
Electric vehicles to which CISPR 14-1 applies are not in the scope of this document. This document applies only to road vehicles where an electric propulsion is used for sustained speed of more than 6 km/h. Vehicles where the electric motor is only used to start up the internal combustion engine (e.g. "micro hybrid") and vehicles where the electric motor is used for additional propulsion only during acceleration (e.g. "48 V mild hybrid vehicles") are not in the scope of this document. The radiated emission requirements in this document are not applicable to the intentional transmissions from a radio transmitter as defined by the ITU including their spurious emissions. Annex C lists work being considered for future revisions.
- Standard48 pagesEnglish and French languagesale 15% off
- Standard104 pagesEnglish and French languagesale 15% off
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.